background image

 

Operation manual

 

3

 

E(D/B)(H/L)Q011~0W1

 

Unit for air to water heat pump system

 

4PW57622-1

 

O

 

PERATING

 

 

 

THE

 

 

 

DIGITAL

 

 

 

CONTROLLER

 

Operating the unit comes down to operating the digital controller.

 

Features and functions

 

The digital controller is a state of the art controller that offers full
control over your installation. It can control a cooling/heating and a
heating only installation.

Both installations are available in multiple versions which vary in
capacity, electrical supply and installed equipment (with an optional
domestic hot water tank with a booster heater).

 

Basic controller functions

 

The basic controller functions are:

 

 

Turning the unit ON/OFF.

 

 

Operation mode change-over:
-

space heating (refer to 

page 5

),

-

space cooling (refer to 

page 5

) (*),

-

domestic water heating (refer to 

page 5

) (*).

 

 

Selection of features:
-

quiet mode (refer to 

page 5

),

-

weather dependent control (refer to 

page 6

).

 

 

Temperature set point adjustment (refer to 

page 6

).

The digital controller supports a power cut off of maximum 2 hours.
When autorestart is enabled (see 

"Field settings" on page 11

) this

allows a power supply shut down of 2 hours without user intervention
(e.g. benefit kWh rate power supply).

 

Clock function

 

The clock functions are:

 

 

24 hour real time clock.

 

 

Day of the week indicator.

 

Schedule timer function

 

The schedule timer function allows the user to schedule the
operation of the installation according to a daily or a weekly program.

 

Name and function of buttons and icons

 

1.

 

COOLING/HEATING ON/OFF BUTTON 

 

y

 

The ON/OFF button starts or stops the heating or cooling
function of the unit.

When the unit is connected with an external room thermostat,
this button is not operable and the icon 

 

e

 

 is shown.

Pressing the ON/OFF button consecutively too many times may
cause malfunction of the system (maximum 20 times per hour).

 

2.

 

OPERATION LED 

 

0

 

The operation LED is lit during space cooling or space heating
operation. The LED blinks if a malfunction occurs. When the
LED is OFF, space cooling or space heating are inactive while
the other operation modes can still be active.

 

3.

 

OPERATION MODE ICONS 

 

hcws

 

These icons indicate the current operation mode(s): space
heating (

 

h

 

), space cooling (

 

c

 

), domestic water heating (

 

w

 

) or

quiet mode (

 

s

 

). Within limits, different modes can be combined,

e.g. space heating and domestic water heating. The
corresponding mode icons will be displayed simultaneously.

In a heating only installation, the 

 

c

 

 icon will never be displayed.

If the domestic hot water tank is not installed, the 

 

w

 

  icon will

never be displayed.

If the solar option is installed and active, the 

 

w

 

  icon will be

blinking.

 

4.

 

EXTERNAL CONTROL ICON 

 

e

 

This icon indicates that an external room thermostat with higher
priority is controlling your installation. This external room
thermostat can start and stop the space heating/cooling
operation and change the operation mode (cooling/heating).

When an external room thermostat with a higher priority is
connected, the schedule timer for space cooling and space
heating will not function.

When the benefit kWh power rate signal is sent, the centralised
control indication 

 

e

 

 will flash to indicate that benefit kWh power

rate is active.

 

5.

 

DAY OF THE WEEK INDICATOR 

 

1234567

 

This indicator shows the current weekday.

When reading or programming the schedule timer, the indicator
shows the set day.

 

Never let the digital controller get wet. This may cause an
electric shock or fire.

Never press the buttons of the digital controller with a hard,
pointed object. This may damage the digital controller.

Never inspect or service the digital controller yourself, ask
a qualified service person to do this.

 

NOTE

 

 

Descriptions in this manual that apply to a specific
installation or that depend on the installed
equipment, are marked with an asterisk (*).

 

 

Some functions described in this manual may not
be available or should not be available. Ask your
installer or your local dealer for more information
on permission levels.

 

NOTE

 

(*) The functions 'space cooling' and 'domestic water
heating' can only be selected when the corresponding
equipment is installed.

 

NOTE

 

Remark that pushing the 

 

y

 

 button has no influence

on the domestic water heating. Domestic water
heating is only switched on or off by means of the 

 

v

 

button.

1

17

3

5

6

24

8

13

25

26

11

19

21

14

4

7

9

12
10

22

34

27

28

23

20

33

32

31

29

30

2

16

18

15

Содержание EBHQ011BA6V3

Страница 1: ...DHQ016BA6W1 EDLQ011BA6V3 EDLQ014BA6V3 EDLQ016BA6V3 EDLQ011BA6W1 EDLQ014BA6W1 EDLQ016BA6W1 EBHQ011BA6V3 EBHQ014BA6V3 EBHQ016BA6V3 EBHQ011BA6W1 EBHQ014BA6W1 EBHQ016BA6W1 EBLQ011BA6V3 EBLQ014BA6V3 EBLQ016BA6V3 EBLQ011BA6W1 EBLQ014BA6W1 EBLQ016BA6W1 Unit for air to water heat pump system ...

