Installation manual
33
E(D/B)(H/L)Q011~0W1
Unit for air to water heat pump system
4PW57621-1A
■
[7-01]
Hysteresis value booster heater: temperature
difference determining the booster heater ON temperature
(T
BH ON
). T
BH ON
= T
BH OFF
– [7-01]
Dual set point control
Applies only to installations with different heat emitter which require
different set points.
Dual set point control makes it possible to generate 2 different set
points.
■
[7-02] Dual set point control status: defines whether the dual
set point control is enabled (1) or disabled (0).
■
[7-03] Second set point heating: specifies the second set
point temperature in heating operation.
■
[7-04] Second set point cooling: specifies the second set
point temperature in cooling operation.
[8] Domestic water heating mode timer
Applies only to installations with a domestic hot water tank.
The 'domestic water heating mode timer' field settings defines the
minimum and maximum domestic water heating times, minimum time
between two domestic water heating cycles by heat pump, and
booster heater delay time.
■
[8-00] Minimum running time: specifies the minimum time
period during which heat pump domestic water heating mode
should be activated, even when the target domestic hot water
temperature for heat pump (T
HP OFF
) has already been
reached.
■
[8-01] Maximum running time: specifies the maximum time
period during which heat pump domestic water heating mode
can be activated, even when the target domestic hot water
temperature for heat pump (T
HP OFF
) has not yet been
reached.
The actual maximum running time will automatically vary
between [8-01] and [8-01]+[8-04] depending on the outdoor
temperature. See figure in chapter
■
[8-02] Anti-recycling time: specifies the minimum required
interval between two heat pump domestic water heating
mode cycles.
The actual anti-recycling time will automatically vary between
[8-02] and 0 depending on the outdoor temperature. See
figure in chapter
.
The minimum value for booster heater ON
temperature (T
BH ON
) is 2°C (fixed) below heat pump
OFF temperature (T
HP OFF
).
NOTE
There is no indication available which set point is
active!
NOTE
■
The first set point heating/cooling is the set point
selected on the user interface.
-
In heating mode the first set point can be a
fixed value or weather dependent.
-
In cooling mode the first set point is always a
fixed value.
■
The second set point heating [7-03] should be
linked to the heat emitters which requires the
highest set point in heating mode. Example: fan
coil unit.
■
The second set point cooling [7-04] should be
linked to the heat emitters which requires the
lowest set point in cooling mode. Example: fain
coil unit.
■
The actual second set point heating value
depends on the selected value of setting [7-03].
-
In case [7-03]=1~24°C, the actual second set
point will be first set point heating increased
with [7-03] (the maximum is 55°C).
In this way the second set point heating is
linked to the first set point heating.
-
In case [7-03]=25~55°C, the actual second set
point heating is equal to [7-03].
■
The selection of second set point or first set point
is determined by the terminals (X2M: 1, 2, 4).
The second set point has always priority on the
first set point.
When dual set point control is enabled, heating/cooling
selection always has to be done on the user interface.
NOTE
It is the responsibility of the installer to make sure no
unwanted situations can occur.
It is very important that the water temperature to the
floor heating loops never becomes too high in heating
mode or never too cold in cooling mode. Failure to
observe this rule can result in construction damage or
discomfort. For example in cooling mode condensation
on the floor can occur when water towards the floor
heating loops is too cold (dew point).
X2M
1
2
3
4
SP1
SP2
SP1
First set point contact
SP2
Second set point
contact
Note that when the unit is configured to work with a
room thermostat (refer to
installation configuration" on page
maximum running timer will only be taken into
account when there is a request for space cooling
or space heating. When there is no request for
room cooling or room heating, domestic water
heating by the heat pump will continue until the
'heat pump OFF temperature' (see field settings
on
) is reached. When no room thermostat
is installed, the timer is always taken into account.
1
Domestic water heating (1 = active, 0 = not active)
2
Hot water request (1 = request, 0 = no request)
t
Time
If the outdoor temperature is higher than the field setting to
which parameter [4-02] is set, then field settings of
parameters [8-01], [8-02], and [8-04] are not considered.
t
1
0
1
0
[8-01]
[8-02]
[8-00]