EKHBRD011~Y1
Indoor unit for air to water heat pump system
4PW54465-1A
Installation manual
28
The configuration of pattern B is done by field settings:
1
Select the appropriate pattern: [7-02] = 1
2
Turn on multiple set point 1: [7-03] = 0
➞
[7-03] = 1
Turn on multiple set point 2: [7-04] = 0
➞
[7-04] = 1
3
Enter the temperature multiple set point 1: [A-03] (see below)
Enter the temperature multiple set point 2: [A-04] (see below)
Configuration example:
Pattern B can also be used to do some primary multi zoning (if all set
point temperatures are selected the same, no temperature reducing
device (
) is required).
Multiple thermo ON signals for 3 rooms can be generated. Thermo
OFF signals are only valid if all requests are OFF.
Field settings table
Set
point
Field
setting
Thermo status
Space 0
65°C
Remote
controller
OFF
ON
OFF
OFF
OFF
Space 1
45°C
[A-03]
OFF
ON/OFF ON
ON
OFF
Space 2
35°C
[A-04]
OFF
ON/OFF OFF
ON
ON
Resulting heat pump water
OFF
65°C
45°C
45°C
35°C
NOTE
■
Leaving water control is not allowed for pattern B.
■
It is the installers responsibility to make sure no
unwanted situations can occur (e.g. too high
water temperatures towards floor heating loops,
etc.).
■
It is the installers responsibility to make sure the
water circuit is well balanced (e.g. when a
domestic hot water request occurs, there will be
sufficient flow towards other appliances as well,
etc.)
■
Daikin does not offer any temperature reducing
device (
). This system only provides the
possibility to use multiple set points.
■
When space 0 is in thermo OFF, but space 1 or 2
are active, space 0 will be fed with water at a
temperature equal to the highest set point of
spaces 1 and 2.
This can lead to unwanted heating of space 0.
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range
Step
Unit
Date
Value
Date
Value
0
Remote control setup
00
User permission level
2
2~3
1
—
01
Room temperature compensation value
0
–5~5
0.5
°C
03
Status : space heating schedule timer mode
1 (ON)
0/1
—
—
1
Automatic storage timing for domestic water heating
00
Status: night time storage
1 (ON)
0/1
—
—
01
Night time storage start time
1:00
0:00~23:00
1:00
hour
02
Status: day time storage
0 (OFF)
0/1
—
—
03
Day time storage start time
15:00
0:00~23:00
1:00
hour
2
Automatic setback function
00
Status: setback operation
1 (ON)
0/1
—
—
01
Setback operation start time
23:00
0:00~23:00
1:00
hour
02
Setback operation stop time
5:00
0:00~23:00
1:00
hour
3
Weather dependent set point
00
Low ambient temperature (Lo_A)
–10
–20~5
1
°C
01
High ambient temperature (Hi_A)
15
10~20
1
°C
02
Set point at low ambient temperature (Lo_Ti)
70
25~80
1
°C
03
Set point at high ambient temperature (Hi_Ti)
45
25~80
1
°C
4
Disinfection function
00
Status: disinfection operation
1 (ON)
0/1
—
—
01
Disinfection operation day selection
Fri
Mon~Sun
—
—
02
Disinfection operation start time
23:00
0:00~23:00
1:00
hour
5
Automatic setback and disinfection set point
00
Set point: disinfection operation temperature
70
60~70
5
°C
01
Disinfection operation time duration
10
5~60
5
min
02
Leaving water setback temperature
5
0~10
1
°C
03
Room setback temperature
18
17~23
1
°C
6
Option setup
00
Domestic hot water tank installed
0 (OFF)
0/1
—
—
01
Optional room thermostat installed
0 (OFF)
0/1
—
—
04
Benefit kWh power supply mode
0 0/2
1
—