Operation manual

15

EKHVWQ0 E260AA1V3

Domestic hot water heat pump

4PW65343-1A – 10.2010

6.2.

Field settings table

First 
code

Second 
code

Setting name

Installer setting at variance with default value

Default 

value

Range

Step

Unit

Date

Value

Date

Value

0

Different operation modes

00

Powerfull operation mode temperature set point

40

35~50

1

°C

01

Disinfection operation mode tempeature set point

60

55~75

1

°C

02

Temperature setpoint: reheat minimum 
temperature

40

35~75

1

°C

03

Temperature setpoint: reheat maximum 
temperature

45

35~75

1

°C

04

 Status: defines whether the reheat operation is 
turned ON(1) or OFF(0)

0 (OFF)

0/1

1

1

Automatic domestic hot water tank temperature set point calculation

00

Renewal time for set point calculation

6:00

0:00~23:30

0:30

hour

01

Mnimum automatic temperature set point

42

35~75

1

°C

02

Maximum automatic temperature set point

60

35~75

1

°C

2

Disinfection operation

00

Installation related setting

Fri

01

Installation related setting

1 (ON)

02

Installation related setting

23:00

03

Installation related setting

0 (OFF)

04

Installation related setting

32

3

Miscellaneous

00

Installation related setting

1 (ON)

01

Installation related setting

3

02

Installation related setting

0 (OFF)

03

Installation related setting

0 (OFF)

4

Miscellaneous

03

Installation related setting

0

04

Installation related setting

1

6

Miscellaneous

00

Installation related setting

10

01

Installation related setting

0

02

Installation related setting

0

03

Installation related setting

1 (ON)

04

Installation related setting

1

7

Miscellaneous

01

Installation related setting

2

02

Installation related setting

3

03

Installation related setting

0

04

Installation related setting

2

8

Automatic setpoint calculation

00

Installation related setting

45

01

Installation related setting

50

02

Installation related setting

15

03

Installation related setting

0 (OFF)

04

Installation related setting

0 (260 l)

D

Benefit kWh rate power supply/Local shift value weather dependent

01

Installation related setting

0

E

Unit information readout

00

Installation related setting

01

Installation related setting

02

Installation related setting

Содержание EKHHS200AA1V3

Страница 1: ...OPERATION MANUAL EKHVWQ002AAV3 EKHHS200AA1V3 EKHHS260AA1V3 Domestic hot water heat pump ...

Страница 2: ...ance activities 16 7 3 Standstill 16 8 Troubleshooting 17 9 Disposal requirements 17 The English text is the original instruction Other languages are translations of the original instructions This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruc...

Страница 3: ...s a potentially hazardous situation which if not avoided may result in minor or moderate injury It may also be used to alert against unsafe practices NOTICE Indicates situations that may result in equipment or property damage accidents only INFORMATION This symbol identifies useful tips or additional information Electric current Danger of burning and scalding DANGER ELECTRICAL SHOCK Switch off all ...

Страница 4: ...nual 4 1 Domestic water heating operation quick start up Schedule timer operation Continuous operation Powerful operation INFORMATION Refer to the installation manual of the unit for installation procedures Icon p is displayed a a To display or remove the p icon press the pr button Schedule timer operation Push the ba button Push the Y button Push the Y button The 0 LED will light up and the unit ...

Страница 5: ...fers full control over your installation Basic controller functions The basic controller functions are Turning the unit ON OFF Schedule timer continuous mode Selection of features quiet mode refer to page 8 auto adaptive set point control refer to page 9 Temperature set point adjustment refer to page 6 Powerful mode The digital controller supports a power cut off of maximum 2 hours When autorestar...

Страница 6: ...ailable 14 DEFROST MODE ICON d This icon indicates that the defrost mode is active 15 COMPRESSOR ICON ç This icon indicates that the compressor of the heat pump unit is active When freeze protection mode is active this icon is blinking 16 BOOSTER HEATER ICON m This icon indicates that the booster heater is active The booster heater provides auxiliary heating for the domestic hot water tank if a hi...

Страница 7: ...e by 10 minutes 3 Use the wi or wj button to adjust the day of the week Each time the wi or wj button is pressed the next or previous day is displayed 4 Press the button to confirm the current set time and day of the week To leave this procedure without saving press the pr button If no button is pressed for 5 minutes the clock and day of the week will return to their previous setting Setting the sc...

Страница 8: ... command It is clear that the last programmed command may date from the day before Refer to Consulting programmed actions on page 12 INFORMATION Default the schedule timer is set as follows Time Set point temperature Sunday until thursday 7 4 22 6 h 45 C Friday and saturday 5 6 22 6 h 55 C If this does not fullfill the customers demands it has to be set as explained in Programming and consulting th...

Страница 9: ...he desired quiet mode is set through a field setting Refer to the field settings explained in the installation manual for a detailed description how to set one or more field settings Disinfection operation This mode will disinfect the domestic hot water tank by periodically heating the domestic water to a specific temperature During the operation of this mode the w icon will be blinking slowly with 0 ...

Страница 10: ...more actions are programmed for the same day and at the same time only the action with the lowest action number will be executed You can always alter add or remove the programmed actions later Example 1 Example 2 If on mondays the customer is usually at home and uses a lot of hot water the set point for monday will increase untill the required amount of hot water is reached as shown in the figure b...

Страница 11: ...s e g 4 and 5 are not displayed 7 Press the button for 5 seconds to enter the programming mode 8 Use the button to select the action number you would like to program or to modify 9 Use the pi and pj buttons to set the correct action time 10 Use the ba button to select x to switch heating and the controller off 9 set the temperature by means of the wi and wj buttons 11 Repeat steps 8 to 10 to progr...

Страница 12: ...rogramming mode 6 Use the button to select the action number you would like to program or to modify 7 Use the pi and pj buttons to set the correct action time 8 Use the ba button to select or deselect x as action 9 Repeat steps 6 to 8 to program the other actions of the selected mode When all actions have been programmed make sure that the display shows the highest action number you would like to ...

Страница 13: ...i e after pressing the button for 5 seconds press the pr button once You can now select another day by using the pi and pj buttons and restart consulting and programming Copying programmed actions to next day In heating mode program it is possible to copy all programmed actions of a specific day to the next day e g copy all programmed actions from 1 to 2 To copy programmed actions to the next day p...

Страница 14: ...on If the P button is pressed the heat pump module heats up the domestic hot water tank as fast as possible to a predefined setpoint This means that the inverter compressor frequency will be higher then in normal operation mode and that sound level and power consumption can be higher This mode might be usefull when exceptional high hot water consumption depletes all the available domestic hot water...

Страница 15: ...ed defines whether the reheat operation is turned ON 1 or OFF 0 1 Automatic domestic hot water tank temperature set point calculation 1 00 Renewal time for set point calculation The automatic temperature set point calculation is done on a daily basis The algorithm calculates for each day of the week an optimum domestic hot water tank temperature set point To calculate this temperature setpoint the ...

Страница 16: ...lated setting 1 ON 02 Installation related setting 23 00 03 Installation related setting 0 OFF 04 Installation related setting 32 3 Miscellaneous 00 Installation related setting 1 ON 01 Installation related setting 3 02 Installation related setting 0 OFF 03 Installation related setting 0 OFF 4 Miscellaneous 03 Installation related setting 0 04 Installation related setting 1 6 Miscellaneous 00 Inst...

Страница 17: ...dissipate this gas safely it is recommended that a hot tap be turned on for several minutes at a sink basin or bath but not at a dishwasher clothes washer or other appliance During this procedure there must be no smoking open flame or any electrical appliance operating nearby If hydrogen is discharged through the tap it will probably make a sound as of air escaping Each inspection has to be carried...

Страница 18: ...zed treatment facility for re use recycling and recovery By ensuring this product is disposed off correctly you will help to prevent potential negative consequences for the environment and human health Please contact the installer or local authority for more information NOTES POSSIBLE CAUSES CORRECTIVE ACTIONS No readings on the remote controller blank display Check if the mains power is still con...

Страница 19: ......

Страница 20: ...4PW65343 1A 10 2010 Copyright 2010 Daikin ...

Отзывы: