INSTALLATION MANUAL                                                                                        FXMQ_PB/FBQ ECONOMIZER 

 

1.

 

Ducted Indoor Unit Economizer Summary 

 
The Daikin economizer option allows the FXMQ_PBVJU indoor units to utilize outside air to reduce the mechanical cooling when 
the  condition of the outside air  permits.    Automatic, sensor-controlled dampers provide a  constant, programmable leaving air 
temperature  from  the  economizer  whenever  the  indoor  unit  receives  a  call  for  cooling  and  the  outside  air  conditions  satisfy 
enthalpy  requirements.    This  allows  the  indoor  unit  expansion  valve,  and  in  turn  the  compressor,  to  operate  at  part  load 
conditions to maximize energy efficiency. 

 

 
 
 

Table 1. Economizer Model Numbers 

 

Model Number 

Description 

Applicable Indoor Units 

Field Supplied 

Power 

ECONMQ12P-8-1K 

Fully modulating economizer 

(1) 12

 x 20

 x 

2” MERV 8 filter

 

FXMQ07PBVJU 
FXMQ09PBVJU 

24VAC 

ECONMQ12P-13-1K 

Fully modulating economizer 

(1) 12

 x 20

 x 4

” MERV 

13 filter 

FXMQ07PBVJU 
FXMQ09PBVJU 

24VAC 

ECONMQ30P-8-1K 

Fully modulating economizer

 

(1) 12

 x 20

 x 

2” MERV 8 filter

 

FXMQ15PBVJU 
FXMQ18PBVJU   
FXMQ24PBVJU 

FBQ18PVJU 
FBQ24PVJU 
FBQ30PVJU 

24VAC 

ECONMQ30P-13-1K 

Fully modulating economizer

 

(1) 12

 x 20

 x 4

” MERV 

13 filter 

FXMQ15PBVJU 
FXMQ18PBVJU   
FXMQ24PBVJU 

FBQ18PVJU 
FBQ24PVJU 
FBQ30PVJU 

24VAC 

ECONMQ48P-8-1K 

Fully modulating economizer

 

(2) 12

 x 24

 x 2

” MERV 

8 filter 

FXMQ30PBVJU 
FXMQ36PBVJU   
FXMQ48PBVJU 
FXMQ54PBVJU 

FBQ36PVJU 
FBQ48PVJU 

24VAC 

ECONMQ48P-13-1K 

Fully modulating economizer

 

(2) 12

 x 24

 x 4

” MERV 

13 filter 

FXMQ30PBVJU 
FXMQ36PBVJU   
FXMQ48PBVJU 
FXMQ54PBVJU 

FBQ36PVJU 
FBQ48PVJU 

24VAC 

 

 

 

Содержание ECONMQ12P-8-1K

Страница 1: ...1 INSTALLATION MANUAL FXMQ_PB FBQ Economizer MODELS ECONMQ12P 8 1K ECONMQ12P 13 1K ECONMQ30P 8 1K ECONMQ30P 13 1K ECONMQ48P 8 1K ECONMQ48P 13 1K ...

Страница 2: ...el Number Description Applicable Indoor Units Field Supplied Power ECONMQ12P 8 1K Fully modulating economizer 1 12 x 20 x 2 MERV 8 filter FXMQ07PBVJU FXMQ09PBVJU 24VAC ECONMQ12P 13 1K Fully modulating economizer 1 12 x 20 x 4 MERV 13 filter FXMQ07PBVJU FXMQ09PBVJU 24VAC ECONMQ30P 8 1K Fully modulating economizer 1 12 x 20 x 2 MERV 8 filter FXMQ15PBVJU FXMQ18PBVJU FXMQ24PBVJU FBQ18PVJU FBQ24PVJU FB...

Страница 3: ...ER 3 2 Dimensions Kit Model A B1 B2 C D E ECONMQ12P 8 1K 21 625 13 00 9 75 24 25 7 50 17 00 ECONMQ12P 13 1K ECONMQ30P 8 1K 36 4375 13 00 9 75 24 25 7 50 32 00 ECONMQ30P 13 1K ECONMQ48P 8 1K 52 1875 13 00 9 75 24 25 7 50 48 00 ECONMQ48P 13 1K ...

Страница 4: ...zer and indoor unit g Place the return air duct and fresh air duct over the economizer return and fresh air dampers Note Economizer section may be rotated 180 for bottom fresh air connection 5 Operation Mode A Cooling Mode 1 While in cooling thermo on with the ambient temperature and humidity above the enthalpy control set point the fresh air damper will open to the minimum vent position and the c...

Страница 5: ... the minimum vent position This setpoint can be adjusted as needed Figure 2 Single Enthalpy Curve and Boundaries Table 3 Single Enthalpy and Dual Enthalpy High Limit Curves E Settings 1 The mixed air temperature set point must be no lower than 65 FDB for continuous operation This may be configured down to 60 FDB however thermo off may be carried out due to freeze protection 2 The economizer is rec...

Страница 6: ...ay the value of the currently displayed item Press the button to increase change the displayed parameter value Press the button to decrease change the displayed parameter value Press the button to accept the displayed value and store it in non volatile RAM CHANGE STORED displays Press the button Enter to return to the current parameter Press the button MenuUp Exit to return to the previous menu No...

Отзывы: