Operation manual

13

EKHBH/X016AB

Indoor unit for hot water heat pump system and options

[7] Domestic hot water step length

Applies only to installations with a domestic hot water tank.

When the domestic water is heated and the domestic hot water set
point temperature (as set by the user) has been reached, the booster
heater will continue to heat the domestic hot water to a temperature a
few degrees above the set point temperature, i.e. the booster heater
OFF temperature. These extra degrees are specified by the domestic
hot water step length field setting. Correct setting prevents the
booster heater from repeatedly turning on and off (i.e. chattering) to
maintain the domestic hot water set point temperature. Note: the
booster heater will turn back on when the domestic hot water
temperature drops 2°C (fixed value) below the booster heater OFF
temperature.

[7-00] Domestic hot water step length: temperature
difference above the domestic hot water set point
temperature before the booster heater is turned off.

[8] Domestic water heating mode timer

Applies only to installations with a domestic hot water tank.

The 'domestic water heating mode timer' field settings defines the
minimum and maximum domestic water heating times, and minimum
time between two domestic water heating cycli.

[8-00] Minimum running time: specifies the minimum time
period during which domestic water heating should be
activated, even when the target domestic hot water
temperature has already been reached.

[8-01] Maximum running time: specifies the maximum time
period during which domestic water heating can be activated,
even when the target domestic hot water temperature has
not yet been reached.
Note that when the unit is configured to work with a room
thermostat (refer to the installation manual), the maximum
running timer will only be taken into account when there is a
request for space cooling or space heating. When there is no
request for room cooling or room heating, domestic water
heating by the heat pump will continue until the "heat pump
OFF temperature" (see field settings [5]) is reached. When
no room thermostat is installed, the timer is always taken into
account.

[8-02] Anti-recycling time: specifies the minimum required
interval between two domestic water heating cycli.

[8-03] Booster heater delay time: specifies the start-up time
delay of the booster heater operation after start of the heat
pump domestic water heating operation.

NOTE

If the schedule timer for booster heater (see the
operation manual) is active, the booster heater will only
operate if allowed by this schedule timer.

BH

Booster heater

HP

Heat pump. If heating up time by the heat pump takes too 
long, auxiliary heating by the booster heater can take place

T

BH OFF

Booster heater OFF temperature (T

U

 + [7-00]) 

T

BH ON

Booster heater ON temperature (T

BH OFF

 – 2°C)

T

HP MAX

Maximum heat pump temperature at sensor in domestic hot 
water tank

T

HP OFF

Heat pump OFF temperature (T

HP MAX

 – [6-01])

T

HP ON

Heat pump ON temperature (T

HP OFF

 – [6-00])

T

DHW

Domestic hot water temperature

T

U

User set point temperature (as set on the user interface)

t

Time

t

T

BH ON

T

DHW

T

HP ON

T

HP OFF

T

HP MAX

T

U

T

BH OFF

[6-01]
[6-00]

[7-00]

T

U

= 70

°

C

[7-00] =

3

°

C

[6-01] =

7

°

C

[6-00] =

7

°

C

HP

BH

HP

0

10

20

30

40

41

48

55

60

71
70

73

1

Domestic water heating (1 = active, 0 = not active)

2

Hot water request (1 = request, 0 = no request)

t

Time

1

Booster heater operation (1 = active, 0 = not active)

2

Heat pump domestic water heating operation (1 = request, 0 = 
no request)

3

Hot water request (1 = request, 0 = no request)

t

Time

t

1

0

1

0

[8-01]

[8-02]

[8-00]

t

1

0

1

0

1

0

[8-03]

3

Содержание EKHBH016AB

Страница 1: ...OPERATION MANUAL EKHBH016AB EKHBX016AB Indoor unit for hot water heat pump system and options ...

Страница 2: ...mbined with Daikin fan coil units floor heating low temperature radiators the Daikin domestic hot water tanks and the solar option kit The hot water heat pump system indoor unit range consists of two main versions a heating cooling EKHBX version and a heating only EKHBH version Both versions can optionally be delivered with an integrated backup heater for additional heating capacity during cold ou...

Страница 3: ...ow electricity cost tariffs in mind To do this program both the domestic water heating and booster heating schedule timer Refer to Programming in chapter Programming and consulting the schedule timer on page 7 OPERATING THE DIGITAL CONTROLLER Operating the EKHB unit comes down to operating the digital controller Features and functions The digital controller is a state of the art controller that of...

Страница 4: ...ected when programming the schedule timer 10 INSPECTION REQUIRED k and l These icons indicate that inspection is required on the installation Consult your Daikin dealer 11 SET TEMPERATURE DISPLAY 9 The display shows the current set temperature of the installation 12 SETTING Not used For installation purposes only 13 NOT AVAILABLE n This icon is displayed whenever a non installed option is addresse...

Страница 5: ...he domestic hot water tank is not installed 34 QUIET MODE BUTTON s This button enables or disables quiet mode If the controller is set in permission level 2 or 3 refer to Field settings on page 10 the quiet mode button will not be operable Setting up the controller After initial installation the user can set the clock and day of the week The controller is equipped with a schedule timer that enable...

Страница 6: ...perable when the outdoor ambient temperature rises above a certain temperature as set through field setting 4 02 refer to Field settings on page 10 Temperature range for cooling 5 C to 22 C 3 Switch on the unit by pushing the y button The operation LED 0 lights up Selection and setting of domestic water heating w 1 Use the v button to activate domestic water heating w Icon w appears on the display...

Страница 7: ...ions 2 Quiet mode refer to Programming quiet mode booster heating or domestic water heating on page 9 Switch the mode on or off at a scheduled time Five actions can be programmed per mode These actions are repeated daily 3 Booster heating refer to Programming quiet mode booster heating or domestic water heating on page 9 Allow or disallow booster heating at a scheduled time Five actions can be pro...

Страница 8: ...ement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day and at the same time only the action with the highest action number will be executed You can always alter add or remove the programmed actions later When programming heating actions time and set point cooling actions are added automatically at the same time but with the predefined d...

Страница 9: ...t x to switch cooling or heating and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation only in heating mode 10 Use the pi and pj buttons to set the correct action time 11 Repeat steps 8 to 10 to program the other actions of the selected day When all actions have been programmed make sure that the display shows the highest actio...

Страница 10: ...ult 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to consult by means of the pi and pj buttons The selected day is blinking 5 Press the button to confirm the selected day The first programmed action of the selected day appears 6 Use the pi and pj buttons to consult the other programmed actio...

Страница 11: ...aneously for 5 seconds to delete the selected mode Deleting a day of the week cooling or heating mode 1 Use the button to select the operation mode cooling or heating you want to delete 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to delete by means of the pi and pj buttons The selected day...

Страница 12: ...ld be higher than Hi_Ti as for colder outdoor temperatures i e Lo_A warmer water is required 1 03 Set point at high ambient temperature Hi_Ti the target outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature Hi_A Note that the Hi_Ti value should be lower than Lo_Ti as for warmer outdoor temperatures i e Hi_A less warm water suffices 2 Disinfectio...

Страница 13: ...atus specifies whether space heating priority is enabled 1 or disabled 0 5 03 Space heating priority temperature outdoor temperature below which the domestic water will be heated by the booster heater only i e low outdoor temperature 5 04 Set point correction for domestic hot water temperature set point correction for the desired domestic hot water temperature to be applied at low outdoor temperat...

Страница 14: ...hed Note that when the unit is configured to work with a room thermostat refer to the installation manual the maximum running timer will only be taken into account when there is a request for space cooling or space heating When there is no request for room cooling or room heating domestic water heating by the heat pump will continue until the heat pump OFF temperature see field settings 5 is reach...

Страница 15: ...iet operation might be overridden when higher performance is required In certain cases this might result in less quiet operation of the outdoor unit to meet the requested performance A 00 Quiet mode type defines whether quiet mode A 0 or quiet mode B 2 is selected A 01 Parameter 01 do not change this setting Leave it set to its default value C Solar priority mode For information concerning the EKS...

Страница 16: ...5 1 C 5 Equilibrium temperature and space heating priority temperature 00 Equilibrium temperature status 1 ON 0 1 01 Equilibrium temperature 0 15 20 1 C 02 Space heating priority status 0 OFF 0 1 03 Space heating priority temperatures 0 15 20 1 C 04 Set point correction for domestic hot water temperature 10 0 20 1 C 6 DT for domestic water heating 00 Start 5 1 20 1 C 01 Stop 2 2 10 1 C 7 Domestic ...

Страница 17: ...r local Daikin dealer The schedule timer does work but the programmed actions are executed at the wrong time e g 1 hour too late or too early Check if the clock and the day of the week are set correctly correct if necessary DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant local and national legislation Do ...

Страница 18: ...NOTES NOTES ...

Страница 19: ......

Страница 20: ...Copyright Daikin ...

Отзывы: