E(D/B)(H/L)Q011~0W1

Unit for air to water heat pump system

4PW57622-1

Operation manual

6

Controller operations

Manual operation

In manual operation, the user manually controls the settings of the
installation. The last setting remains active until the user changes it or
until the schedule timer forces another setting (refer to 

"Schedule

timer operation" on page 7

).

As the controller can be used for a wide variety of installations, it is
possible to select a function which is not available on your
installation. In that case the message 

n

 will appear.

Switching on and setting space cooling (

c

) and heating (

h

)

1

Use the 

=

 button to select space cooling (

c

) or space heating (

h

).

Icon 

c

 or 

h

 appears on the display as well as the corresponding

water temperature set point.

2

Use the 

bi

  and 

bj

  buttons to set the desired water

temperature.

Temperature range for heating: 25°C to 55°C
The temperature for heating can be set as low as 15°C (see

"Field settings" on page 11

). However, the temperature for

heating should only be set lower than 25°C during
commissioning of the installation. When set lower than 25°C,
only the backup heater will operate.
In order to avoid overheating, space heating is not operable
when the outdoor ambient temperature rises above a certain
temperature (as set through field setting [4-02], refer to 

"Field

settings" on page 11

).

Temperature range for cooling: 5°C to 22°C

3

Switch on the unit by pushing the 

y

 button.

The operation LED 

0

 lights up.

Selection and setting of domestic water heating (

w

)

1

Use the 

v

 button to activate domestic water heating (

w

).

Icon 

w

 appears on the display.

2

Use the 

wi

  or 

wj

  button to display the actual

temperature set point and subsequently, to set the correct
temperature.

The actual temperature set point only appears on the display
after pressing one of the buttons 

wi

 or 

wj

. If no button is

pressed for 5 seconds, the temperature set point will
automatically disappear from the display again.
Temperature range for domestic water heating: 30°C to 78°C

3

Press the 

v

 button to deactivate domestic water heating (

w

).

Icon 

w

 disappears from the display.

Selecting powerful domestic water heating operation

1

Press 

v

  for 5 seconds to activate powerful domestic water

heating operation.

Icons 

w

 and 

m

 start flashing.

Powerful domestic water heating is deactivated automatically
when the set point for the domestic hot water is reached.

Selecting quiet mode operation (

s

)

1

Use the 

s

 button to activate quiet mode operation (

s

).

Icon 

s

 appears on the display.

If the controller is set in permission level 2 or 3 (refer to 

"Field

settings" on page 11

), the 

s

 button will not be operable.

Selecting weather dependent set point operation (only in
heating mode)

1

Press the 

ba

  button to select weather dependent set point

operation.

Icon 

a

  appears on the display as well as the shift value. The

shift value is not shown in case it is 0.

2

Use the 

bi

 and 

bj

 buttons to set the shift value.

Range for the shift value: –5°C to +5°C

Displaying actual temperatures

1

Push the 

ba

 button for 5 seconds.

The 

b

 icon and the outgoing water temperature are displayed.

The icons 

l

 and 

=

 are flashing.

2

Use the 

pi

 and 

pj

 buttons to display:

The outdoor temperature (

u

 icon is flashing).

The domestic hot water tank temperature (

w

  icon is

flashing).

The outgoing water temperature (

=

 are flashing).

If no button is pressed for 5 seconds, the controller leaves the
display mode.

CAUTION

The actual operation range depends on the values set on
field setting [9].

These values shall be determined based on the
application.

NOTE

In heating mode (

h

), the water temperature set point

can also be weather dependent (icon 

a

 is shown).

This means that the controller calculates the water
temperature set point based on the outdoor temperature.

In this case, instead of showing the water temperature
set point, the controller shows the "shift value" which
can be set by the user. This shift value is the
temperature difference between the temperature set
point calculated by the controller and the real set point.
E.g. a positive shift value means that the real
temperature set point will be higher than the calculated
set point.

NOTE

When the unit is connected to an external room
thermostat, buttons 

=

 and 

y

 are not operable and

the icon 

e

  is shown. In this case, the external room

thermostat switches the unit on or off and determines
the operation mode (space cooling or space heating).

Remark that pushing the 

y

  button has no influence on

the domestic water heating. Domestic water heating is only
switched on or off by means of the 

v

 button.

Содержание EBHQ011BA6V3

Страница 1: ...DHQ016BA6W1 EDLQ011BA6V3 EDLQ014BA6V3 EDLQ016BA6V3 EDLQ011BA6W1 EDLQ014BA6W1 EDLQ016BA6W1 EBHQ011BA6V3 EBHQ014BA6V3 EBHQ016BA6V3 EBHQ011BA6W1 EBHQ014BA6W1 EBHQ016BA6W1 EBLQ011BA6V3 EBLQ014BA6V3 EBLQ016BA6V3 EBLQ011BA6W1 EBLQ014BA6W1 EBLQ016BA6W1 Unit for air to water heat pump system ...

Страница 2: ...ly units The monoblock unit range consists of two main versions a heating cooling EB version and a heating only ED version Both versions are delivered with an integrated backup heater for additional heating capacity during cold outdoor temperatures The backup heater also serves as a backup in case of malfunctioning of the unit and for freeze protection of the outside water piping during winter tim...

Страница 3: ...room thermostat connected to the unit This will prevent excessive space heating and will stop the unit and the circulation pump when the room temperature is above the thermostat set point Next recommendations only apply to installations with an optional domestic hot water tank Make sure the domestic hot water is only heated up to the domestic hot water temperature you require Start with a low dome...

Страница 4: ...ive 3 OPERATION MODE ICONS hcws These icons indicate the current operation mode s space heating h space cooling c domestic water heating w or quiet mode s Within limits different modes can be combined e g space heating and domestic water heating The corresponding mode icons will be displayed simultaneously In a heating only installation the c icon will never be displayed If the domestic hot water ...

Страница 5: ...ce purposes only Refer to the installation manual 25 SPACE HEATING COOLING BUTTON This button allows manual switching between cooling or heating mode provided the unit is not a heating only unit When the unit is connected with an external room thermostat this button is not operable and the icon e is shown 26 DOMESTIC WATER HEATING BUTTON v This button enables or disables heating of the domestic wa...

Страница 6: ...r tank by heat pump when the space heating space cooling operation has reached its temperature set point or heat pump domestic water heating has a higher demand request than space side depends on DIP switch setting When necessary and when allowed by the booster heater schedule timer refer to Programming quiet mode booster heating or domestic water heating on page 9 the booster heater provides auxi...

Страница 7: ... v for 5 seconds to activate powerful domestic water heating operation Icons w and m start flashing Powerful domestic water heating is deactivated automatically when the set point for the domestic hot water is reached Selecting quiet mode operation s 1 Use the s button to activate quiet mode operation s Icon s appears on the display If the controller is set in permission level 2 or 3 refer to Fiel...

Страница 8: ...mmed at 13 00 16 00 and 19 00 The last programmed command 16 00 overruled the previous programmed command 13 00 and will remain active until the next programmed command 19 00 occurs So in order to know the actual setting one should consult the last programmed command It is clear that the last programmed command may date from the day before Refer to Consulting programmed actions on page 10 Only use...

Страница 9: ...oint Conversely when programming cooling actions time and setpoint heating actions are added automatically at the same time but with the default heating set point The set points of these automatically added actions can be adjusted by programming the corresponding mode This means that after programming heating you should also program the corresponding cooling set points and vice versa Programming P...

Страница 10: ...store the programmed actions If the button is pressed when action number 3 is displayed actions 1 2 and 3 are stored but 4 and 5 are deleted You automatically return to step 6 By pressing the pr button several times you return to previous steps in this procedure and finally return to normal operation Programming quiet mode booster heating or domestic water heating Programming domestic water heatin...

Страница 11: ...is possible to copy all programmed actions of a specific day to the next day e g copy all programmed actions from 1 to 2 To copy programmed actions to the next day proceed as follows 1 Press the button The actual mode is blinking 2 Use the pi and pj buttons to select the mode you want to program The selected mode is blinking You can leave programming by pressing the pr button 3 Press the button to...

Страница 12: ...p 2 through 4 to change other field settings as required 7 When finished press the z button to exit FIELD SET MODE Detailed description 0 User permission level If required certain user interface buttons can be made unavailable for the user Three permission levels are defined see the table below Switching between level 1 and level 2 3 is done by simultaneously pressing buttons pfi and pfj immediate...

Страница 13: ... whether the disinfection function is turned on 1 or off 0 2 02 Start time time of the day at which the domestic water should be heated 2 03 Set point high water temperature to be reached 2 04 Interval time period defining how long the set point temperature should be maintained 3 Auto restart When power returns after a power supply failure the auto restart function reapplies the user interface set...

Страница 14: ...his setting Leave it set to its default value C Setup on EKRP1HB digital I O PCB Solar priority mode C 00 Solar priority mode setting for information concerning the EKSOLHW solar kit refer to the installation manual of that kit D Local shift value weather dependent Local shift value weather dependent The local shift value weather dependent field setting is only relevant in case weather dependent s...

Страница 15: ...ace heating off temperature 35 14 35 1 C 03 Installation related setting 04 Installation related setting 5 Installation related settings 00 Installation related setting 01 Installation related setting 02 Installation related setting 03 Installation related setting 04 Installation related setting 6 Installation related settings 00 Installation related setting 01 Installation related setting 02 Inst...

Страница 16: ...lated setting 04 Installation related setting D Local shift value weather dependent 00 Installation related setting 01 Installation related setting 02 Installation related setting 03 Local shift value weather dependent 0 0 1 2 3 4 E Unit information readout 00 Software version Read only 01 EEPROM version Read only 02 Unit model identification Read only 03 Liquid refrigerant temperature Read only C...

Страница 17: ...fied installer in accordance with relevant local and national legislation Units must be treated at a specialized treatment facility for re use recycling and recovery By ensuring this product is disposed off correctly you will help to prevent potential negative consequences for the environment and human health Please contact the installer or local authority for more information DANGER Do not touch ...

Страница 18: ...NOTES NOTES ...

Страница 19: ......

Страница 20: ...Copyright Daikin 4PW57622 1 ...

Отзывы: