Installation manual
43
E(D/B)(H/L)Q011~0W1
Unit for air to water heat pump system
4PW57621-1A
T
ECHNICAL
SPECIFICATIONS
General
Electrical specifications
AA
Booster heater thermal protector
is open (applies only to
installations with a domestic hot
water tank)
Reset the thermal protector
Backup heater thermal protector
is open.
Reset the thermal protector by
pressing the reset button (refer
to
for location of the reset
button)
Check the reset button of the
thermal protector.
If both the thermal protector and
the controller are reset, but the
AA
error code persists, the
backup heater thermal fuse has
blown.
Contact your local dealer.
C0
Flow switch failure (flow switch
remains closed while pump is
stopped)
Check that the flow switch is not
clogged with dirt.
C4
Heat exchanger thermistor
failure (heat exchanger
temperature sensor broken)
Contact your local dealer.
E1
Compressor PCB defective
Contact your local dealer.
E3
Abnormal high pressure
Check that the unit is operating
within its operating range (refer
to
Contact your local dealer.
E4
Actuation of low pressure sensor
Check that the unit is operating
within its operating range (refer
to
Contact your local dealer.
E5
Overload activation of
compressor
Check that the unit is operating
within its operating range (refer
to
Contact your local dealer.
E7
Fan lock failure (fan is locked)
Check if the fan is not obstructed
by dirt. If the fan is not
obstructed, contact your local
dealer.
E9
Malfunction of electronic
expansion valve
Contact your local dealer.
EC
Domestic hot water temperature
too high (>89°C)
• Check that the contactor of the
electric booster heater is not
short circuited.
• Check that the domestic hot
water thermistor is giving the
correct read out.
F3
Too high discharge temperature
(e.g. due to outdoor coil
blockage)
Clean the outdoor coil. If the coil
is clean, contact your local
dealer.
H3
Malfunctioning HPS system
Contact your local dealer.
H9
Outdoor temperature thermistor
failure (outdoor thermistor is
broken)
Contact your local dealer.
HC
Domestic hot water tank
thermistor failure
Contact your local dealer.
J1
Malfunction of pressure sensor
Contact your local dealer.
J3
Discharge pipe thermistor failure
Contact your local dealer.
J5
Suction pipe unit thermistor
failure
Contact your local dealer.
J6
Aircoil thermistor frost detection
failure
Contact your local dealer.
J7
Aircoil thermistor mean
temperature failure
Contact your local dealer.
J8
Liquid pipe unit thermistor failure
Contact your local dealer.
L4
Electric component failure
Contact your local dealer.
L5
Electric component failure
Contact your local dealer.
L8
Electric component failure
Contact your local dealer.
L9
Electric component failure
Contact your local dealer.
LC
Electric component failure
Contact your local dealer.
P1
PCB failure
Contact your local dealer.
P4
Electric component failure
Contact your local dealer.
PJ
Failure of capacity setting
Contact your local dealer.
U0
Refrigerant failure (due to
refrigerant leak)
Contact your local dealer.
Error
code
Failure cause
Corrective action
U1
Power supply cables are
connected in the reverse phase
instead of the normal phase.
Connect the power supply
cables in normal phase. Change
any two of the three power
supply cables (L1, L2 , L3) to
correct phase.
U2
Main circuit voltage failure
Contact your local dealer.
U4
Communication failure
Contact your local dealer.
U5
Communication failure
Contact your local dealer.
U7
Communication failure
Contact your local dealer.
UA
Communication failure
Contact your local dealer.
EDLQ
EDHQ
EBLQ
EBHQ
Nominal capacity
• heating
Refer to the Technical Data
• cooling
Refer to the Technical Data
Dimensions H x W x D
1418 x 1435 x 382 mm
Weight
• machine weight
180 kg
• operation weight
185 kg
Connections
• water inlet/outlet
G 5/4" FBSP
(a)
(a) FBSP = Female British Standard Pipe
• water drain
hose nipple
Expansion vessel
• volume
10 l
• maximum working
pressure (MWP)
3 bar
Pump
• type
water cooled
• no. of speed
2
Internal water volume
5.5 l
Pressure relief valve
water circuit
3 bar
Operation range - water side
• heating
+15~+55°C
+15~+55°C
• cooling
—
+5~+22°C
Operation range - air side
• heating
–15~+35°C
(b)
(b) EDL and EBL models can reach –20°C / EDL_W1 and EBL_W1 models can
reach –25°C, but this is without capacity guarantee
–15~+35°C
• cooling
—
+10~+46°C
• domestic hot water by
heat pump
–15~+35°C
V3 models (1~)
W1 models (3N~)
Standard unit (power supply via unit)
• power supply
230 V 50 Hz 1P
400 V 50 Hz 3P
• nominal running current
—
5.8 A
Backup heater
• power supply
See
"Connection of the backup heater power
• maximum running current
See
"Connection of the backup heater power
Error
code
Failure cause
Corrective action