 Product description

Daikin Altherma EHS(X/H) 
Daikin Altherma integrated solar unit
008.1420944 – 05/2014

Operating instructions

5

2 Product description

2.1 Brief description

The air-water heat pump system uses the physical effect of con-
densation and latent heat and makes it possible as required to 
heat or cool buildings. The Daikin Altherma EHS(X/H) (Altherma 
integrated solar unit) is the primary component of the highly-effi-
cient heating- and cooling system for domestic applications.

Located in the external heat pump unit (ERLQ)

 

are the coolant 

compressor and a finned heat exchanger, which, in heating 
mode, acts as a vaporiser and extract heat from the ambient air.

In cooling mode this acts as a condensator and returns heat to 
the environment (refrigerator principle).

The heat pump external unit is connected to the heat pump in-
ternal unit in the building by means of a closed coolant circuit. 
Heat or cold is transported between the heat pump external unit 
and the heat pump internal unit by means of the circulating refrig-
erant, which alternately takes on the liquid and gaseous phases.

The internal heat pump unit contains the control devices, the heat 
exchanger and integrated storage tank. In the heat exchanger, 
the heat is transferred to the water flowing in the heating circuit or 
the water in the storage tank (heating/hot water supply), or heat 
is extracted from the water (cooling). 

The storage tank on the Daikin Altherma EHS(X/H) is built in such 
a way to enable the heat pump system to be combined with a 
Daikin solar system without needing an additional hot water tank.

With optional solar heating, the entire hot water storage tank can 
be heated, depending on the heat offered by the sun. The stored 
heat is used both for hot water heating and for heating support. 
The high total storage capacity also temporarily allows time 
without sunshine to be bridged. The excellent heat insulation 
properties of the integrated storage tank also ensure that heat 
losses are kept to a minimum. This allows efficient and economic 
water heating and also solar support.

If the heating capacity of the Altherma EHS(X/H) is not adequate, 
the optional backup heater (EKBUxx) can provide additional 
heating capacity for heating the heating circuit.

In order to make more cost effective use of the Daikin Altherma 
EHS(X/H), it can be operated on a low tariff network connection 
(HT/NT) or with an intelligent controller (SMART GRID). Here the 
energy supply company (EVU) is afforded the opportunity to 
control their network utilisation by changing the heat pump oper-
ating mode. Information on the prerequisites and connection pos-
sibilities are described in the enclosed installation manual.

2.1.1 Mode of operation

In 

room heating mode 

the refrigerant which was compressed in 

the refrigerant compressor in the heat pump external unit con-
denses in the plate heat exchanger in the heat pump internal unit. 
The heat released during the liquefaction of the coolant is trans-
ferred to the heating water in the plate heat exchanger. The heat 
circulating pump ensures the required flow of the heating water in 
the internal hear generation circuit.

The hot water zone of the storage tank integrated into the interior 
heat pump unit is heated by the heat pump or other external heat 
generators (solar system, backup heater. The cold water flowing 
downstream of the hot water extraction cools the lower area of 
the integrated storage tank to maximum effect.

The drinking water is heated indirectly in a corrosion resistant 
stainless steel corrugated pipe heat exchanger by the unpres-
surised water from the integrated storage tank. On its way to the 
top, it continuously absorbs the heat from the storage tank water.

The flow direction, operating on the principle of counter-flow, and 
the coil-shaped heat exchanger create a pronounced temper-
ature layering in the hot water storage tank. As high temperatures 
can be maintained for a very long time in the upper section of the 
storage tank, a high hot water output is achieved even if water is 
drawn off over a long period of time.

In the case of 

room cooling

 the 3-way switching valves 

(3UV1 + 3UVB) mounted on the heat pump internal unit switches 
off the flow to storage tank charging/heating support. The heat 
circulation pump of the heat pump internal device now operates 
exclusively within the heating circuit. 

The cooling process now takes place by inverting the heat pump 
process in the heat pump external unit. Thus the heat exchanger 
of the heat pump internal unit acts as a vaporiser and extracts 
heat from the heating water that flows through it. This cools the 
heating circuit.

The lower the required temperature in the heating cir-
cuit, the more effectively the heat pump works.

It is, in particular, possible to achieve the lowest flow 
temperatures possible with under-floor heating, as the 
heat transfer surface is very large. Furthermore, the 
building to be heated should ideally have extremely 
good heat insulation, so that when there is a low heat 
requirement, the heat carrier can run with a low flow 
temperature.

Содержание EHSX04P30A

Страница 1: ...EHS X H B04P30A EHS X H 08P30A EHS X H B08P30A EHS X H 08P50A EHS X H B08P50A EHS X H 16P50A EHS X H B16P50A Indoor unit for air water heat pumps Daikin Altherma integrated solar unit Operating instr...

Страница 2: ...egionella protection 27 3 6 7 Reset to factory settings Reset 27 3 6 8 Settings for optional circulation pump 27 3 6 9 Remote control via Internet 28 4 Commissioning 29 4 1 Initial commissioning 29 4...

Страница 3: ...e information in this manual has limited validity The validity is highlighted by a symbol 1 2 3 Handling instructions Instructions on actions are shown as a list Actions of which the sequential order...

