ESIE15-08B
|
Part 2. Troubleshooting
4. Component checklist - Water Circuit
Page 76
19/07/16
Daikin Altherma Monobloc CA
6.
Measure the voltage on terminal strip X8M pin 8-9 in the control box, if no /- 10% is measured, replace PCB A1P.
7.
If /- 10% is present on n terminal strip X8M pin 8-9, replace the water pump M2P.
Location
M2P
Control box
X8M/9
X8M/8
230 VAC +/-10%