Operation manual

15

EKHBH/X016BA

Indoor unit for air to water heat pump system and options

4PW54186-1

9

Heating and cooling set point ranges

00

Heating set point upper limit

55

37~55

1

°C

01

Heating set point lower limit

25

15~37

1

°C

02

Cooling set point upper limit

22

18~22

1

°C

03

Cooling set point lower limit

5

5~18

1

°C

04

Installation related setting

A

Quiet mode

00

Quiet mode type

0

0/2

01

Parameter 01

3

02

Not applicable

1

Read only

03

Not applicable

0

Read only

04

Not applicable

0

Read only

b

Not applicable

00

Not applicable

0

Read only

01

Not applicable

0

Read only

02

Not applicable

0

Read only

03

Not applicable

0

Read only

04

Not applicable

0

Read only

C

Setup on EKRP1HB digital I/O PCB

00

Solar priority mode setting

0

0/1

1

01

Installation related setting

02

Installation related setting

03

Installation related setting

04

Installation related setting

D

Local shift value weather dependent

00

Installation related setting

01

Installation related setting

02

Installation related setting

03

Local shift value weather dependent

0

0/1/2/3/4

E

Unit information readout

00

Software version

Read 

only

01

EEPROM version

Read 

only

02

Unit model identification

Read 

only

03

Liquid refrigerant temperature

Read 

only

°C

04

Inlet water temperature

Read 

only

°C

F

Installation related settings

00

Installation related setting

01

Installation related setting

02

Installation related setting

03

Installation related setting

04

Installation related setting

First 
code

Second 
code

Setting name

Installer setting at variance with default value

Default 

value

Range

Step

Unit

Date

Value

Date

Value

Содержание EKHBH016BA

Страница 1: ...OPERATION MANUAL EKHBH016BA EKHBX016BA Indoor unit for air to water heat pump system and options...

Страница 2: ...to water ERHQ or ERLQ heat pumps These units are designed for wall mounted indoor installation The units can be combined with Daikin fan coil units floor heating applications low temperature radiators...

Страница 3: ...rmostat connected to the indoor unit This will prevent excessive space heating and will stop the outdoor unit and the indoor circulation pump when the room temperature is above the thermostat set poin...

Страница 4: ...eration mode s space heating h space cooling c domestic water heating w or quiet mode s Within limits different modes can be combined e g space heating and domestic water heating The corresponding mod...

Страница 5: ...E HEATING COOLING BUTTON This button allows manual switching between heating or cooling mode provided the unit is not a heating only unit When the unit is connected with an external room thermostat th...

Страница 6: ...turns to space heating operation Space cooling operation c In this mode cooling will be activated as required by the water temperature set point Domestic water heating operation w In this mode the ind...

Страница 7: ...n 1 Press v for 5 seconds to activate powerful domestic water heating operation Icons w and m start flashing Powerful domestic water heating is deactivated automatically when the set point for the dom...

Страница 8: ...rammed at 13 00 16 00 and 19 00 The last programmed command 16 00 overruled the previous programmed command 13 00 and will remain active until the next programmed command 19 00 occurs So in order to k...

Страница 9: ...nt Conversely when programming cooling actions time and set point heating actions are added automatically at the same time but with the default heating set point The set points of these automatically...

Страница 10: ...nds to store the programmed actions If the button is pressed when action number 3 is displayed actions 1 2 and 3 are stored but 4 and 5 are deleted You automatically return to step 6 By pressing the p...

Страница 11: ...ram it is possible to copy all programmed actions of a specific day to the next day e g copy all programmed actions from 1 to 2 To copy programmed actions to the next day proceed as follows 1 Press th...

Страница 12: ...ep 2 through 4 to change other field settings as required 7 When finished press the z button to exit FIELD SET MODE Detailed description 0 User permission level If required certain user interface butt...

Страница 13: ...2 Start time time of the day at which the domestic hot water should be heated 2 03 Set point high water temperature to be reached 2 04 Interval time period defining how long the set point temperature...

Страница 14: ...not change this setting Leave it set to its default value C Setup on EKRP1HB digital I O PCB Solar priority mode C 00 Solar priority mode setting for information concerning the EKSOLHW solar kit refe...

Страница 15: ...restart 00 Status 0 ON 0 1 4 Space heating off temperature 00 Installation related setting 01 Installation related setting 02 Space heating off temperature 35 14 35 1 C 03 Installation related setting...

Страница 16: ...O PCB 00 Solar priority mode setting 0 0 1 1 01 Installation related setting 02 Installation related setting 03 Installation related setting 04 Installation related setting D Local shift value weathe...

Страница 17: ...ed household waste Do not try to dismantle the system yourself the dismantling of the system treatment of the refrigerant of oil and other parts must be done by a qualified installer in accordance wit...

Страница 18: ...NOTES NOTES...

Страница 19: ......

Страница 20: ...4PW54186 1 Copyright Daikin...

Отзывы: