Installation manual
23
E(D/B)(H/L)Q011~0W1
Unit for air to water heat pump system
4PW57621-1A
Wiring the 3-way valve
1
Using the appropriate cable, connect the valve control cable to
the appropriate terminals as shown on the wiring diagram.
2
Fix the cable(s) with cable ties to the cable tie mountings to
ensure strain relief.
Connection to a benefit kWh rate power supply
Electricity companies throughout the world work hard to provide
reliable electric service at competitive prices and are often authorized
to bill clients at benefit rates. E.g. time-of-use rates, seasonal rates,
Wärmepumpentarif in Germany and Austria, ... .
This equipment allows for connection to such benefit rate power
supply delivery systems.
Consult with the electricity company acting as provider at the site
where this equipment is to be installed to know whether it is
appropriate to connect the equipment in one of the benefit kWh rate
power supply delivery systems available, if any.
When the equipment is connected to such benefit kWh rate power
supply, the electricity company is allowed to:
■
interrupt power supply to the equipment for certain periods of
time;
■
demand that the equipment only consumes a limited amount of
electricity during certain periods of time.
The unit is designed to receive an input signal by which the unit
switches into forced off mode. At that moment, the outdoor unit
compressor will not operate.
Two types of 3-way valves can be connected. Wiring
is different for each type:
■
"Spring return 2-wire" type 3-way valve
The 3-way valve should be fitted as such that
when the 3-way valve is idle (not activated), the
space heating circuit is selected.
■
"SPST 3-wire" type 3-way valve
The 3-way valve should be fitted as such that
when terminal ports 9 and 10 are electrified, the
domestic hot water circuit is selected.
"Spring return 2-wire" valve
"SPST 3-wire" valve
9
X2M
8
10
M
9
X2M 8
10
M
CAUTION
for a benefit kWh rate power supply like illustrated
below as type 1 (allowed for all models)
■
If the benefit kWh rate power supply is of the type that
power supply is not interrupted, then control of the
heaters is still possible.
For the different possibilities of controlling heaters at
moments that benefit kWh rate is active, refer to
"[D] Benefit kWh rate power supply/Local shift value
weather dependent" on page 35
If heaters must be controlled at moments that the
benefit kWh rate power supply is off, then these
heaters shall be connected to a separate power
supply.
■
During the period that the benefit kWh rate is active
and power supply is continuous, then stand-by power
consumption is possible (PCB, controller, pump, ...).
for a benefit kWh rate power supply like illustrated
below as types 2 or 3 (only allowed for EDL and EBL
models)
If during benefit kWh rate power supply the power supply is
shut off, then heaters can not be controlled.
■
This power supply interruption should not be longer
than 2 hours, otherwise the real time clock of the
controller will be reset.
■
During power supply interruption, the controller
display will be blank.
If during benefit kWh rate power supply the power supply is
shut off, the freeze protection function (refer to
Freeze protection function" on page 31
) can not operate.
For this reason it is important that the power supply of the
expansion vessel heater, plate heat exchanger heater and
switch box heater are changed to guarantee freeze
protection.
Procedure
1
Using the appropriate cable, connect the power
supply to the circuit heater as shown in the wiring
diagram and in the figure below.
2
Connect the earth conductor (yellow/green) to the
earthing screw.
3
Fix the cable with cable ties to the cable tie mountings
to ensure strain relief.
4
Reconnect the wires according to the figure below.
4
3
2
1
2
1
N
L
X11M
1
2
1 2 3 4
1
Earth leakage
circuit breaker
2
Fuse
4
3
2
1
4
3
2
1
2
1
N
L
X11M
4
3
2
1
2
1
N
L
X11M
BLK
WHT
BLK
WHT
4
3
2
1
Содержание EBHQ011BA6V3
Страница 47: ...NOTES NOTES ...
Страница 48: ...4PW57621 1A Copyright Daikin ...