Installation manual
34
0 EKCBX/H008BAV3
Unit for air to water heat pump system
4PW64602-1A – 09.2010
[6] DT for heat pump domestic water heating mode
Applies only to installations with a domestic hot water tank.
The 'DT (temperature difference) for heat pump domestic water
heating mode' field settings determine the temperatures at which
heating of the domestic hot water by the heat pump will be started
(i.e., the heat pump ON temperature) and stopped (i.e., the heat
pump OFF temperature).
When the domestic hot water temperature drops below the heat pump
ON temperature (T
HP ON
), heating of the domestic hot water by the
heat pump will be started. As soon as the domestic hot water
temperature reaches the heat pump OFF temperature (T
HP OFF
) or the
user set point temperature (T
U
), heating of the domestic hot water by
the heat pump will be stopped (by switching the 3-way valve).
The heat pump OFF temperature, and the heat pump ON
temperature, and its relation with field settings [6-00] and [6-01] are
explained in the illustration below.
■
[6-00] Start: temperature difference determining the heat
pump ON temperature (T
HP ON
). See illustration.
■
[6-01] Stop: temperature difference determining the heat
pump OFF temperature (T
HP OFF
). See illustration.
[7] DT for booster heater and dual set point control
DT for booster heater
Applies only to installations with a domestic hot water tank.
When the domestic hot water is heated and the domestic hot water
set point temperature (as set by the user) has been reached, the
booster heater will continue to heat the domestic hot water to a
temperature a few degrees above the set point temperature, i.e. the
booster heater OFF temperature. These extra degrees are specified
by the domestic hot water step length field setting. Correct setting
prevents the booster heater from repeatedly turning on and off (i.e.
chattering) to maintain the domestic hot water set point temperature.
Note: the booster heater will turn back on when the domestic hot
water temperature drops [7-01] (field setting) below the booster
heater OFF temperature.
■
[7-00]
Domestic hot water step length: temperature
difference above the domestic hot water set point
temperature before the booster heater is turned off.
WARNING
Be aware that the domestic hot water temperature will be
automatically increased with the value selected in field
setting [5-04] (if the outdoor temperature drops below field
setting [5-03]) compare to the user set point for domestic
hot water (T
U
). Refer to field setting [5-03], [7-00] and the
operation manual to select preferable set point.
If this high domestic hot water temperature can be a
potential risk for human injuries, a mixing valve (field
supply) shall be installed at the hot water outlet connection
of the domestic hot water tank. This mixing valve shall
secure that the hot water temperature at the hot water tap
never rise above a set maximum value. This maximum
allowable hot water temperature shall be selected
according to local and national regulations.
T
U
User set point temperature (as set on the user interface)
T
HP MAX
Maximum heat pump temperature at sensor in domestic hot
water tank (50°C)(depending on T
A
)
(a)
(a) 45°C = T
HP MAX
at T
A
>25°C.
50°C = T
HP MAX
at 5°C
≤
T
A
≤
25°C.
48°C = T
HP MAX
at T
A
<5°C.
T
HP OFF
Heat pump OFF temperature
T
HP ON
Heat pump ON temperature
NOTICE
The maximum domestic hot water temperature that can be
reached with the heat pump is 50°C. It is advised to select
T
HP OFF
not higher than 48°C in order to improve
performance of the heat pump during domestic water
heating mode.
When setting [4-03]=0 or 2 special attention to setting
[6-00] is recommended. A good balance between the
required domestic hot water temperature and heat pump
ON temperature (T
HP ON
) is a must.
T
U
> T
HP MAX
T(
°
C)
70
T
U
50
T
HP MAX
48
T
HP OFF
41
T
HP ON
[6-01]
[6-00]
T
U
< T
HP MAX
T(
°
C)
45
T
U
= T
HP OFF
50
T
HP MAX
38
T
HP ON
[6-00]
T
U
= 45
°
C
[6-01] = 2
°
C
[6-00] = 7
°
C
T
U
= 70
°
C
[6-01] = 2
°
C
[6-00] = 7
°
C
NOTICE
If the schedule timer for booster heater (see the operation
manual) is active, the booster heater will only operate if
allowed by this schedule timer.
BH
Booster heater
HP
Heat pump. If heating up time by the heat pump takes too
long, auxiliary heating by the booster heater can take place
T
BH OFF
Booster heater OFF temperature (T
U
+ [7-00])
T
BH ON
Booster heater ON temperature (T
BH OFF
– [7-01])
T
HP MAX
Maximum heat pump temperature at sensor in domestic hot
water tank
T
HP OFF
Heat pump OFF temperature (T
HP MAX
– [6-01])
T
HP ON
Heat pump ON temperature (T
HP OFF
– [6-00])
T
DHW
Domestic hot water temperature
T
U
User set point temperature (as set on the user interface)
t
Time
WARNING
Be aware that the domestic hot water temperature will be
automatically increased (always) with the value selected in
field setting [7-00] compare to the user set point for
domestic hot water (T
U
). Refer to field setting [7-00] and
the operation manual to select preferable set point.
If this high water temperature can be a potential risk for
human injuries, a mixing valve (field supply) shall be
installed at the hot water outlet connection of the domestic
hot water tank. This mixing valve shall secure that the hot
water temperature at the hot water tap never rise above a
set maximum value. This maximum allowable hot water
temperature shall be selected according to local and
national regulations.
t
T
BH ON
T
DHW
T
HP ON
T
HP OFF
T
HP MAX
T
U
T
BH OFF
[6-01]
[6-00]
[7-00]
[7-01]
T
U
= 70
°
C
[7-00] =
3
°
C
[6-01] =
2
°
C
[6-00] =
7
°
C
HP
BH
HP
5
10
20
30
40
41
48
50
60
71
70
73
4PW64602-1A.book Page 34 Thursday, September 23, 2010 10:40 AM
Содержание EBHQ006BAV3
Страница 50: ...NOTES ...
Страница 51: ...NOTES ...
Страница 52: ...4PW64602 1A 09 2010 Copyright 2010 Daikin ...