8 Configuration
Installer reference guide
67
ERLQ004~008CA + 26CB6W
Daikin Altherma – Low temperature split
4P449978-1B – 2018.07
When the bivalent operation function is disabled, the space heating
by indoor unit is possible at all outdoor temperatures (see operation
ranges) and permission signal for auxiliary boiler is ALWAYS
deactivated.
▪ [C‑03] Bivalent ON temperature: defines the outdoor temperature
below which the permission signal for the auxiliary boiler will be
active (closed, KCR on EKRP1HB) and space heating by indoor
unit will be stopped.
▪ [C‑04] Bivalent hysteresis: defines the temperature difference
between bivalent ON temperature and bivalent OFF temperature.
Permission signal X1–X2 (
EKRP1HB
)
T
A
[C-03]
[C-04]
a
b
T
A
Outdoor temperature
a
Closed
b
Open
#
Code
Description
N/A
[C-03]
Range: –25°C~25°C (default: 0°C) (step:
1°C)
N/A
[C-04]
Range: 2°C~10°C (default: 3°C) (step:
1°C)
Possibility 2
The installer can set a temperature range ([C‑04]). Depending on the
energy prices, a calculated point T
calc
changes between this range.
#
Code
Description
[7.4.5.1]
N/A
What is the high electricity
price?
[7.4.5.2]
N/A
What is the medium electricity
price?
[7.4.5.3]
N/A
What is the low electricity
price?
[7.4.6]
N/A
What is the fuel price?
NOTICE
Do NOT use overview settings!
When T
A
reaches the T
calc
point, then the bivalent heat source
permission will be active. To prevent too much switching, there is a
hysteresis of 3°C.
▪ [C‑03] ON temperature. Below this temperature, bivalent will
always be ON. T
calc
is ignored.
▪ [C‑04] Operation range between which T
calc
is calculated.
T
A
T
calc
[C-03]+[C-04]
3°C
[C-03]
a
b
T
A
Outdoor temperature
T
calc
Calculated temperature
a
Closed
b
Open
#
Code
Description
N/A
[C-03]
Range: –25°C~25°C (default: 0°C) (step:
1°C)
N/A
[C-04]
Range: 2°C~10°C (default: 3°C) (step:
1°C)
It is recommended to choose [C‑04] bigger than the default value to
have an optimal operation when choosing possibility 2. Depending
on the used boiler, the boiler efficiency should be chosen as follows:
#
Code
Description
[A.6.A]
[7‑05]
▪ 0: Very high
▪ 1: High
▪ 2: Medium
▪ 3: Low
▪ 4: Very low
INFORMATION
Electricity price can only be set when bivalent is ON
([A.2.2.6.1] or [C-02]). These values can only be set in
menu structure [7.4.5.1], [7.4.5.2] and [7.4.5.3]. Do NOT
use overview settings.
INFORMATION
Boiler efficiency [A.6.A] or [7‑05] becomes visible when
bivalent is ON ([A.2.2.6.1] or [C‑02]).
CAUTION
Make sure to observe all rules mentioned in application
guideline 5 when bivalent operation function is enabled.
Daikin shall NOT be held liable for any damage resulting
from failure to observe this rule.
INFORMATION
▪ The combination of setting [4‑03]=0/2 with bivalent
operation at low outdoor temperature can result in
domestic hot water shortage.
▪ The bivalent operation function has no impact on the
domestic water heating mode. The domestic hot water
is still and only heated by the indoor unit.
▪ The permission signal for the auxiliary boiler is located
on the EKRP1HB (digital I/O PCB). When it is
activated, the contact X1, X2 is closed and open when
it is deactivated. See illustration below for the
schematic location of this contact.
YC Y1 Y2 Y3 Y4
X1
X2
X3
X4
OFF ON
X2M
SS1
X1M
Bottom plate heater
Applies only to installation with an outdoor unit ERHQ and the option
bottom plate heater kit is installed.
▪ [F-02] Bottom plate heater ON temperature: defines the outdoor
temperature below which the bottom plate heater will be activated
by indoor unit in order to prevent ice build-up in the bottom plate of
the outdoor unit at lower outdoor temperatures.
▪ [F-03] Bottom plate heater hysteresis: defines the temperature
difference between bottom plate heater ON temperature and the
bottom plate heater OFF temperature.
Bottom plate heater