Faults and malfunctions
Installation and maintenance instructions
52
Daikin Altherma EHS(X/H)
Daikin Altherma integrated solar unit
008.1444099_00 – 07/2018 – EN
Code
Component/Designation
Error
Possible fault rectification
E9055 Room temperature sensor
(optional)
Room temperature sensor fault
Sensor or connecting cable defective
▪ Check, replace
E9056 Outside temperature sensor
(optional)
Room temperature sensor fault
Sensor or connecting cable defective
▪ Check, replace
E9057
Overpressure in the refrigerant circuit; shutdown by
high-pressure switch
Please contact your service partner
E9058 Controller housing in the
outdoor unit
Temperature fault
Please contact your service partner
E9059 Inverter in the outdoor unit
Temperature fault
Please contact your service partner
E9060 Software
Screed program not ended correctly
▪ Check the screed program
▪ Restart the program if necessary
W8006 Pressure sensor DS
Pressure loss warning
Warning message: Maximum permissible pressure
drop exceeded.
Insufficient water in the heating system.
▪ Check the heating system for leaks, top up water.
W8007
Water pressure in heating system too high
Warning message: Water pressure has exceeded
permissible maximum value.
▪ Diaphragm expansion vessel defective or incor-
rect admission pressure set.
▪ Check, replace.
▪ [Max Pressure] parameter setting too low.
▪ Set the parameter if necessary. If the setting is
correct,
▪ drain water to reduce system pressure.
Tab. 8-2
Fault codes
INFORMATION
Observe maximum temperature sensor tightening torque
(see
).
Fig. 8-1
Components in the heat pump circuit
Item
Designation
Item
Designation
a
Plate heat ex-
changer (con-
denser)
N
4-way switch
valve (—>
Heating, ····>
Cooling)
b
Fan motor
O
Inverter circuit
board
c
Fin-cooled heat
exchanger (va-
poriser)
R1T
External tem-
perature sensor
Item
Designation
Item
Designation
d
R2T
Outlet temperat-
ure sensor (re-
frigerant com-
pressor)
e
Filter
R3T
(2)
Inlet temperat-
ure sensor (re-
frigerant com-
pressor)
f
Electronic ex-
pansion valve
R4T
(2)
Temperature
sensor of fin-
cooled heat ex-
changer input
g
Service valve
(fluid line)
R5T
Temperature
sensor of fin-
cooled heat ex-
changer middle
h
Service valve
with mainten-
ance connec-
tion (gas line)
R6T
(2)
Fluid line tem-
perature sensor
(t
L2
)
i
Accumulator
R10T
(2)
Temperature
sensor on in-
verter circuit
board
K
Refrigerant
compressor
S1PH
High-pressure
switch
Tab. 8-3
(2)
Only for 11-16 kW heat pump outdoor units.