Страница 2: ...ly units The monoblock unit range consists of two main versions a heating cooling EB version and a heating only ED version Both versions are delivered with an integrated backup heater for additional heating capacity during cold outdoor temperatures The backup heater also serves as a backup in case of malfunctioning of the unit and for freeze protection of the outside water piping during winter tim...

Страница 3: ...room thermostat connected to the unit This will prevent excessive space heating and will stop the unit and the circulation pump when the room temperature is above the thermostat set point Next recommendations only apply to installations with an optional domestic hot water tank Make sure the domestic hot water is only heated up to the domestic hot water temperature you require Start with a low dome...

Страница 4: ...ive 3 OPERATION MODE ICONS hcws These icons indicate the current operation mode s space heating h space cooling c domestic water heating w or quiet mode s Within limits different modes can be combined e g space heating and domestic water heating The corresponding mode icons will be displayed simultaneously In a heating only installation the c icon will never be displayed If the domestic hot water ...

Страница 5: ...ce purposes only Refer to the installation manual 25 SPACE HEATING COOLING BUTTON This button allows manual switching between cooling or heating mode provided the unit is not a heating only unit When the unit is connected with an external room thermostat this button is not operable and the icon e is shown 26 DOMESTIC WATER HEATING BUTTON v This button enables or disables heating of the domestic wa...

Страница 6: ...r tank by heat pump when the space heating space cooling operation has reached its temperature set point or heat pump domestic water heating has a higher demand request than space side depends on DIP switch setting When necessary and when allowed by the booster heater schedule timer refer to Programming quiet mode booster heating or domestic water heating on page 9 the booster heater provides auxi...

Страница 7: ... v for 5 seconds to activate powerful domestic water heating operation Icons w and m start flashing Powerful domestic water heating is deactivated automatically when the set point for the domestic hot water is reached Selecting quiet mode operation s 1 Use the s button to activate quiet mode operation s Icon s appears on the display If the controller is set in permission level 2 or 3 refer to Fiel...

Страница 8: ...mmed at 13 00 16 00 and 19 00 The last programmed command 16 00 overruled the previous programmed command 13 00 and will remain active until the next programmed command 19 00 occurs So in order to know the actual setting one should consult the last programmed command It is clear that the last programmed command may date from the day before Refer to Consulting programmed actions on page 10 Only use...

Страница 9: ...oint Conversely when programming cooling actions time and setpoint heating actions are added automatically at the same time but with the default heating set point The set points of these automatically added actions can be adjusted by programming the corresponding mode This means that after programming heating you should also program the corresponding cooling set points and vice versa Programming P...

Страница 10: ...store the programmed actions If the button is pressed when action number 3 is displayed actions 1 2 and 3 are stored but 4 and 5 are deleted You automatically return to step 6 By pressing the pr button several times you return to previous steps in this procedure and finally return to normal operation Programming quiet mode booster heating or domestic water heating Programming domestic water heatin...

Страница 11: ...is possible to copy all programmed actions of a specific day to the next day e g copy all programmed actions from 1 to 2 To copy programmed actions to the next day proceed as follows 1 Press the button The actual mode is blinking 2 Use the pi and pj buttons to select the mode you want to program The selected mode is blinking You can leave programming by pressing the pr button 3 Press the button to...

Страница 12: ...p 2 through 4 to change other field settings as required 7 When finished press the z button to exit FIELD SET MODE Detailed description 0 User permission level If required certain user interface buttons can be made unavailable for the user Three permission levels are defined see the table below Switching between level 1 and level 2 3 is done by simultaneously pressing buttons pfi and pfj immediate...

Страница 13: ... whether the disinfection function is turned on 1 or off 0 2 02 Start time time of the day at which the domestic water should be heated 2 03 Set point high water temperature to be reached 2 04 Interval time period defining how long the set point temperature should be maintained 3 Auto restart When power returns after a power supply failure the auto restart function reapplies the user interface set...

Страница 14: ...his setting Leave it set to its default value C Setup on EKRP1HB digital I O PCB Solar priority mode C 00 Solar priority mode setting for information concerning the EKSOLHW solar kit refer to the installation manual of that kit D Local shift value weather dependent Local shift value weather dependent The local shift value weather dependent field setting is only relevant in case weather dependent s...

Страница 15: ...ace heating off temperature 35 14 35 1 C 03 Installation related setting 04 Installation related setting 5 Installation related settings 00 Installation related setting 01 Installation related setting 02 Installation related setting 03 Installation related setting 04 Installation related setting 6 Installation related settings 00 Installation related setting 01 Installation related setting 02 Inst...

Страница 16: ...lated setting 04 Installation related setting D Local shift value weather dependent 00 Installation related setting 01 Installation related setting 02 Installation related setting 03 Local shift value weather dependent 0 0 1 2 3 4 E Unit information readout 00 Software version Read only 01 EEPROM version Read only 02 Unit model identification Read only 03 Liquid refrigerant temperature Read only C...

Страница 17: ...fied installer in accordance with relevant local and national legislation Units must be treated at a specialized treatment facility for re use recycling and recovery By ensuring this product is disposed off correctly you will help to prevent potential negative consequences for the environment and human health Please contact the installer or local authority for more information DANGER Do not touch ...

Страница 18: ...NOTES NOTES ...

Страница 19: ......

Страница 20: ...Copyright Daikin 4PW57622 1 ...

Отзывы: