Operation manual

7

EDLQ036~054B EBLQ036~054BA6VJU1

Unit for air to water heat pump system

4PW56183-1

Schedule timer operation

In schedule timer operation, the installation is controlled by the
schedule timer. The actions programmed in the schedule timer will be
executed automatically.

The schedule timer always follows the last command until a new
command is given. This means that the user can temporarily overrule
the last executed programmed command by manual operation (Refer
to  "Manual operation" on page 6). The schedule timer will regain
control over the installation as soon as the next programmed
command of the schedule timer occurs.

The schedule timer is enabled (

p

 icon displayed) or disabled (

p

 icon

not displayed), by pressing the 

pr

 button.

To set up the SCHEDULE TIMER refer to chapter "Programming and
consulting the schedule timer" on page 8.

What can the schedule timer do?

The schedule timer allows the programming of:

1.

Space heating and space cooling (refer to "Programming space
cooling or space heating" on page 8)
Switch on the desired mode at a scheduled time, in combination
with a set point (weather dependent or manually set). Five
actions per weekday can be programmed, totalling 35 actions.

2.

Quiet mode (refer to "Programming quiet mode, booster heating
or domestic water heating" on page 9)
Switch the mode on or off at a scheduled time. Five actions can
be programmed per mode. These actions are repeated daily.

3.

Booster heating (refer to "Programming quiet mode, booster
heating or domestic water heating" on page 9)
Allow or disallow booster heating at a scheduled time. Five
actions can be programmed per mode. These actions are
repeated daily.

4.

Domestic water heating (refer to "Programming quiet mode,
booster heating or domestic water heating" on page 9)
Switch the mode on or off at a scheduled time. Five actions can
be programmed per mode. These actions are repeated daily.

What can the schedule timer NOT do?

The schedule timer can not change the operation mode from space
cooling to space heating or vice versa.

How to interpret the programmed actions

To be able to understand the behaviour of your installation when the
schedule timer is enabled, it is important to keep in mind that the
"last" programmed command overruled the "preceding" programmed
command and will remain active until the "next" programmed
command occurs.

Example: imagine the actual time is 17:30 and actions are
programmed at 13:00, 16:00 and 19:00. The "last" programmed
command (16:00) overruled the "previous" programmed command
(13:00) and will remain active until the "next" programmed command
(19:00) occurs.

So in order to know the actual setting, one should consult the last
programmed command. It is clear that the "last" programmed
command may date from the day before. Refer to "Consulting
programmed actions" on page 10.

Only use the 

pr

  button to enable or disable the

schedule timer. The schedule timer overrules the 

y

button. The 

y

  button only overrules the schedule

timer until the next programmed action.

If the auto restart function is disabled, the schedule
timer will not be activated when power returns to the
unit after a power supply failure. Press the 

pr

 button

to enable the schedule timer again.

When power returns after a power supply failure, the
auto restart function reapplies the user interface
settings at the time of the power supply failure.

It is therefore recommended to leave the auto restart
function enabled.

The programmed schedule is time driven. Therefore, it
is essential to set the clock and the day of the week
correctly. Refer to "Setting the clock" on page 5.

Manually adjust the clock for summertime and
wintertime. Refer to "Setting the clock" on page 5.

A power failure exceeding 2 hours will reset the clock
and the day of the week. The schedule timer will
continue operation, but with a disordered clock. Refer
to  "Setting the clock" on page 5  to adjust the clock
and the day of the week.

The actions programmed in the schedule timer will not
be lost after a power failure so that reprogramming the
schedule timer is not required.

NOTE

When the unit is connected to an external room
thermostat, the schedule timer for space cooling and
space heating is overruled by the external room
thermostat.

The programmed actions are not stored according to
their timing but according to the time of programming.
This means that the action that was programmed first
gets action number 1, even though it is executed after
other programmed action numbers.

When the schedule timer switches space heating or
space cooling 

x

, the controller will also be

switched off. Note that this has no influence on
domestic water heating.

During schedule timer operation, someone may have
altered the actual settings manually (in other words, the
"last" command was overruled manually). The icon 

p

,

indicating the schedule timer operation, may still be
displayed, giving the impression that the "last" command
settings are still active. The "next" programmed command
will overrule the altered settings and return to the original
program.

1D_OM_4PW56183-1.book  Page 7  Monday, September 21, 2009  11:09 AM

Содержание EDLQ036BA6VJU1

Страница 1: ...glish Manuel d utilisation Unit pour syst me de pompe chaleur air eau Fran ais Manual de operaci n Unidad para bomba de calor de aire agua Espa ol EDLQ036BA6VJU1 EDLQ048BA6VJU1 EDLQ054BA6VJU1 EBLQ036B...

Страница 2: ...low temperature radiators domestic hot water tank option and solar kit option Heating cooling units and heating only units The monoblock unit range consists of two main versions a heating cooling EB...

Страница 3: ...oom thermostat connected to the unit This will prevent excessive space heating and will stop the unit and the circulation pump when the room temperature is above the thermostat set point Next recommen...

Страница 4: ...e icons indicate the current operation mode s space heating h space cooling c domestic water heating w or quiet mode s Within limits different modes can be combined e g space heating and domestic wate...

Страница 5: ...itching between cooling or heating mode provided the unit is not a heating only unit When the unit is connected with an external room thermostat this button is not operable and the icon e is shown 26...

Страница 6: ...hot water tank by heat pump when the space heating space cooling operation has reached its temperature set point or heat pump domestic water heating has a higher demand request than space side depends...

Страница 7: ...r heating operation 1 Press v for 5 seconds to activate powerful domestic water heating operation Icons w and m start flashing Powerful domestic water heating is deactivated automatically when the set...

Страница 8: ...rogrammed at 13 00 16 00 and 19 00 The last programmed command 16 00 overruled the previous programmed command 13 00 and will remain active until the next programmed command 19 00 occurs So in order t...

Страница 9: ...set point Conversely when programming cooling actions time and setpoint heating actions are added automatically at the same time but with the default heating set point The set points of these automati...

Страница 10: ...s to store the programmed actions If the button is pressed when action number 3 is displayed actions 1 2 and 3 are stored but 4 and 5 are deleted You automatically return to step 6 By pressing the pr...

Страница 11: ...m it is possible to copy all programmed actions of a specific day to the next day e g copy all programmed actions from 1 to 2 To copy programmed actions to the next day proceed as follows 1 Press the...

Страница 12: ...e z button to exit FIELD SET MODE Detailed description 0 User permission level If required certain user interface buttons can be made unavailable for the user Three permission levels are defined see t...

Страница 13: ...tus defines whether the disinfection function is turned on 1 or off 0 2 02 Start time time of the day at which the domestic water should be heated 2 03 Set point high water temperature to be reached 2...

Страница 14: ...it set to its default value C Setup on EKRP1HB digital I O PCB Solar priority mode C 00 Solar priority mode setting for information concerning the EKSOLHW solar kit refer to the installation manual o...

Страница 15: ...1 02 Start time 23 00 0 00 23 00 1 00 hour 03 Set point 158 70 104 176 40 80 9 5 F C 04 Interval 10 5 60 5 min 3 Auto restart 00 Status 0 ON 0 1 4 Space heating off temperature 00 Installation relate...

Страница 16: ...Read only C Setup on EKRP1HB digital I O PCB 00 Solar priority mode setting 0 0 1 1 01 Installation related setting 02 Installation related setting 03 Installation related setting 04 Installation rela...

Страница 17: ...ts must be done by a qualified installer in accordance with relevant local and national legislation Units must be treated at a specialized treatment facility for re use recycling and recovery By ensur...

Страница 18: ...mestique option et au kit solaire option Unit s de chauffage refroidissement et unit s de chauffage uniquement La gamme des unit s monobloc consiste en deux versions princi pales une version chauffage...

Страница 19: ...ge de locaux excessif et arr tera l unit et la pompe de circulation lorsque la temp rature ambiante d passe le point de consigne du thermostat Les recommandations suivantes s appliquent uniquement aux...

Страница 20: ...a DEL clignote si un dysfonctionnement se produit Lorsque la DEL est teinte le refroidissement ou le chauffage de locaux est inactif pendant que les autres modes de fonctionnement peuvent toujours tre...

Страница 21: ...NCTIONNEMENT TEST t Cette ic ne indique que l unit fonctionne en mode test Pri re de se r f rer au manuel d installation 23 CODE DE REGLAGE SUR PLACE Ce code repr sente le code de la liste des r glage...

Страница 22: ...leur du syst me int rieur pour emp cher le gel du syst me ext rieur Apr s un maximum de 8 minutes en mode d givrage le syst me revient en mode chauffage de locaux Mode de refroidissement de locaux c D...

Страница 23: ...e ment de l affichage Plage de temp rature pour le chauffage d eau domestique 86 F 172 F 30 C 78 C 3 Appuyer sur le bouton v pour activer le chauffage d eau domestique w L ic ne w dispara t de l cran...

Страница 24: ...programm es 13h00 16h00 et 19h00 La derni re commande programm e 16 00 a supplant la commande programm e pr c dente 13 00 et restera active jusqu ce que la commande programm e suivante 19 00 se produi...

Страница 25: ...efroidissement sont ajout es automatiquement en m me temps mais avec le point de con signe de refroidissement par d faut d fini Inversement lors de la programmation des actions de refroidissement dur...

Страница 26: ...refroidissement et le chauffage de la commande 9 r gler la temp rature au moyen des boutons bi et bj a pour s lectionner le calcul de temp rature automatique uniquement en mode de chauffage 10 Utilise...

Страница 27: ...ions de refroidissement ou de chauffage de locaux La consultation du refroidissement ou du chauffage de locaux s effectue comme suit 1 Utiliser le bouton pour s lectionner le mode de fonctionnement re...

Страница 28: ...fonc lorsque le num ro d action 3 est affich les actions 1 2 et 3 sont sauvegard es mais 4 et 5 sont supprim es Suppression d un mode 1 Appuyer sur le bouton Le mode r el clignote 2 Utiliser les bouto...

Страница 29: ...ultan ment sur le touches pfi et pfj puis en appuyant tout de suite apr s sur les touches s et ba et en maintenant les 4 touches enfonc es pendant au moins 5 secondes en mode normal A noter qu aucune...

Страница 30: ...on S applique uniquement aux installations avec un ballon d eau chaude domestique La fonction de d sinfection d sinfecte le ballon d eau chaude domestique en chauffant p riodiquement l eau domestique...

Страница 31: ...sup rieures sont requises Dans certains cas cela peut entra ner un fonctionnement moins silencieux de l unit pour satisfaire aux performances requises A 00 Type de mode discret d finit si le mode disc...

Страница 32: ...t 1 ON 0 1 02 Heure de d but 23 00 0 00 23 00 1 00 heure 03 Point de consigne 158 70 104 176 40 80 9 5 F C 04 Intervalle 10 5 60 5 min 3 Red marrage automatique 00 Statut 0 ON 0 1 4 Temp rature d arr...

Страница 33: ...ecture seule 04 Ne s applique pas 0 Lecture seule C Configuration sur la carte d E S num rique EKRP1HB 00 R glage du mode de priorit solaire 0 0 1 1 01 R glage relatif l installation 02 R glage relati...

Страница 34: ...e utilisation car ces tuyaux peuvent tre chauds Il y a un risque de br lures aux mains Pour viter des blessures laisser le temps aux tuyaux de revenir une temp rature normale ou veiller porter des gan...

Страница 35: ...in s s par ment des ordures m nag res non tri es Ne pas essayer de d monter vous m me l appareil le d montage du syst me ainsi que le traitement du r frig rant de l huile et d autres composants doiven...

Страница 36: ...ia opcional y kit solar opcional Unidades de s lo calefacci n refrigeraci n La gama de unidades monobloque consta de dos versiones princi pales una versi n de calefacci n refrigeraci n EB y una versi...

Страница 37: ...termostato en la estancia conectado a la unidad As se evitar el exceso de calefacci n del espacio interior y se har parar la unidad y la bomba de circulaci n cuando la temperatura de la estancia sea...

Страница 38: ...do de calefacci n o el modo de refrigeraci n est n inactivos mientras el resto de los modos de funcionamiento pueden permanecer activados 3 ICONOS DEL MODO OPERATIVO hcws Estos iconos indican el modo...

Страница 39: ...C DIGO DE AJUSTE DE OBRA Este c digo representa el c digo de la lista de ajustes de obra Consulte el manual de instalaci n 24 C DIGO DE ERROR Este c digo procede de la lista de c digos de error y s l...

Страница 40: ...anitaria es posible que se congele el intercambiador de calor externo debido a las bajas temperaturas exteriores Si esto sucede se activar el modo de desescarche del sistema Esta funci n invertir el c...

Страница 41: ...l agua sanitaria w 1 Pulse el bot n v para activar el modo de calentamiento del agua sanitaria w El icono w aparecer en la pantalla 2 Pulse el bot n wi o wj para mostrar la temperatura de referencia a...

Страница 42: ...iariamente Qu posibilidades NO ofrece el programador El temporizador de programaci n no puede cambiar el modo de funcionamiento de refrigeraci n a calefacci n o viceversa C mo interpretar las acciones...

Страница 43: ...de referencia las acciones de calefacci n se a aden autom tica mente al mismo tiempo pero con el punto de referencia de calefacci n predefinido por defecto Los puntos de referencia de estas acciones a...

Страница 44: ...eraci n y el de calefacci n y apagar el controlador 9 ajuste la temperatura mediante los botones bi y bj a para seleccionar el c lculo autom tico de temperatura s lo en modo calefacci n 10 Pulse los b...

Страница 45: ...geraci n o calefacci n La consulta del modo de refrigeraci n o de calefacci n se realiza del siguiente modo 1 Pulse el bot n para seleccionar el modo de funcionamiento refrigeraci n o calefacci n que...

Страница 46: ...1 Pulse el bot n El modo real parpadea 2 Pulse los botones pi y pj para seleccionar el modo que desee borrar modo susurrante s resistencia el ctrica m o calentamiento de agua sanitaria w El modo sele...

Страница 47: ...mult neamente inmediatamente seguido por los botones s y ba durante al menos 5 segundos en modo normal Tenga presente que no se proporciona ninguna indicaci n en la interfaz de usuario Cuando el nivel...

Страница 48: ...eraturas exteriores m s c lidas Hi_A se requiere menos agua caliente 2 Funci n de desinfecci n S lo disponible en las instalaciones con dep sito de agua caliente sanitaria La funci n de desinfecci n d...

Страница 49: ...nsecuencia un bajo rendimiento En el modo susurrante B podr a anularse el funcionamiento a bajo nivel de ruido cuando se requiera un rendimiento superior En determinados casos esto podr a tener como c...

Страница 50: ...ejemplo 23 E 02 Lectura de la identificaci n de modelo de la unidad ejemplo 11 E 03 Lectura de la temperatura del refrigerante l quido E 04 Lectura de la temperatura del agua a la entrada NOTA Las lec...

Страница 51: ...e ajuste punto de referencia 158 70 104 176 40 80 9 5 F C 04 Intervalo 10 5 60 5 min 3 Reinicio autom tico 00 Estado 0 ON 0 1 4 Temperatura de calefacci n de habitaciones OFF 00 Ajuste relacionado con...

Страница 52: ...P1HB 00 Ajuste del modo de prioridad solar 0 0 1 1 01 Ajuste relacionado con la instalaci n 02 Ajuste relacionado con la instalaci n 03 Ajuste relacionado con la instalaci n 04 Ajuste relacionado con...

Страница 53: ...de agua durante ni inmediata mente despu s de la operaci n porque pueden estar calientes Puede sufrir quemaduras en las manos Para evitar lesiones deje que las tuber as vuelvan a su temperatura normal...

Страница 54: ...esiduos dom sticos no clasificados No intente desmontar el sistema usted mismo El desmantelamiento del sistema as como el tratamiento del refrigerante aceite y otros componentes debe ser efectuado por...

Страница 55: ......

Страница 56: ...DAIKIN AIR CONDITIONING AMERICAS 1645 Wallace Drive Suite 110 Carrollton TX 75006 Copyright Daikin 4PW56183 1...

Отзывы: