Operating instructions

34

 Daikin Altherma EHS(X/H)

Daikin Altherma integrated solar unit

008.1420944 – 05/2014

x

 Parameter settings

6.2.3 Level "HC Configuration"

Sub-

le

vel

Parameter

Description

Access

Setting range

Min / Max

Factory 

setting

Incre-

ment

BE

HF

T-Frost Protect

Off: No frost protection of the heating circuit
Otherwise: If the outside temperature falls below the programmed value, the system 
switches into the frost protection mode (switches the pumps on). The function ceases 
once the outside temperature has risen to the set value +1 K.

E

E

Off, 

-15 to +5°C

0 °C

1 °C

Insulation

Setting the insulation standard of the building. This affects the way the heating curve and 
the heating times automatically adapt to the outside temperature.

E

E

Off

low

Normal

Good

Very Good

low

-

Heating

T-Outside lim day

Setting the automatic summer shutdown of the heating system. If the outside tempera-
ture measured and averaged out by the controller exceeds the set value by 1 K, the heat-
ing circuit is switched off. The heating is released again if the outdoor temperature falls 
below the set heat curve.

E

E

Off, 10 - 40 °C

19 °C

0.5 °C

T-Outside lim night

Parameter for setting the heating limit for "Switch-off" of the heating circuit during econ-
omy mode (functionality as for parameter [T-Outside lim day]).

E

E

Off, 10 - 40 °C

10 °C

0.5 °C

Heat-Slope

Only if the parameter [HC Function] = 0 is in delivery status is this function activated. It 
can only be changed with a technician code. Contact your specialist heating technician 
in this regard:
Setting the heating curve. The heating curve reflects the dependence of the set inflow 
temperature of the heating circuit on the outside temperature (see chapter 3.6.2).

E

E

0.0 - 3.0

0.5

0.1

Room Influence

Only if the room station 

 is connected and assigned to the heating circuit.

Setting of the impact the deviation of the room temperature measured by the EHS157034 
from the actual set value (see sections 3.4.3 and 3.4.4) has on the flow temperature.
Off: Exclusively weather-controlled flow temperature regulation
0: Purely weather-controlled flow temperature regulation, but internal heat recirculation 
pump continues to run until the next heating cycle following a heat demand during the 
setback time.
1-20: Causes a correction of the set flow temperature (parallel shift of the heat curve) by 
the set factor.

For example: If the measured temperature is 2 K below the set value, the set flow tem-
perature is raised 2-times the set value.

E

E

Off, 0 - 20

Off

1

T-Room Adj

Only if the room station 

 is connected and assigned to the heating circuit.

Individual adaptation of the room temperature relevant for control.
Should a systematic deviation of the room temperature as measured by the EHS157034 
from the actual temperature in the living area of this room be detected, the measured val-
ue can be corrected by the set value.

E

E

-5.0 to +5.0 kW

0.0 K

1 K

T-Flow Day

Only if the parameter [HC Function] = 1 is in delivery status is this function activated. It 
can only be changed with a technician code. Contact your specialist heating technician 
in this regard:
Setting the inflow target temperature for the heating circuit during the heating time when 
in operating mode: "Automatic 1", "Automatic 2", "Heating".

E

E

20 - 90°C

40 °C

1 °C

T-Flow Night

Only if the parameter [HC Function] = 1 is in delivery status is this function activated. It 
can only be changed with a technician code. Contact your specialist heating technician 
in this regard:
Setting the inflow target temperature for the heating circuit during the setback time when 
in operating mode: "Automatic 1", "Automatic 2", "Reducing".

E

E

10 - 90°C

10 °C

1 °C

Cooling (

Can be used only if the assigned heat generator has a cooling function.)

Start T-Out Cooling

Only if the parameter [HC Function] = 0 is in delivery status is this function activated. It 
can only be changed with a technician code. Contact your specialist heating technician 
in this regard:
Setting from which outside temperature the cooling operation with the highest cooling in-
feed target temperature [T-Flow Cooling start] starts (Setting condition: operating mode 
"Cooling").

E

E

15 - 45°C

24 °C

1 °C

Max T-Out Cooling

Only if the parameter [HC Function] = 0 is in delivery status is this function activated. It 
can only be changed with a technician code. Contact your specialist heating technician 
in this regard:
Setting to determine from which outdoor temperature the lowest cooling flow tempera-
ture [T-Flow Cooling max] is stipulated (Setting condition: operating mode "Cooling").

E

E

20 - 45°C

35 °C

1 °C

T-Flow Cooling start Only if the parameter [HC Function] = 0 is in delivery status is this function activated. It 

can only be changed with a technician code. Contact your specialist heating technician 
in this regard:
Setting the cooling inflow target temperature at the start of cooling mode (outside tem-
perature = parameter [Start T-Out Cooling]). 

E

E

5 - 25°C

18 °C

1 °C

T-Flow Cooling max Only if the parameter [HC Function] = 0 is in delivery status is this function activated. It 

can only be changed with a technician code. Contact your specialist heating technician 
in this regard:
Setting the minimum cooling inflow target temperature. This is kept constant relative to 
the outside temperature (parameter [Max T-Out Cooling]).

E

E

5 - 25°C

8 °C

1 °C

T-Flow Cooling

Only if the parameter [HC Function] = 1 is in delivery status is this function activated. It 
can only be changed with a technician code. Contact your specialist heating technician 
in this regard:
Setting the cooling inflow target temperature (fixed value) when cooling mode is active.

E

E

8 - 30°C

18 °C

1 °C

Cooling Setpoint adj Parallel displacement of the cooling characteristic curve to match the set value.

E

E

-5.0 to +5.0 kW

0.0 K

1 K

Tab. 6-3 Parameter in rotary switch setting "Configuration" level "HC Configuration"

Содержание EHSX04P30A

Страница 1: ...EHS X H B04P30A EHS X H 08P30A EHS X H B08P30A EHS X H 08P50A EHS X H B08P50A EHS X H 16P50A EHS X H B16P50A Indoor unit for air water heat pumps Daikin Altherma integrated solar unit Operating instr...

Страница 2: ...egionella protection 27 3 6 7 Reset to factory settings Reset 27 3 6 8 Settings for optional circulation pump 27 3 6 9 Remote control via Internet 28 4 Commissioning 29 4 1 Initial commissioning 29 4...

Страница 3: ...e information in this manual has limited validity The validity is highlighted by a symbol 1 2 3 Handling instructions Instructions on actions are shown as a list Actions of which the sequential order...

Страница 4: ...wledge of the subject of proper and appropriate installation and maintenance of heating climate control and cooling installations and heat pumps Electrical installation may be carried out only by elec...

Страница 5: ...e the energy supply company EVU is afforded the opportunity to control their network utilisation by changing the heat pump oper ating mode Information on the prerequisites and connection pos sibilitie...

Страница 6: ...ig erant or undefined operating states a safety switch off is per formed A corresponding fault signal provides an engineer with all the necessary information for troubleshooting 2 1 4 Electronic contr...

Страница 7: ...rated solar unit 008 1420944 05 2014 Operating instructions 7 2 2 2 Device external and internal design Daikin Altherma EHS X H P30A Fig 2 2 Design and components of the Daikin Altherma EHS X H P30A e...

Страница 8: ...ated solar unit 008 1420944 05 2014 2 x Product description 2 2 3 Device external and internal design Daikin Altherma EHS X H B P30A Fig 2 3 Design and components of the Daikin Altherma EHS X H B P30A...

Страница 9: ...rated solar unit 008 1420944 05 2014 Operating instructions 9 2 2 4 Device external and internal design Daikin Altherma EHS X H P50A Fig 2 4 Design and components of the Daikin Altherma EHS X H P50A e...

Страница 10: ...rated solar unit 008 1420944 05 2014 2 x Product description 2 2 5 Device external and internal design Daikin Altherma EHS X H B P50A Fig 2 5 Design and components of the Daikin Altherma EHS X H B P50...

Страница 11: ...cal backup heater EKBUxx 19 Submersible sensor sleeve for storage tank temperature sensor tDHW1 and tDHW2 20 Unpressurised storage tank water 21 Solar zone 22 Hot water zone 23 Safety overflow connect...

Страница 12: ...ackup Heater is used at inflow target temperatures of over 50 C the efficiency COP of the Daikin Altherma EHS X H can be affected negatively depending on the outside temperature 1 Clear text display 2...

Страница 13: ...BH is displayed In the case of no demands from the heat pump the abbreviation ES is displayed instead of the current inflow temperature The control system has switched to energy saving mode see sectio...

Страница 14: ...is displayed first Select the language using the rotary switch Confirm the changes with a brief press of the rotary switch When the system is switched on based on the stipulations set in the Controlle...

Страница 15: ...Info In this rotary switch position the rotary switch can be used to call up all the system temperatures the type of Daikin Altherma EHS X H various software information and the operating sta tuses o...

Страница 16: ...ks in normal mode RT Parameter Room thermostat Interlink fct Off Parameter Room thermostat On Heating or cooling demand No heating demand Parameter Interlink fct On priority Only frost protection IL1...

Страница 17: ...operating mode with the rotary switch Confirm the changes with a brief push of the rotary switch Daikin Altherma EHS X H operates in accordance with the set operating mode The current operating mode i...

Страница 18: ...t temporary heating programmes available see tab 3 6 which run according to priority after they have been activated Tab 3 6 Overview of temporary timer programmes 3 4 3 Temperature setting Daytime roo...

Страница 19: ...ogram Various different timer programmes are available that are set in the factory but which can be adjusted to suit to provide conven ient and individual room and hot water temperature control The ti...

Страница 20: ...me settings for one switching cycle in one weekday or block programme are also adopted for other time pe riods provided that they affect the same weekdays Ex amples referring to tab 3 7 a For the sing...

Страница 21: ...de according to the room temperature set in the rotary switch setting Set Temp Night in the parameter T Absence Hot water generation according to the set temperatures and switching cycles in the hot w...

Страница 22: ...ture of the mixer module EHS157068 For operation of the local equipment this must be activated again in the selection list parameter No selection Activating Deactivating normal operation Requirement A...

Страница 23: ...ng the exit button again or Briefly pressing the rotary switch or Selecting a different menu using the rotary switch 3 5 1 Manual Operation Manual Operation is used to regulate the Daikin Altherma EHS...

Страница 24: ...perature limits that have been set for the corre sponding heating circuit The room temperature measured in the living area may differ from the desired room temperature these deviations can be kept to...

Страница 25: ...sition or b via the room thermostat function cooling switching contact closed No heating demand active in the heating system The cooling characteristic curve is specified using the following four para...

Страница 26: ...onomously control the assigned heating circuit fully independently of the Daikin Altherma EHS X H More detailed explanations and possible setting values for this function can be seen in sections 6 2 3...

Страница 27: ...ian access rights permit all customer specific pa rameter settings in the Special Level to be reset to the factory setting according to tab 6 1 to tab 6 11 Possibility 3 If fundamental changes to the...

Страница 28: ...ated by the active hot water timer programme ON or from a separate timer programme OFF Circl Pump Interval Setting the interval control for an optional circulation pump Confirm the changes with a brie...

Страница 29: ...ltherma EHS X H not put into operation properly can lead to damage to property and the envi ronment Minimum requirements regarding the quality of filling and supplementary water Water hardness calcium...

Страница 30: ...ching of escaping water wearing appropriate protective clothing CAUTION A heating system that is shut down can freeze in the event of frost and may suffer damage If there is any risk of frost drain an...

Страница 31: ...o refer to fig 5 5 and drain the water content of the storage tank 5 1 2 Draining the heating circuit and hot water circuit Connect the drainage hose to the combined filling and drainage valve on the...

Страница 32: ...rried out by persons who are authorised and who have successfully completed qualifying technical or vocational training and who have taken part in advanced training sessions recognised by the relevant...

Страница 33: ...utes E E Keylock Function Release of the keylock function Off Button block cannot be activated On The button block can be activated using the rotary switch see chapter 3 3 E E Off On Off Access Rights...

Страница 34: ...detected the measured val ue can be corrected by the set value E E 5 0 to 5 0 kW 0 0 K 1 K T Flow Day Only if the parameter HC Function 1 is in delivery status is this function activated It can only...

Страница 35: ...e heat pump in hot water charging E E 20 95 min 50 min 1 min Tab 6 5 Parameter in rotary switch setting DHW Install Parameter Designation Access Setting range Min Max Factory setting Incre ment BE HF...

Страница 36: ...Set Temp Day Parameter Designation Access Setting range Min Max Factory setting Incre ment BE HF T Reduced Target room temperature for the setback times for the permanent timer programmes Automatic 1...

Страница 37: ...hh mm hh mm Off Also the cycles can be parametrised from Monday to Friday Saturday to Sunday and Monday to Sunday E E see chapter 3 4 7 see tab 3 8 15 min DHW Program 1 In this menu we can parametris...

Страница 38: ...ion S S 0 100 1 Qboh The amount of heat in the additional heat generator for hot water generation is displayed in kWh S S kWh Qchhp The amount of heat in the additional heat generator for heating mode...

Страница 39: ...apter 3 1 E E Off On Off Access Rights Entering access code Setting character by character like a combination lock see chapter 3 6 1 E E 0 9 0000 1 Tab 6 14 Parameter in rotary switch setting Configur...

Страница 40: ...hanged with a technician code Contact your specialist heating technician in this regard Setting from which outside temperature the cooling operation with the highest cooling infeed target temperature...

Страница 41: ...ion and maintenance carried out by authorised and trained HVAC engineers once a year ideally before the heating period This can prevent faults during the heating period Daikin recommends an inspection...

Страница 42: ...eration hot water temperatures 60 C arise Touching components during or after operation leads to a risk of burns Water discharged during maintenance and servic ing work can cause scalding on contact w...

Страница 43: ...2 Connect the filling hose fig 7 3 item 1 with back flush prevention 1 2 and an external pressure gauge on site to the KFE cock fig 7 3 item 2 and secure from slipping using a hose clamp 3 Open the wa...

Страница 44: ...the external pressure gauge again Where necessary refill with water via the KFE cock fig 7 3 item 2 13 Close the water cock fig 7 3 item 4 in the supply line 14 Disconnect the filler hose fig 7 3 item...

Страница 45: ...possible causes are listed Tips to correct the faults are also provided Information messages which are displayed without red back lighting normally result in no permanent limitations on the op eratio...

Страница 46: ...ol unit o do so disconnect the system from the power supply for at least 10 s and then switch on again Operating data are not updated Operating system of control unit crashed Carry out RESET of contro...

Страница 47: ...primary pressure in the expansion container and the water pressure if necessary refill the heating water and reset the primary pressure see chapter 7 5 Hot water supply is taking too much of the out...

Страница 48: ...tely open Fully vent the heating system and device internal circulation pump On the control unit rotary switch position Info check that there is sufficient water pressure 0 5 bar if necessary refill t...

Страница 49: ...ank is defective Have the expansion tank checked by a Daikin specialist heating technician Water pressure in the heating system is too high On the control unit rotary switch position Info check that t...

Страница 50: ...water circuit e g filling the hot water storage tank Flow pipe Part of the hydraulic circuit that directs the heated water from heat generator to the heating surfaces Heat exchanger A part that trans...

Страница 51: ...heating cooling economy and hot water cycles Water shortage overheating protection Safety device which switches off the heat generator automatically if there is a water shortage in order to avoid over...

Страница 52: ...T Room 3 Setpoint ____ C Time period On Off On Off On Off HC Program 1 Monday Tuesday Wednesday Thursday Friday Saturday Sunday HC Program 2 Monday Tuesday Wednesday Thursday Friday Saturday Sunday T...

Страница 53: ...resses in the RoCon system Switching cycle 1 Switching cycle 2 Switching cycle 3 Time period On Off On Off On Off Circulation Time Monday Tuesday Wednesday Thursday Friday Saturday Sunday Tab 10 3 Ind...

Страница 54: ...Operating instructions 54 Daikin Altherma EHS X H Daikin Altherma integrated solar unit 008 1420944 05 2014 10 x Notes 10 3 Other items...

Страница 55: ...rtant information 4 I Inflow target temperature 18 in cooling mode 25 in heating mode 24 with weather dependent regulation 26 Information messages 38 Initial commissioning 29 K KFE filling connection...

Страница 56: ...008 1420944_08 05 2014 Copyright Daikin...

Отзывы: