INSTALLATION MANUAL                                                                                        FXMQ_PB/FBQ ECONOMIZER 

 

3.

 

Shipping and Packing List 

Economizer package contains: 
1 ea. 

 Economizer Assembly 

1 ea. 

 Install Instructions Including Wiring Diagram 

3 ea. 

 Wire Ties 

1 ea. 

 Honeywell JADE Operation Manual   

 

4.

 

Installation

 

 

Before starting the installation work, carefully read the following safety precautions.

 

 

a)

 

Disconnect all power to the indoor unit 

b)

 

Remove the factory duct flange from the return inlet of the indoor unit. 

c)

 

Attach the economizer over the return opening with sheet metal screws.   

d)

 

Remove the control access panel on the economizer and indoor unit.     

e)

 

Route wires from the indoor unit control box to the terminal strip located in the economizer control panel.    Route a 
field-supplied 24VAC power supply to the economizer terminal strip and the KRP1C74. Refer to wiring diagram, Figure 3.   

f)

 

Replace the control access panels on the economizer and indoor unit. 

g)

 

Place the return air duct and fresh air duct over the economizer return and fresh air dampers.   

 

Note

: Economizer section may be rotated 180° for bottom fresh air connection.   

 

5.

 

Operation Mode 

 

A.

 

Cooling Mode 

1.

 

While in cooling thermo-on, with the ambient temperature and humidity above the enthalpy control set point, the 
fresh air damper will open to the minimum vent position and the cooling demand is satisfied by the compressor.   
The minimum vent position is site-configurable.   
 

2.

 

While in cooling thermo-on, with the ambient temperature and humidity below the enthalpy control set point, the 
fresh air damper will modulate to ensure the mixed air supplied to the indoor unit is no lower than the set point 
temperature. This will reduce the mechanical cooling of the indoor unit and VRV System . The mixed air set point 
should be configured in accordance with the operating conditions of the fan coil. 

 

 

Figure 1. JADE Economizer Module 

 

B.

 

Heating Mode 

1.

 

While in heating thermo-on, the damper will open to the minimum position. The minimum position is 
site-configurable. 

 
 
 

Содержание ECONMQ12P-8-1K

Страница 1: ...1 INSTALLATION MANUAL FXMQ_PB FBQ Economizer MODELS ECONMQ12P 8 1K ECONMQ12P 13 1K ECONMQ30P 8 1K ECONMQ30P 13 1K ECONMQ48P 8 1K ECONMQ48P 13 1K ...

Страница 2: ...el Number Description Applicable Indoor Units Field Supplied Power ECONMQ12P 8 1K Fully modulating economizer 1 12 x 20 x 2 MERV 8 filter FXMQ07PBVJU FXMQ09PBVJU 24VAC ECONMQ12P 13 1K Fully modulating economizer 1 12 x 20 x 4 MERV 13 filter FXMQ07PBVJU FXMQ09PBVJU 24VAC ECONMQ30P 8 1K Fully modulating economizer 1 12 x 20 x 2 MERV 8 filter FXMQ15PBVJU FXMQ18PBVJU FXMQ24PBVJU FBQ18PVJU FBQ24PVJU FB...

Страница 3: ...ER 3 2 Dimensions Kit Model A B1 B2 C D E ECONMQ12P 8 1K 21 625 13 00 9 75 24 25 7 50 17 00 ECONMQ12P 13 1K ECONMQ30P 8 1K 36 4375 13 00 9 75 24 25 7 50 32 00 ECONMQ30P 13 1K ECONMQ48P 8 1K 52 1875 13 00 9 75 24 25 7 50 48 00 ECONMQ48P 13 1K ...

Страница 4: ...zer and indoor unit g Place the return air duct and fresh air duct over the economizer return and fresh air dampers Note Economizer section may be rotated 180 for bottom fresh air connection 5 Operation Mode A Cooling Mode 1 While in cooling thermo on with the ambient temperature and humidity above the enthalpy control set point the fresh air damper will open to the minimum vent position and the c...

Страница 5: ... the minimum vent position This setpoint can be adjusted as needed Figure 2 Single Enthalpy Curve and Boundaries Table 3 Single Enthalpy and Dual Enthalpy High Limit Curves E Settings 1 The mixed air temperature set point must be no lower than 65 FDB for continuous operation This may be configured down to 60 FDB however thermo off may be carried out due to freeze protection 2 The economizer is rec...

Страница 6: ...ay the value of the currently displayed item Press the button to increase change the displayed parameter value Press the button to decrease change the displayed parameter value Press the button to accept the displayed value and store it in non volatile RAM CHANGE STORED displays Press the button Enter to return to the current parameter Press the button MenuUp Exit to return to the previous menu No...

Отзывы: