Input register
VRV
Sky
-air
H
RV
Sp
lit
VRV
h
yd
ro
b
o
x
LT
&
H
T
Air cu
rta
in
s
ERQ
con
tro
l b
o
x
H
eat
in
g
Ap
p
lie
d
Room temperature
Suction temperature of indoor units
(or user interface sensor
temperature)
* Split: KRP928BB2S is required
O
O
-
O*
O
-
O
O
-
32005 (1-00)
32011 (1-01)
.. (step of 6)
32383 (4-15)
Bit
Description
Meaning
15..0 Room
temperature
- 511,9 ..
511,9°C
(unity: 0,1°C)
16 bit signed integer equals the value multiplied by 10
(bit 15= sign)
Additional notes concerning the room temperature Or Suction temperature.
By default the Suction temperature value is applicable.
If the room temperature of the user interface (e.g. BRC1E52A/B7 or BRC2/3E52C7) is required, following
settings should be confirmed on the user interface:
Mode No.
–
First Code
No.
( ) = group
setting
Description of setting
Required values:
User interface settings (e.g. BRC1E52A/B7 or BRC2/3E52C7)
1c
–
1
Thermostat sensor used for the
"Auto" operation mode and the
Setback function (room temperature on detailed
display).
Value 02:
Remote controller
thermistor
Unit settings
10 (20)
–
2
Thermostat sensor in the remote
controller
Value 03:
Use exclusively
10 (20)
–
5
Sensor value information to DIII devices
Value 02:
Sensor value as
set by 10-2-0X or 10-6-0X.
10 (20)
–
6
Thermostat sensor in group
control
Value 02:
Use both the unit sensor (or
remote sensor if installed) AND
the remote controller sensor.
For more information, refer to the installation manual of applicable indoor unit.