4P642495-1A
–
2022.02
Page
24
of
52
Input register
VRV
Sky
-air
H
RV
Sp
lit
VRV h
yd
ro
b
o
x
LT
&
H
T
Air cu
rta
in
s
ERQ
con
tro
l b
o
x
H
eat
in
g
Ap
p
lie
d
Leaving water set
point range
Leaving water set point range cooling
and heating
-
-
-
-
O
-
-
O
O
31402 (1-00)
31406 (1-01)
.. (step of 4)
31654 (4-15)
Bit
Description
Meaning
15..8 Unit cooling
water set
point upper
limit
- 128 .. 127°C
(unity 1°C)
8 bit signed integer
(bit 15= sign)
7..0
Unit cooling
water set
point lower
limit
- 128 .. 127°C
(unity 1°C)
8 bit signed integer
(bit 7= sign)
31403 (1-00)
31407 (1-01)
.. (step of 4)
31655 (4-15)
15..8 Unit
heating
water set
point upper
limit
- 128 .. 127°C
(unity 1°C)
8 bit signed integer
(bit 15= sign)
7..0
Unit
heating
water set
point lower
limit
- 128 .. 127°C
(unity 1°C)
8 bit signed integer
(bit 7= sign)
(Note: Unit set point range is depending on unit e.g. 5 till 20°C.
In some user interfaces, it is possible to change the set point range towards the user e.g. 10 till 15°C.
But these values are independent from the unit set point range. Meaning unit set point range values are not
modified. E.g. 5 till 20°C)