EKHBH/X008BB
Indoor unit for air to water heat pump system
4PW62570-1A – 01.2011
Installation manual
40
5
Equilibrium temperature and space heating priority temperature
00
Equilibrium temperature status (only in combination
with domestic hot water tank
without
electrical
booster heater (EKHTS), [4-03]=5, this setting is
fixed and can not be consulted)
1 (ON)
—
—
—
00
Equilibrium temperature status (only in combination
with domestic hot water tank
with
built-in electrical
booster heater (EKHW*), [4-03]
≠
5)
1 (ON)
0/1
—
—
01
Equilibrium temperature
0
–15~35
1
°C
02
Space heating priority status (only in combination
with domestic hot water tank
without
electrical
booster heater (EKHTS), [4-03]=5, this setting is
fixed and can not be consulted)
1 (ON)
—
—
—
02
Space heating priority status (only in combination
with domestic hot water tank
with
built-in electrical
booster heater (EKHW*), [4-03]
≠
5)
0 (OFF)
0/1
—
—
03
Space heating priority temperature
0
–15~35
1
°C
04
Set point correction for domestic hot water
temperature (only in combination with domestic hot
water tank
with
built-in electrical booster heater
(EKHW*), [4-03]
≠
5)
10
0~20
1
°C
6
DT for heat pump domestic water heating mode
00
Start
2
2~20
1
°C
01
Stop
2
0~10
1
°C
Scheduled storage and reheat domestic water heating
(a)
03
Scheduled time storage
1 (ON)
0/1
1
—
04
Scheduled time storage start time
1:00
0:00~23:00
1:00
hour
05
Scheduled time reheat or continuous reheat
0 (OFF)
0/1/2
1
—
06
Scheduled time reheat start time
15:00
0:00~23:00
1:00
hour
07
Domestic hot water reheat set point
45
30~50
1
°C
08
Domestic hot water reheat set point hysteresis
10
2~20
1
°C
7
DT for booster heater and dual set point control
00
Domestic hot water step length (only in combination
with domestic hot water tank
with
built-in electrical
booster heater (EKHW*), [4-03]
≠
5)
0
0~4
1
°C
01
Hysteresis value booster heater (only in
combination with domestic hot water tank
with
built-
in electrical booster heater (EKHW*), [4-03]
≠
5)
2
2~40
1
°C
02
Dual set point control status
0 (OFF)
0/1
—
—
03
Second set point heating
10
1~24 / 25~55
1
°C
04
Second set point cooling
7
5~22
1
°C
8
Domestic water heating mode timer
00
Minimum running time
5
0~20
1
min
01
Maximum running time
30
5~95
5
min
02
Anti-recycling time (only in combination with
domestic hot water tank
without
electrical booster
heater (EKHTS), [4-03]=5)
0.5
0~10
0.5
hour
02
Anti-recycling time (only in combination with
domestic hot water tank
with
built-in electrical
booster heater (EKHW*), [4-03]
≠
5)
3
0~10
0.5
hour
03
Booster heater delay time (only in combination with
domestic hot water tank
with
built-in electrical
booster heater (EKHW*), [4-03]
≠
5)
50
20~95
5
min
04
Additional running time at [4-02]/[F-01]
95
0~95
5
min
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range
Step
Unit
Date
Value
Date
Value
Содержание EKHBH008BB Series
Страница 62: ......
Страница 63: ......
Страница 64: ...4PW62570 1A 01 2011 Copyright 2010 Daikin...