Страница 4: ...wledge of the subject of proper and appropriate installation and maintenance of heating climate control and cooling installations and heat pumps Electrical installation may be carried out only by elec...

Страница 5: ...e the energy supply company EVU is afforded the opportunity to control their network utilisation by changing the heat pump oper ating mode Information on the prerequisites and connection pos sibilitie...

Страница 6: ...ig erant or undefined operating states a safety switch off is per formed A corresponding fault signal provides an engineer with all the necessary information for troubleshooting 2 1 4 Electronic contr...

Страница 7: ...rated solar unit 008 1420944 05 2014 Operating instructions 7 2 2 2 Device external and internal design Daikin Altherma EHS X H P30A Fig 2 2 Design and components of the Daikin Altherma EHS X H P30A e...

Страница 8: ...ated solar unit 008 1420944 05 2014 2 x Product description 2 2 3 Device external and internal design Daikin Altherma EHS X H B P30A Fig 2 3 Design and components of the Daikin Altherma EHS X H B P30A...

Страница 9: ...rated solar unit 008 1420944 05 2014 Operating instructions 9 2 2 4 Device external and internal design Daikin Altherma EHS X H P50A Fig 2 4 Design and components of the Daikin Altherma EHS X H P50A e...

Страница 10: ...rated solar unit 008 1420944 05 2014 2 x Product description 2 2 5 Device external and internal design Daikin Altherma EHS X H B P50A Fig 2 5 Design and components of the Daikin Altherma EHS X H B P50...

Страница 11: ...cal backup heater EKBUxx 19 Submersible sensor sleeve for storage tank temperature sensor tDHW1 and tDHW2 20 Unpressurised storage tank water 21 Solar zone 22 Hot water zone 23 Safety overflow connect...

Страница 12: ...ackup Heater is used at inflow target temperatures of over 50 C the efficiency COP of the Daikin Altherma EHS X H can be affected negatively depending on the outside temperature 1 Clear text display 2...

Страница 13: ...BH is displayed In the case of no demands from the heat pump the abbreviation ES is displayed instead of the current inflow temperature The control system has switched to energy saving mode see sectio...

Страница 14: ...is displayed first Select the language using the rotary switch Confirm the changes with a brief press of the rotary switch When the system is switched on based on the stipulations set in the Controlle...

Страница 15: ...Info In this rotary switch position the rotary switch can be used to call up all the system temperatures the type of Daikin Altherma EHS X H various software information and the operating sta tuses o...

Страница 16: ...ks in normal mode RT Parameter Room thermostat Interlink fct Off Parameter Room thermostat On Heating or cooling demand No heating demand Parameter Interlink fct On priority Only frost protection IL1...

Страница 17: ...operating mode with the rotary switch Confirm the changes with a brief push of the rotary switch Daikin Altherma EHS X H operates in accordance with the set operating mode The current operating mode i...

Страница 18: ...t temporary heating programmes available see tab 3 6 which run according to priority after they have been activated Tab 3 6 Overview of temporary timer programmes 3 4 3 Temperature setting Daytime roo...

Страница 19: ...ogram Various different timer programmes are available that are set in the factory but which can be adjusted to suit to provide conven ient and individual room and hot water temperature control The ti...

Страница 20: ...me settings for one switching cycle in one weekday or block programme are also adopted for other time pe riods provided that they affect the same weekdays Ex amples referring to tab 3 7 a For the sing...

Страница 21: ...de according to the room temperature set in the rotary switch setting Set Temp Night in the parameter T Absence Hot water generation according to the set temperatures and switching cycles in the hot w...

Страница 22: ...ture of the mixer module EHS157068 For operation of the local equipment this must be activated again in the selection list parameter No selection Activating Deactivating normal operation Requirement A...

Страница 23: ...ng the exit button again or Briefly pressing the rotary switch or Selecting a different menu using the rotary switch 3 5 1 Manual Operation Manual Operation is used to regulate the Daikin Altherma EHS...

Страница 24: ...perature limits that have been set for the corre sponding heating circuit The room temperature measured in the living area may differ from the desired room temperature these deviations can be kept to...

Страница 25: ...sition or b via the room thermostat function cooling switching contact closed No heating demand active in the heating system The cooling characteristic curve is specified using the following four para...

Страница 26: ...onomously control the assigned heating circuit fully independently of the Daikin Altherma EHS X H More detailed explanations and possible setting values for this function can be seen in sections 6 2 3...

Страница 27: ...ian access rights permit all customer specific pa rameter settings in the Special Level to be reset to the factory setting according to tab 6 1 to tab 6 11 Possibility 3 If fundamental changes to the...

Страница 28: ...ated by the active hot water timer programme ON or from a separate timer programme OFF Circl Pump Interval Setting the interval control for an optional circulation pump Confirm the changes with a brie...

Страница 29: ...ltherma EHS X H not put into operation properly can lead to damage to property and the envi ronment Minimum requirements regarding the quality of filling and supplementary water Water hardness calcium...

Страница 30: ...ching of escaping water wearing appropriate protective clothing CAUTION A heating system that is shut down can freeze in the event of frost and may suffer damage If there is any risk of frost drain an...

Страница 31: ...o refer to fig 5 5 and drain the water content of the storage tank 5 1 2 Draining the heating circuit and hot water circuit Connect the drainage hose to the combined filling and drainage valve on the...

Страница 32: ...rried out by persons who are authorised and who have successfully completed qualifying technical or vocational training and who have taken part in advanced training sessions recognised by the relevant...

Страница 33: ...utes E E Keylock Function Release of the keylock function Off Button block cannot be activated On The button block can be activated using the rotary switch see chapter 3 3 E E Off On Off Access Rights...

Страница 34: ...detected the measured val ue can be corrected by the set value E E 5 0 to 5 0 kW 0 0 K 1 K T Flow Day Only if the parameter HC Function 1 is in delivery status is this function activated It can only...

Страница 35: ...e heat pump in hot water charging E E 20 95 min 50 min 1 min Tab 6 5 Parameter in rotary switch setting DHW Install Parameter Designation Access Setting range Min Max Factory setting Incre ment BE HF...

Страница 36: ...Set Temp Day Parameter Designation Access Setting range Min Max Factory setting Incre ment BE HF T Reduced Target room temperature for the setback times for the permanent timer programmes Automatic 1...

Страница 37: ...hh mm hh mm Off Also the cycles can be parametrised from Monday to Friday Saturday to Sunday and Monday to Sunday E E see chapter 3 4 7 see tab 3 8 15 min DHW Program 1 In this menu we can parametris...

Страница 38: ...ion S S 0 100 1 Qboh The amount of heat in the additional heat generator for hot water generation is displayed in kWh S S kWh Qchhp The amount of heat in the additional heat generator for heating mode...

Страница 39: ...apter 3 1 E E Off On Off Access Rights Entering access code Setting character by character like a combination lock see chapter 3 6 1 E E 0 9 0000 1 Tab 6 14 Parameter in rotary switch setting Configur...

Страница 40: ...hanged with a technician code Contact your specialist heating technician in this regard Setting from which outside temperature the cooling operation with the highest cooling infeed target temperature...

Страница 41: ...ion and maintenance carried out by authorised and trained HVAC engineers once a year ideally before the heating period This can prevent faults during the heating period Daikin recommends an inspection...

Страница 42: ...eration hot water temperatures 60 C arise Touching components during or after operation leads to a risk of burns Water discharged during maintenance and servic ing work can cause scalding on contact w...

Страница 43: ...2 Connect the filling hose fig 7 3 item 1 with back flush prevention 1 2 and an external pressure gauge on site to the KFE cock fig 7 3 item 2 and secure from slipping using a hose clamp 3 Open the wa...

Страница 44: ...the external pressure gauge again Where necessary refill with water via the KFE cock fig 7 3 item 2 13 Close the water cock fig 7 3 item 4 in the supply line 14 Disconnect the filler hose fig 7 3 item...

Страница 45: ...possible causes are listed Tips to correct the faults are also provided Information messages which are displayed without red back lighting normally result in no permanent limitations on the op eratio...

Страница 46: ...ol unit o do so disconnect the system from the power supply for at least 10 s and then switch on again Operating data are not updated Operating system of control unit crashed Carry out RESET of contro...

Страница 47: ...primary pressure in the expansion container and the water pressure if necessary refill the heating water and reset the primary pressure see chapter 7 5 Hot water supply is taking too much of the out...

Страница 48: ...tely open Fully vent the heating system and device internal circulation pump On the control unit rotary switch position Info check that there is sufficient water pressure 0 5 bar if necessary refill t...

Страница 49: ...ank is defective Have the expansion tank checked by a Daikin specialist heating technician Water pressure in the heating system is too high On the control unit rotary switch position Info check that t...

Страница 50: ...water circuit e g filling the hot water storage tank Flow pipe Part of the hydraulic circuit that directs the heated water from heat generator to the heating surfaces Heat exchanger A part that trans...

Страница 51: ...heating cooling economy and hot water cycles Water shortage overheating protection Safety device which switches off the heat generator automatically if there is a water shortage in order to avoid over...

Страница 52: ...T Room 3 Setpoint ____ C Time period On Off On Off On Off HC Program 1 Monday Tuesday Wednesday Thursday Friday Saturday Sunday HC Program 2 Monday Tuesday Wednesday Thursday Friday Saturday Sunday T...

Страница 53: ...resses in the RoCon system Switching cycle 1 Switching cycle 2 Switching cycle 3 Time period On Off On Off On Off Circulation Time Monday Tuesday Wednesday Thursday Friday Saturday Sunday Tab 10 3 Ind...

Страница 54: ...Operating instructions 54 Daikin Altherma EHS X H Daikin Altherma integrated solar unit 008 1420944 05 2014 10 x Notes 10 3 Other items...

Страница 55: ...rtant information 4 I Inflow target temperature 18 in cooling mode 25 in heating mode 24 with weather dependent regulation 26 Information messages 38 Initial commissioning 29 K KFE filling connection...

Страница 56: ...008 1420944_08 05 2014 Copyright Daikin...

Отзывы: