 Service and maintenance

1.

Dismount the protective cover (see section 7.2).

2.

Carry out a functional inspection of the Daikin Altherma 
EHS(X/H), as well as all installed accessory components 
(backup heater, solar installation) by checking the 
temperature display and the switching states in the individual 
modes.

3.

If a Daikin solar system of the DrainBack 

 

type is 

connected and in operation, switch this off and empty the 
solar panels.

4.

When operating the Daikin Altherma EHS(X/H) in a bivalent-
alternative system; switch off all heat generators and 
deactivate the bivalent control unit.

5.

Visual check of general condition of the Daikin Altherma 
EHS(X/H).

6.

Visual check of the water storage tank level (filling level 
indicator)

Top up the water if necessary (see section 7.4), deter-
mine the reason for the low water level and remedy it.

7.

Check the connection of the safety overflow and drain hose 
for leaks, free drainage and gradient.

If necessary, clean the safety overflow and drain hose and 
relay it; replace damaged parts.

8.

Visual check of connections, lines and safety pressure relief 
valve. In the event of damage, determine the cause.

Have damaged parts replaced by an expert heating tech-
nician.

9.

Check all electrical components, connections, and cables. 

Have damaged parts repaired or replaced by an expert 
heating technician.

10.

Check the water pressure of the cold water supply (<6 bar)

and if necessary the fitting or adjustment of the pressure 
reducer.

11.

Check the system water pressure on the RoCon HP controller 
of the Daikin Altherma EHS(X/H).

Top up the water in the heating system if necessary, until 
the pressure display is within the permitted range. (see 
section 7.5).

12.

Clean plastic surface of Daikin Altherma EHS(X/H) 

with a 

soft cloth and mild cleaning agent

. Do not use any 

cleaners with aggressive solvents (damage to the plastic 
surface may occur).

13.

Refit the cover (see section 7.2).

7.4 Filling and topping up the storage tank

WARNING!

Under the cover

 of the Daikin Altherma EHS(X/H) 

temperatures of up to 90 °C

 can arise during oper-

ation. During operation, 

hot water temperatures 

>60 °C arise.

– Touching components during or after operation 

leads to a 

risk of burns

– Water discharged during maintenance and servic-

ing work can cause 

scalding

 on contact with the 

skin.

Before carrying out servicing and maintenance 
work, allow the Daikin Altherma EHS(X/H) to cool 
down sufficiently.

Wear protective gloves.

WARNING!

Live parts can cause an 

electric shock 

on contact 

and cause fatal burns and injuries.

Before beginning work on live parts, 

disconnect

 

all of the systems circuits 

from the power supply 

(switch off main switch, disconnect fuse) and 
secure against unintentional restart.

Electrical connection and work on electrical 
components must only be carried out by 

qualified 

electricians

 in compliance with valid standards 

and guidelines as well as the specifications of the 
energy supply company.

Covers off equipment and servicing flaps are to 
be replaced 

as soon as the work is completed.

The Daikin Altherma EHS(X/H) is designed to be low-
maintenance. No corrosion protection equipment is re-
quired (such as expendable anodes). This means there 
is no need for maintenance work such as changing the 
protective anodes or cleaning the inside of the storage 
tank.

CAUTION!

Filling the storage container with excessive water 
pressure or at too great a flow speed can result in 
damage to the Daikin Altherma EHS(X/H).

Only fill with a water pressure <6 bar and a flow 
speed <15 l/min.

UK only!

CAUTION!

If filling or topping up the storage tank is done by 
means of the boiler filling and drain valve, a temporary 
filling loop must be used with the appropriate backflow 
prevention device in accordance with clause G24.2, 
Guidance to the Water Supply (Water Fittings) 
Regulations 1999.

If the storage temperature falls below a certain 
minimum value, the safety settings of the Daikin 
Altherma EHS(X/H) prevent the operation of the heat 
pump in the case of low external temperatures:

External temperature < -2 °C

, minimum 

storage 

temperature = 30 °C

External temperature < 12 °C

, minimum 

storage 

temperature = 23 °C

.

Without backup-heater:
The storage tank water must be heated to the minimum 
required storage temperature by an external heater.

With backup heater (EKBUxx): 
With an outdoor temperature < 12 °C and a storage 
tank temperature < 35 °C, the backup heater (EKBUxx) 
is switched on automatically on in order to heat up the 
storage tank water to at least 35 °C.

Содержание EHSX04P30A

Страница 1: ...EHS X H B04P30A EHS X H 08P30A EHS X H B08P30A EHS X H 08P50A EHS X H B08P50A EHS X H 16P50A EHS X H B16P50A Indoor unit for air water heat pumps Daikin Altherma integrated solar unit Operating instr...

Страница 2: ...egionella protection 27 3 6 7 Reset to factory settings Reset 27 3 6 8 Settings for optional circulation pump 27 3 6 9 Remote control via Internet 28 4 Commissioning 29 4 1 Initial commissioning 29 4...

Страница 3: ...e information in this manual has limited validity The validity is highlighted by a symbol 1 2 3 Handling instructions Instructions on actions are shown as a list Actions of which the sequential order...

Страница 4: ...wledge of the subject of proper and appropriate installation and maintenance of heating climate control and cooling installations and heat pumps Electrical installation may be carried out only by elec...

Страница 5: ...e the energy supply company EVU is afforded the opportunity to control their network utilisation by changing the heat pump oper ating mode Information on the prerequisites and connection pos sibilitie...

Страница 6: ...ig erant or undefined operating states a safety switch off is per formed A corresponding fault signal provides an engineer with all the necessary information for troubleshooting 2 1 4 Electronic contr...

Страница 7: ...rated solar unit 008 1420944 05 2014 Operating instructions 7 2 2 2 Device external and internal design Daikin Altherma EHS X H P30A Fig 2 2 Design and components of the Daikin Altherma EHS X H P30A e...

Страница 8: ...ated solar unit 008 1420944 05 2014 2 x Product description 2 2 3 Device external and internal design Daikin Altherma EHS X H B P30A Fig 2 3 Design and components of the Daikin Altherma EHS X H B P30A...

Страница 9: ...rated solar unit 008 1420944 05 2014 Operating instructions 9 2 2 4 Device external and internal design Daikin Altherma EHS X H P50A Fig 2 4 Design and components of the Daikin Altherma EHS X H P50A e...

Страница 10: ...rated solar unit 008 1420944 05 2014 2 x Product description 2 2 5 Device external and internal design Daikin Altherma EHS X H B P50A Fig 2 5 Design and components of the Daikin Altherma EHS X H B P50...

Страница 11: ...cal backup heater EKBUxx 19 Submersible sensor sleeve for storage tank temperature sensor tDHW1 and tDHW2 20 Unpressurised storage tank water 21 Solar zone 22 Hot water zone 23 Safety overflow connect...

Страница 12: ...ackup Heater is used at inflow target temperatures of over 50 C the efficiency COP of the Daikin Altherma EHS X H can be affected negatively depending on the outside temperature 1 Clear text display 2...

Страница 13: ...BH is displayed In the case of no demands from the heat pump the abbreviation ES is displayed instead of the current inflow temperature The control system has switched to energy saving mode see sectio...

Страница 14: ...is displayed first Select the language using the rotary switch Confirm the changes with a brief press of the rotary switch When the system is switched on based on the stipulations set in the Controlle...

Страница 15: ...Info In this rotary switch position the rotary switch can be used to call up all the system temperatures the type of Daikin Altherma EHS X H various software information and the operating sta tuses o...

Страница 16: ...ks in normal mode RT Parameter Room thermostat Interlink fct Off Parameter Room thermostat On Heating or cooling demand No heating demand Parameter Interlink fct On priority Only frost protection IL1...

Страница 17: ...operating mode with the rotary switch Confirm the changes with a brief push of the rotary switch Daikin Altherma EHS X H operates in accordance with the set operating mode The current operating mode i...

Страница 18: ...t temporary heating programmes available see tab 3 6 which run according to priority after they have been activated Tab 3 6 Overview of temporary timer programmes 3 4 3 Temperature setting Daytime roo...

Страница 19: ...ogram Various different timer programmes are available that are set in the factory but which can be adjusted to suit to provide conven ient and individual room and hot water temperature control The ti...

Страница 20: ...me settings for one switching cycle in one weekday or block programme are also adopted for other time pe riods provided that they affect the same weekdays Ex amples referring to tab 3 7 a For the sing...

Страница 21: ...de according to the room temperature set in the rotary switch setting Set Temp Night in the parameter T Absence Hot water generation according to the set temperatures and switching cycles in the hot w...

Страница 22: ...ture of the mixer module EHS157068 For operation of the local equipment this must be activated again in the selection list parameter No selection Activating Deactivating normal operation Requirement A...

Страница 23: ...ng the exit button again or Briefly pressing the rotary switch or Selecting a different menu using the rotary switch 3 5 1 Manual Operation Manual Operation is used to regulate the Daikin Altherma EHS...

Страница 24: ...perature limits that have been set for the corre sponding heating circuit The room temperature measured in the living area may differ from the desired room temperature these deviations can be kept to...

Страница 25: ...sition or b via the room thermostat function cooling switching contact closed No heating demand active in the heating system The cooling characteristic curve is specified using the following four para...

Страница 26: ...onomously control the assigned heating circuit fully independently of the Daikin Altherma EHS X H More detailed explanations and possible setting values for this function can be seen in sections 6 2 3...

Страница 27: ...ian access rights permit all customer specific pa rameter settings in the Special Level to be reset to the factory setting according to tab 6 1 to tab 6 11 Possibility 3 If fundamental changes to the...

Страница 28: ...ated by the active hot water timer programme ON or from a separate timer programme OFF Circl Pump Interval Setting the interval control for an optional circulation pump Confirm the changes with a brie...

Страница 29: ...ltherma EHS X H not put into operation properly can lead to damage to property and the envi ronment Minimum requirements regarding the quality of filling and supplementary water Water hardness calcium...

Страница 30: ...ching of escaping water wearing appropriate protective clothing CAUTION A heating system that is shut down can freeze in the event of frost and may suffer damage If there is any risk of frost drain an...

Страница 31: ...o refer to fig 5 5 and drain the water content of the storage tank 5 1 2 Draining the heating circuit and hot water circuit Connect the drainage hose to the combined filling and drainage valve on the...

Страница 32: ...rried out by persons who are authorised and who have successfully completed qualifying technical or vocational training and who have taken part in advanced training sessions recognised by the relevant...

Страница 33: ...utes E E Keylock Function Release of the keylock function Off Button block cannot be activated On The button block can be activated using the rotary switch see chapter 3 3 E E Off On Off Access Rights...

Страница 34: ...detected the measured val ue can be corrected by the set value E E 5 0 to 5 0 kW 0 0 K 1 K T Flow Day Only if the parameter HC Function 1 is in delivery status is this function activated It can only...

Страница 35: ...e heat pump in hot water charging E E 20 95 min 50 min 1 min Tab 6 5 Parameter in rotary switch setting DHW Install Parameter Designation Access Setting range Min Max Factory setting Incre ment BE HF...

Страница 36: ...Set Temp Day Parameter Designation Access Setting range Min Max Factory setting Incre ment BE HF T Reduced Target room temperature for the setback times for the permanent timer programmes Automatic 1...

Страница 37: ...hh mm hh mm Off Also the cycles can be parametrised from Monday to Friday Saturday to Sunday and Monday to Sunday E E see chapter 3 4 7 see tab 3 8 15 min DHW Program 1 In this menu we can parametris...

Страница 38: ...ion S S 0 100 1 Qboh The amount of heat in the additional heat generator for hot water generation is displayed in kWh S S kWh Qchhp The amount of heat in the additional heat generator for heating mode...

Страница 39: ...apter 3 1 E E Off On Off Access Rights Entering access code Setting character by character like a combination lock see chapter 3 6 1 E E 0 9 0000 1 Tab 6 14 Parameter in rotary switch setting Configur...

Страница 40: ...hanged with a technician code Contact your specialist heating technician in this regard Setting from which outside temperature the cooling operation with the highest cooling infeed target temperature...

Страница 41: ...ion and maintenance carried out by authorised and trained HVAC engineers once a year ideally before the heating period This can prevent faults during the heating period Daikin recommends an inspection...

Страница 42: ...eration hot water temperatures 60 C arise Touching components during or after operation leads to a risk of burns Water discharged during maintenance and servic ing work can cause scalding on contact w...

Страница 43: ...2 Connect the filling hose fig 7 3 item 1 with back flush prevention 1 2 and an external pressure gauge on site to the KFE cock fig 7 3 item 2 and secure from slipping using a hose clamp 3 Open the wa...

Страница 44: ...the external pressure gauge again Where necessary refill with water via the KFE cock fig 7 3 item 2 13 Close the water cock fig 7 3 item 4 in the supply line 14 Disconnect the filler hose fig 7 3 item...

Страница 45: ...possible causes are listed Tips to correct the faults are also provided Information messages which are displayed without red back lighting normally result in no permanent limitations on the op eratio...

Страница 46: ...ol unit o do so disconnect the system from the power supply for at least 10 s and then switch on again Operating data are not updated Operating system of control unit crashed Carry out RESET of contro...

Страница 47: ...primary pressure in the expansion container and the water pressure if necessary refill the heating water and reset the primary pressure see chapter 7 5 Hot water supply is taking too much of the out...

Страница 48: ...tely open Fully vent the heating system and device internal circulation pump On the control unit rotary switch position Info check that there is sufficient water pressure 0 5 bar if necessary refill t...

Страница 49: ...ank is defective Have the expansion tank checked by a Daikin specialist heating technician Water pressure in the heating system is too high On the control unit rotary switch position Info check that t...

Страница 50: ...water circuit e g filling the hot water storage tank Flow pipe Part of the hydraulic circuit that directs the heated water from heat generator to the heating surfaces Heat exchanger A part that trans...

Страница 51: ...heating cooling economy and hot water cycles Water shortage overheating protection Safety device which switches off the heat generator automatically if there is a water shortage in order to avoid over...

Страница 52: ...T Room 3 Setpoint ____ C Time period On Off On Off On Off HC Program 1 Monday Tuesday Wednesday Thursday Friday Saturday Sunday HC Program 2 Monday Tuesday Wednesday Thursday Friday Saturday Sunday T...

Страница 53: ...resses in the RoCon system Switching cycle 1 Switching cycle 2 Switching cycle 3 Time period On Off On Off On Off Circulation Time Monday Tuesday Wednesday Thursday Friday Saturday Sunday Tab 10 3 Ind...

Страница 54: ...Operating instructions 54 Daikin Altherma EHS X H Daikin Altherma integrated solar unit 008 1420944 05 2014 10 x Notes 10 3 Other items...

Страница 55: ...rtant information 4 I Inflow target temperature 18 in cooling mode 25 in heating mode 24 with weather dependent regulation 26 Information messages 38 Initial commissioning 29 K KFE filling connection...

Страница 56: ...008 1420944_08 05 2014 Copyright Daikin...

Отзывы: