INSTALLATION MANUAL                                                                                        FXMQ_PB/FBQ ECONOMIZER 

 

 

Fig. 3. Field Wiring Diagram 

7.

 

System Setup 

 
To use the keypad when working with Setpoints, System, and Advanced Settings, Checkout tests, and Alarms: 
 

 

Navigate to the desired menu 

 

 

Press the            button (Enter) to display the first item in the currently displayed menu.     

 

 

Use the            and          buttons to scroll to the desired parameter 

 

 

Press the            button (Enter) to display the value of the currently displayed item. 

 

 

Press the            button to increase (change) the displayed parameter value. 

 

 

Press the            button to decrease (change) the displayed parameter value. 

 

 

Press the            button to accept the displayed value and store it in non-volatile RAM. 

 

 

CHANGE STORED displays. 

 

 

Press the            button (Enter) to return to the current parameter. 

 

 

Press the            button (MenuUp/Exit) to return to the previous menu.     

 
Note: Refer to the Honeywell JADE 7220 product data sheet for specific information on settings and parameters available for use.     

http://customer.honeywell.com/techlit/pdf/63-0000s/63-2700.pdf

   

 

Содержание ECONMQ12P-8-1K

Страница 1: ...1 INSTALLATION MANUAL FXMQ_PB FBQ Economizer MODELS ECONMQ12P 8 1K ECONMQ12P 13 1K ECONMQ30P 8 1K ECONMQ30P 13 1K ECONMQ48P 8 1K ECONMQ48P 13 1K ...

Страница 2: ...el Number Description Applicable Indoor Units Field Supplied Power ECONMQ12P 8 1K Fully modulating economizer 1 12 x 20 x 2 MERV 8 filter FXMQ07PBVJU FXMQ09PBVJU 24VAC ECONMQ12P 13 1K Fully modulating economizer 1 12 x 20 x 4 MERV 13 filter FXMQ07PBVJU FXMQ09PBVJU 24VAC ECONMQ30P 8 1K Fully modulating economizer 1 12 x 20 x 2 MERV 8 filter FXMQ15PBVJU FXMQ18PBVJU FXMQ24PBVJU FBQ18PVJU FBQ24PVJU FB...

Страница 3: ...ER 3 2 Dimensions Kit Model A B1 B2 C D E ECONMQ12P 8 1K 21 625 13 00 9 75 24 25 7 50 17 00 ECONMQ12P 13 1K ECONMQ30P 8 1K 36 4375 13 00 9 75 24 25 7 50 32 00 ECONMQ30P 13 1K ECONMQ48P 8 1K 52 1875 13 00 9 75 24 25 7 50 48 00 ECONMQ48P 13 1K ...

Страница 4: ...zer and indoor unit g Place the return air duct and fresh air duct over the economizer return and fresh air dampers Note Economizer section may be rotated 180 for bottom fresh air connection 5 Operation Mode A Cooling Mode 1 While in cooling thermo on with the ambient temperature and humidity above the enthalpy control set point the fresh air damper will open to the minimum vent position and the c...

Страница 5: ... the minimum vent position This setpoint can be adjusted as needed Figure 2 Single Enthalpy Curve and Boundaries Table 3 Single Enthalpy and Dual Enthalpy High Limit Curves E Settings 1 The mixed air temperature set point must be no lower than 65 FDB for continuous operation This may be configured down to 60 FDB however thermo off may be carried out due to freeze protection 2 The economizer is rec...

Страница 6: ...ay the value of the currently displayed item Press the button to increase change the displayed parameter value Press the button to decrease change the displayed parameter value Press the button to accept the displayed value and store it in non volatile RAM CHANGE STORED displays Press the button Enter to return to the current parameter Press the button MenuUp Exit to return to the previous menu No...

Отзывы: