Requirements to discharges

Discharge piping, tundish, drain valves, etc. must be
positioned away from any electrical components.

The discharge pipe away from the tundish must terminate in
a safe, visible position without forming any risk to persons in
the vicinity.

If in any doubt, refer to Building Regulation G3.

Installation procedure of the EKUHWHTA kit

1

Locate the domestic hot water tank in a suitable position to
facilitate the installation of water supply, discharge fittings and
pipework. It is therefor recommended to first read through this
whole procedure.

Refer to the figure on the facing page at the start of this chapter
for full understanding of next procedure steps.

Pre-assembly

2

Pre-assemble the pressure
reducing valve (part 

1 of

this kit, refer to 

page 2

) by

mounting the blind stop and
the 2 black plastic screw-on
closing caps (part 3 of this
kit), so that the pressure
reducing valve is ready for installation.

The black plastic plugs in the pressure reducing valve body are
pressure gauge connections to enable pressure monitoring to
be carried out, should the system develop a fault. It is
recommended that these be accessible (the pressure reducing
valve has two - only one need be accessible).

3

Mount the reducing coupler (part 4 of this kit) in between the
pressure reducing valve and the expansion relief valve (part 2 of
this kit) using a length of copper tube Ø22 mm (to the pressure
reducing valve) and a length of copper tube Ø15 mm (to the
expansion relief valve).

4

Pre-assemble the adaptor and expansion vessel (parts 8 and 5
of this kit) so that the expansion vessel is ready for installation.

5

Remove the insulation piece to get acces to the factory fitted
temperature and pressure relief valve. Manually operate the
temperature and pressure relief valve to ensure free water flow
through discharge pipe. Turn knob left.

Water main in

6

Fit the elbow/drain valve (part 7 of this kit) in the cold water
flexible hose coming out of the rear plate.

Pay attention to position the drain valve in such a way that 80%
of the domestic hot water tank can be drained.

7

Position both, the pressure reducing valve with integrated non
return valve and line strainer and the expansion relief valve
(parts 1 and 2 of this kit - see also procedure step 2) as high as
possible and connect it to the water mains inlet.

The expansion relief valve must be installed with a horizontal
discharge. If fitted inverted, debris may be deposited on the seat
and cause fouling of the seat when the valve operates. Check
direction of flow arrows.

Fit a length of copper tube Ø22 mm (field supply) in between the
elbow/drain valve (procedure step 6) and the pressure reducing
valve.

Make sure to provide for a connection on this pipe to the
expansion vessel (part 5 of this kit).

8

Fit a length of copper tube Ø22 mm (field supply) inbetween the
T-piece (part 9 of this kit) and the pre-assembled expansion
vessel (procedure steps 4 and 7).

Discharge

9

Remove the front decoration panels of the domestic hot water
tank. Install the first tundish (part 6 of this kit) in a vertical
position within a maximum of 500 

mm away from the

temperature and pressure relief valve. Use the foreseen space
inside the domestic hot water tank module as indicated in the
figure. Use tie-wraps to firmly fix the tundish.

10

Connect a metal discharge pipe Ø15 mm (field supply) from the
temperature and pressure relief valve to the tundish (

500 mm).

11

Install the second tundish (part 6 of this kit) in a vertical position
within a maximum of 500 mm away from the expansion relief
valve.

12

Connect a metal discharge pipe Ø15 mm (field supply) from the
expansion relief valve to the tundish (

500 mm).

13

Connect discharge pipes from both tundishes. Refer to
paragraph 

"Tundish pipework" on page 8

.

All pipework must have a continuous fall and be fitted conform to
the requirements of the Building Regulation G3.

After completing the installation

14

After completing the installation, the installer has to fill in the
warning label on the tank with indelible ink. The warning label is
located on the lower front decoration panel inside.

NOTE

To  access the tundish connected to the
temperature and pressure relief valve, the front
decoration panels need to be removed.

Do not install any valves between the domestic hot
water tank and relief valves/expansion vessel.

Ø22 mm

Ø15 mm

Do not remove
Contact the installer.
Should the system develop a fault, switc
contact the installer.

This installation is subject to building regulation approval,
notify Local Authority of intention to install.
Use only manufacturer's recommended spare parts.
Contact your local Daikin dealer.
Installed by

name

address

tel. No.

completion date

Содержание EKHTSU200AA

Страница 1: ...INSTALLATION MANUAL EKHTSU200AA EKHTSU260AA EKUHWHTA Domestic hot water tank with UK kit for air to water heat pump system...

Страница 2: ...5x 1x 1x 1x 1 3 6 7 5 2 4 1x 340 mm 11 10 12 12 13 2 1 5 4 6 8 3 9 1 2 7 772 902 1032 H 120 6 0 1156 778 653 694 443 600 300 5 B C 250 250 A 600 30 D 30 2x 8 9 6 1 2 1 2 5 9 3 5 9 3 7 6 10 10 4 10 4...

Страница 3: ...ct to building regulation approval notify Local Authority of intention to install The EKHTSU domestic hot water tank can only be connected to a EKHBRD indoor unit The domestic hot water tank is availa...

Страница 4: ...oupler 22 mm 15 mm 5 Expansion vessel of 18 litres 6 Tundish 7 Elbow Drain valve 22 mm x 3 4 Male BSP 8 Adaptor 22 mm x 3 4 Female BSP 9 T piece 22 mm x 22 mm x 22 mm 10 Instruction sheet 1x 1x 1x 1x...

Страница 5: ...before opening the decoration panels of the indoor unit NOTE Refer to Installation of the EKUHWHTA kit on the domestic hot water tank on page 8 for connection of other safety devices in accordance wi...

Страница 6: ...itch the panel Mount the top plate of the indoor unit on the domestic hot water tank module 4 Connect the 3 way valve 1 Remove drain plate on top of the indoor unit before installing the 3 way valve 2...

Страница 7: ...ifted slightly manual operation is possible 8 Make sure to firmly fix the power supply cord onto the 3 way valve body with a field supplied cable tie like in illustration below 9 Perform the wiring in...

Страница 8: ...t water tank on page 8 10 Connect the thermistor wire to the indoor unit switch box Make sure power supply is switched off Refer to the wiring diagram delivered with the indoor unit The distance betwe...

Страница 9: ...re and pressure relief valve to ensure free water flow through the discharge pipe turn knob left Refer to Main components on page 2 for location of the temperature and pressure relief valve 13 Reattac...

Страница 10: ...pipework All pipework must have a continuous fall Sizing of copper discharge pipe D2 for common temperature relief valve outlet sizes All pipework and fittings must be flushed free of all flux and de...

Страница 11: ...ne strainer and the expansion relief valve parts 1 and 2 of this kit see also procedure step 2 as high as possible and connect it to the water mains inlet The expansion relief valve must be installed...

Страница 12: ...sing and correcting certain troubles which may occur in the unit General guidelines Before starting the trouble shooting procedure carry out a thorough visual inspection of the unit and look for obvio...

Страница 13: ...then contact your local dealer EKHTSU200AA EKHTSU260AA Storage capacity l 200 260 Material Stainless steel Stainless steel Overall dimensions h x l x w mm 1335 x 600 x 695 1610 x 600 x 695 Operating...

Страница 14: ...4PW53247 1B Copyright Daikin...

Отзывы: