Operation manual

5

EKHBH/X016AB

Indoor unit for hot water heat pump system and options

Space cooling operation (

c

)

In this mode, cooling will be activated as required by the water
temperature set point.

Domestic water heating operation (

w

)

In this mode, the indoor unit will deliver hot water to the domestic hot
water tank when the space heating or space cooling operation has
reached its temperature set point. When necessary and when
allowed by the booster heater schedule timer (refer to 

"Programming

quiet mode, booster heating or domestic water heating" on page 9

),

the booster heater provides auxiliary heating for the domestic hot
water tank.

Powerful domestic water heating operation

In the case of urgent need of domestic hot water, the domestic hot
water temperature set point can be reached quickly by using the
booster heater. Powerful domestic water heating operation is forcing
the booster heater to operate until the domestic hot water
temperature set point is reached.

This function remains available in solar operation.

Quiet mode operation (

s

)

Quiet mode operation means that the outdoor unit works at reduced
capacity so that the noise produced by the outdoor unit drops. This
implies that the indoor heating and cooling capacity will also drop.
Beware of this when a certain level of heating is required indoors.

Two quiet modes are available.

Controller operations

Manual operation

In manual operation, the user manually controls the settings of the
installation. The last setting remains active until the user changes it or
until the schedule timer forces another setting (refer to 

"Schedule

timer operation" on page 6

).

As the controller can be used for a wide variety of installations, it is
possible to select a function which is not available on your
installation. In that case the message 

n

 will appear.

Switching on and setting space cooling (

c

) and heating (

h

)

1

Use the 

=

 button to select space cooling (

c

) or space heating

(

h

).

Icon 

c

 or 

h

 appears on the display as well as the corresponding

water temperature set point.

2

Use the 

bi

  and 

bj

  buttons to set the desired water

temperature.

Temperature range for heating: 25°C to 55°C
The temperature for heating can be set as low as 15°C (see

"Field settings" on page 10

). However, the temperature for

heating should only be set lower than 25°C during
commissioning of the installation. When set lower than 25°C,
only the backup heater will operate.
In order to avoid overheating, space heating is not operable
when the outdoor ambient temperature rises above a certain
temperature (as set through field setting [4-02], refer to 

"Field

settings" on page 10

).

Temperature range for cooling: 5°C to 22°C

3

Switch on the unit by pushing the 

y

 button.

The operation LED 

0

 lights up.

Selection and setting of domestic water heating (

w

)

1

Use the 

v

 button to activate domestic water heating (

w

).

Icon 

w

 appears on the display.

2

Use the 

wi

  or 

wj

  button to display the actual

temperature set point and subsequently, to set the correct
temperature.

The actual temperature set point only appears on the display
after pressing one of the buttons 

wi

 or 

wj

. If no button is

pressed for 5 seconds, the temperature set point will
automatically disappear from the display again.
Temperature range for domestic water heating: 30°C to 80°C

3

Press the 

v

 button to deactivate domestic water heating (

w

).

Icon 

w

 disappears from the display.

NOTE

The space cooling temperature set point can only
be set manually (refer to 

"Manual operation" on

page 5

).

Switching between space heating and space
cooling operation can only be done by pressing
the 

=

 button or by an external room thermostat.

Space cooling operation is not possible if the
installation is a "heating only" installation.

NOTE

In order to provide domestic hot water throughout
the day, it is advised to keep the domestic water
heating operation on continuously.

The domestic hot water water temperature set
point can only be set manually (refer to 

"Manual

operation" on page 5

).

Any domestic water heating operation is
impossible when the domestic hot water tank is
not installed.

When the 

w

  icon is blinking, hot water is

delivered to the domestic hot water tank by the
solar kit option and not by the

 hot water 

heat pump system indoor unit. Refer to installation 
manual of the EKSOLHW solar kit.

NOTE

In heating mode (

h

), the water temperature set point

can also be weather dependent (icon 

a

 is shown).

This means that the controller calculates the water
temperature set point based on the outdoor
temperature.

In this case, instead of showing the water temperature
set point, the controller shows the "shift value" which
can be set by the user. This shift value is the
temperature difference between the temperature set
point calculated by the controller and the real set point.
E.g. a positive shift value means that the real
temperature set point will be higher than the calculated
set point.

NOTE

When the unit is connected to an external room
thermostat, buttons 

=

 and 

y

 are not operable and

the icon 

e

  is shown. In this case, the external room

thermostat switches the unit on or off and determines
the operation mode (space cooling or space heating).

Содержание EKHBH016AB

Страница 1: ...OPERATION MANUAL EKHBH016AB EKHBX016AB Indoor unit for hot water heat pump system and options ...

Страница 2: ...mbined with Daikin fan coil units floor heating low temperature radiators the Daikin domestic hot water tanks and the solar option kit The hot water heat pump system indoor unit range consists of two main versions a heating cooling EKHBX version and a heating only EKHBH version Both versions can optionally be delivered with an integrated backup heater for additional heating capacity during cold ou...

Страница 3: ...ow electricity cost tariffs in mind To do this program both the domestic water heating and booster heating schedule timer Refer to Programming in chapter Programming and consulting the schedule timer on page 7 OPERATING THE DIGITAL CONTROLLER Operating the EKHB unit comes down to operating the digital controller Features and functions The digital controller is a state of the art controller that of...

Страница 4: ...ected when programming the schedule timer 10 INSPECTION REQUIRED k and l These icons indicate that inspection is required on the installation Consult your Daikin dealer 11 SET TEMPERATURE DISPLAY 9 The display shows the current set temperature of the installation 12 SETTING Not used For installation purposes only 13 NOT AVAILABLE n This icon is displayed whenever a non installed option is addresse...

Страница 5: ...he domestic hot water tank is not installed 34 QUIET MODE BUTTON s This button enables or disables quiet mode If the controller is set in permission level 2 or 3 refer to Field settings on page 10 the quiet mode button will not be operable Setting up the controller After initial installation the user can set the clock and day of the week The controller is equipped with a schedule timer that enable...

Страница 6: ...perable when the outdoor ambient temperature rises above a certain temperature as set through field setting 4 02 refer to Field settings on page 10 Temperature range for cooling 5 C to 22 C 3 Switch on the unit by pushing the y button The operation LED 0 lights up Selection and setting of domestic water heating w 1 Use the v button to activate domestic water heating w Icon w appears on the display...

Страница 7: ...ions 2 Quiet mode refer to Programming quiet mode booster heating or domestic water heating on page 9 Switch the mode on or off at a scheduled time Five actions can be programmed per mode These actions are repeated daily 3 Booster heating refer to Programming quiet mode booster heating or domestic water heating on page 9 Allow or disallow booster heating at a scheduled time Five actions can be pro...

Страница 8: ...ement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day and at the same time only the action with the highest action number will be executed You can always alter add or remove the programmed actions later When programming heating actions time and set point cooling actions are added automatically at the same time but with the predefined d...

Страница 9: ...t x to switch cooling or heating and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation only in heating mode 10 Use the pi and pj buttons to set the correct action time 11 Repeat steps 8 to 10 to program the other actions of the selected day When all actions have been programmed make sure that the display shows the highest actio...

Страница 10: ...ult 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to consult by means of the pi and pj buttons The selected day is blinking 5 Press the button to confirm the selected day The first programmed action of the selected day appears 6 Use the pi and pj buttons to consult the other programmed actio...

Страница 11: ...aneously for 5 seconds to delete the selected mode Deleting a day of the week cooling or heating mode 1 Use the button to select the operation mode cooling or heating you want to delete 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to delete by means of the pi and pj buttons The selected day...

Страница 12: ...ld be higher than Hi_Ti as for colder outdoor temperatures i e Lo_A warmer water is required 1 03 Set point at high ambient temperature Hi_Ti the target outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature Hi_A Note that the Hi_Ti value should be lower than Lo_Ti as for warmer outdoor temperatures i e Hi_A less warm water suffices 2 Disinfectio...

Страница 13: ...atus specifies whether space heating priority is enabled 1 or disabled 0 5 03 Space heating priority temperature outdoor temperature below which the domestic water will be heated by the booster heater only i e low outdoor temperature 5 04 Set point correction for domestic hot water temperature set point correction for the desired domestic hot water temperature to be applied at low outdoor temperat...

Страница 14: ...hed Note that when the unit is configured to work with a room thermostat refer to the installation manual the maximum running timer will only be taken into account when there is a request for space cooling or space heating When there is no request for room cooling or room heating domestic water heating by the heat pump will continue until the heat pump OFF temperature see field settings 5 is reach...

Страница 15: ...iet operation might be overridden when higher performance is required In certain cases this might result in less quiet operation of the outdoor unit to meet the requested performance A 00 Quiet mode type defines whether quiet mode A 0 or quiet mode B 2 is selected A 01 Parameter 01 do not change this setting Leave it set to its default value C Solar priority mode For information concerning the EKS...

Страница 16: ...5 1 C 5 Equilibrium temperature and space heating priority temperature 00 Equilibrium temperature status 1 ON 0 1 01 Equilibrium temperature 0 15 20 1 C 02 Space heating priority status 0 OFF 0 1 03 Space heating priority temperatures 0 15 20 1 C 04 Set point correction for domestic hot water temperature 10 0 20 1 C 6 DT for domestic water heating 00 Start 5 1 20 1 C 01 Stop 2 2 10 1 C 7 Domestic ...

Страница 17: ...r local Daikin dealer The schedule timer does work but the programmed actions are executed at the wrong time e g 1 hour too late or too early Check if the clock and the day of the week are set correctly correct if necessary DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant local and national legislation Do ...

Страница 18: ...NOTES NOTES ...

Страница 19: ......

Страница 20: ...Copyright Daikin ...

Отзывы: