4 Unit installation

Installation manual

9

EKHWET90~120BAV3
R32 Split series – Domestic hot water tank
4P680074-1 – 2021.11

A

nv-min

 (dm²) – In case of Refrigerant charge=2.6 kg

Release height (m)

Floor area of room A (m²) [! NOT room A + room B !]

2,00

4,00

6,00

8,00

10,00

12,00

14,00

2.45

4,1

2,1

0,2

(*)

(*)

(*)

(*)

2.65

3,7

1,6

(*)

(*)

(*)

(*)

(*)

1.85

3,3

1,2

(*)

(*)

(*)

(*)

(*)

2.05

3,0

0,7

(*)

(*)

(*)

(*)

(*)

2.25

2,7

0,4

(*)

(*)

(*)

(*)

(*)

PATTERN 3

PATTERN  3  is  only  allowed  for  installations  in  technical  rooms  (i.e.
room that is NEVER occupied by persons). For this pattern there are
no requirements to the minimum floor area if you provide 2 openings
(one  at  the  bottom,  one  at  the  top)  between  the  room  and  the
outside  to  ensure  natural  ventilation.  The  room  must  be  protected
from frost.

Anv 

(≥A

nv-min

)

Min. 50% of A

nv-min

a2

a1

A

A

Unoccupied room where the indoor unit is installed.

Must be protected from frost.

a1

A

nv

Bottom opening

 for natural ventilation between the

unoccupied room and the outside.

▪ Must be a permanent opening that cannot be closed.

▪ Must be above ground level.

▪ Must be completely located between 0 and 300 mm from

the floor of the unoccupied room.

▪ Must  be  ≥A

nv-min

  (minimum  bottom  opening  area  as

specified in the table below).

▪ ≥50%  of  the  required  opening  area  A

nv-min

  must  be

≤200 mm from the floor of the unoccupied room.

▪ The  bottom  of  the  opening  must  be  ≤100  mm  from  the

floor of the unoccupied room.

▪ If  the  opening  starts  from  the  floor,  the  height  of  the

opening must be ≥20 mm.

a2

Top opening

 for natural ventilation between room A and

the outside.

▪ Must be a permanent opening that cannot be closed.

▪ Must  be  ≥50%  of  A

nv-min

  (minimum  bottom  opening  area

as specified in the table below).

▪ Must be ≥1.5 m from the floor of the unoccupied room.

A

nv-min

 (minimum bottom opening area for natural ventilation)

The  minimum  bottom  opening  area  for  natural  ventilation  between
the  unoccupied  room  and  the  outside  depends  on  the  total
refrigerant  in  the  system.  For  intermediate  refrigerant  charges,  use
the  row  with  the  higher  value. 

Example: 

If  the  refrigerant  charge  is

2.55 kg, use the row of 2.6 kg.

Total refrigerant charge (kg)

A

nv-min

 (dm²)

2.20

7.5

2.30

7.7

Total refrigerant charge (kg)

A

nv-min

 (dm²)

2.40

7.9

2.50

8.0

2.60

8.2

4.2

Opening and closing the unit

4.2.1

To open the indoor unit

1

Remove the bottom cover to be able to guide the cables to the
switch box.

2

Remove the top cover.

3

Remove the switch box cover.

4.2.2

To close the indoor unit

1

Reinstall the switch box cover.

2

Reinstall the top cover.

Содержание EKHWET90BAV3

Страница 1: ...Installation manual R32 Split series Domestic hot water tank English Installation manual R32 Split series Domestic hot water tank EKHWET90BAV3 EKHWET120BAV3 https daikintechnicaldatahub eu...

Страница 2: ...trukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi za predpokladu e sa v robky pou...

Страница 3: ...or test run 18 9 Hand over to the user 19 10 Technical data 20 10 1 Piping diagram Indoor unit 20 10 2 Wiring diagram Indoor unit 21 1 About this document Target audience Authorised installers Documen...

Страница 4: ...ng the indoor unit see 4 3 Mounting the indoor unit 410 WARNING Fixing method of the indoor unit MUST be in accordance with the instructions from this manual See 4 3 Mounting the indoor unit 410 Pipin...

Страница 5: ...g ambient temperatures Domestic hot water production 5 35 C Mind the following spacing installation guidelines 300 300 300 300 400 mm 300 300 Additionally to the spacing guidelines Because the total r...

Страница 6: ...ease height From floor to 100 mm below top of the unit N A Not applicable Minimum floor area Release height The minimum floor area requirements depend on the release height of the refrigerant in case...

Страница 7: ...d Must be 50 of Anv min minimum bottom opening area Must be 1 5 m from the floor A B Anv Anv min Min 50 of Anv min Calculate the total floor area Atotal AroomA AroomB See table 4 Look up the minimum b...

Страница 8: ...or area m 2 00 4 00 6 00 8 00 10 00 12 00 14 00 2 2 4 88 2 49 1 70 1 47 2 3 5 10 2 60 1 77 1 53 1 38 2 4 5 32 2 71 1 84 1 59 1 43 2 5 5 53 2 82 1 91 1 65 1 49 1 37 2 6 5 75 2 93 1 99 1 71 1 54 1 42 Ta...

Страница 9: ...a as specified in the table below 50 of the required opening area Anv min must be 200 mm from the floor of the unoccupied room The bottom of the opening must be 100 mm from the floor of the unoccupied...

Страница 10: ...ce when connecting the field piping and make sure the piping is aligned properly Deformation of the piping can cause malfunctioning of the unit For information related with piping length diameter conn...

Страница 11: ...the indoor unit a b a DHW hot water OUT screw connection b DHW cold water IN screw connection NOTICE A pressure relief valve field supply with an opening pressure of maximum 7 bar 0 7 MPa must be inst...

Страница 12: ...heater power supply Booster heater cable Wires 2 GND 1 5 mm 9 4 Booster heater WARNING The booster heater MUST have a dedicated power supply and MUST be protected by the safety devices required by th...

Страница 13: ...tings see 7 1 1 To access the most used commands 413 Afterwards If necessary you can make changes to the configuration in the menu structure or the overview settings INFORMATION When the configuration...

Страница 14: ...rotective functions The unit is equipped with the following protective function Tank disinfection 2 01 The unit automatically runs the protective function when necessary During installation or service...

Страница 15: ...ue When you later want to change the storage setpoint you only have to do it in one place The tank will heat up until the storage comfort temperature has been reached It is the higher desired temperat...

Страница 16: ...fine the weather dependent curve by its slope and offset Change the slope to differently increase or decrease the target temperature of the tank for different ambient temperatures For example if tank...

Страница 17: ...Cold Hot You feel Fine tune with slope and offset At regular outdoor temperatures At cold outdoor temperatures Slope Offset Hot OK Hot Cold Hot Hot See 7 3 3 Slope offset curve 416 To fine tune the w...

Страница 18: ...ly installed protection devices are installed according to this document and have NOT been bypassed The power supply voltage matches the voltage on the identification label of the unit There are NO lo...

Страница 19: ...inished and the unit operates properly please make sure the following is clear for the user Fill in the installer setting table in the operation manual with the actual settings Make sure that the user...

Страница 20: ...aikin website publicly accessible The full set of latest technical data is available on the Daikin Business Portal authentication required 10 1 Piping diagram Indoor unit R5T a1 c a2 R3T b1 b2 3D13820...

Страница 21: ...h box Multi DHW Tank switch box Multi domestic hot water tank switch box Indoor Indoor Outdoor Outdoor SWB Switch box 2 Legend 2 Legend A1P Main PCB F2B Overcurrent fuse booster heater FU1 A1P fuse 5...

Страница 22: ...wiring Power supply OUTDOOR UNIT X1M 1 2 3 earth 4 core X2M 1 2 3 earth INDOOR UNIT 1 1 booster heater power supply 1 2 kW 230 V earth STANDARD PART X1M L N earth Only for normal power supply installa...

Страница 23: ......

Страница 24: ...4P680074 1 2021 11 Copyright 2021 Daikin 4P680074 1 0000000N Verantwortung f r Energie und Umwelt...

Отзывы: