Charge Verification

CAUTION

NOTICE

Violation of EPA regulations may result in fines or other penalties.

Operating the compressor with the suction valve closed will void

the warranty and cause serious compressor damage.

CAUTION

Final Charge Adjustment

The outdoor temperature must be 60°F or higher. Set the room
thermostat to COOL, fan switch to AUTO, and set the temperature
control well below room temperature.

Purge gauge lines.  Connect  service gauge manifold to base-valve
service ports.  Run the system (on low stage for two-stage units)
for 10 minutes to allow pressures to stabilize, then check
subcooling and/or superheat as detailed in the following sec-
tions.

Superheat = Suct. Line Temp. - Sat. Suct. Temp.

Subcooling = Sat. Liquid Temp. - Liquid Line Temp.

To prevent personal injury, carefully connect and disconnect
manifold gauge hoses. Escaping liquid refrigerant can cause burns.
Do not vent refrigerant into the atmosphere. Recover all
refrigerant during system repair and before final unit disposal.

CAUTION

55

57

59

61

63

65

67

69

71

60

10

13

17

20

23

26

29

30

31

65

8

11

14

16

19

22

26

27

29

70

5

8

10

13

15

19

23

24

25

75

----

----

6

9

11

15

20

21

23

80

----

----

----

----

7

12

17

18

20

85

----

----

----

----

----

8

13

15

16

90

----

----

----

----

----

5

10

11

13

95

----

----

----

----

----

----

5

8

10

100

----

----

----

----

----

----

----

5

8

105

----

----

----

----

----

----

----

----

5

110

----

----

----

----

----

----

----

----

----

115

----

----

----

----

----

----

----

----

----

SYSTEM SUPERHEAT

Indoor Wet Bulb Temperature, °F

Outdoor Dry Bulb 

Temperature, °F

SUPERHEAT FORMULA = SUCT. LINE TEMP. - SAT. SUCT. TEMP.

Содержание DZ13SC

Страница 1: ...e is delivered at the specified airflow See outdoor unit specification sheet for split system models or product specifica tion sheet for packaged and light commercial models Specifica tion sheets can be found at www daikincomfort com for Daikin brand products Within the website please select the residential or commercial products menu and then select the submenu for the type of product to be insta...

Страница 2: ...on in areas of heavy snow accumulation and or areas with prolonged continuous subfreezing temperatures Heat pump unit bases have cutouts under the outdoor coil that permit drainage of frost accumulation Situatetheunittopermitfreeunobstructeddrainage of the defrost water and ice In more severe weather locations it is recommended that the unit be elevated to allow unobstructed drainage and air flow ...

Страница 3: ... or TP 107 Long Line Set Application R 410A or contact your dis tributor for assistance Cond Unit Tons Suct Liq Suct Liq Suct Liq 1 1 2 5 8 1 4 3 4 3 8 3 4 3 8 2 5 8 1 4 3 4 3 8 3 4 3 8 2 1 2 5 8 1 4 3 4 3 8 7 8 3 8 3 3 4 3 8 7 8 3 8 1 1 8 3 8 3 1 2 7 8 3 8 1 1 8 3 8 1 1 8 3 8 4 7 8 3 8 1 1 8 3 8 1 1 8 3 8 5 7 8 3 8 1 1 8 3 8 1 1 8 3 8 Line Diameter In OD RECOMMENDED INTERCONNECTING TUBING Ft 0 24...

Страница 4: ...ially important on suction line filter driers which are continually wet when the unit is operating NOTE Be careful not to kink or dent refrigerant lines Kinked or dented lines will cause poor performance or compressor damage Do NOT make final refrigerant line connection until plugs are removed from refrigerant tubing NOTE Before brazing verify indoor piston size by checking the piston kit chart pa...

Страница 5: ...allation instructions supplied with the indoor furnace air handler for spe cific wiring connections and indoor unit configuration Likewise consult the instructions packaged with the thermostat for mount ing and location information Overcurrent Protection The following overcurrent protection devices are approved for use Time delay fuses HACR type circuit breakers These devices have sufficient time ...

Страница 6: ...il it may be necessary to add or remove refrigerant to attain proper charge If line set exceeds 15 feet in length refrigerant should be added at 6 ounces per foot of liquid line NOTE Charge should always be checked using superheat when using a piston and subcooling when using TXV equipped indoor coil to verify proper charge Open the suction service valve first If the liquid service valve is opened...

Страница 7: ...res to stabilize then check subcooling and or superheat as detailed in the following sec tions Superheat Suct Line Temp Sat Suct Temp Subcooling Sat Liquid Temp Liquid Line Temp To prevent personal injury carefully connect and disconnect manifold gauge hoses Escaping liquid refrigerant can cause burns Do not vent refrigerant into the atmosphere Recover all refrigerant during system repair and befo...

Страница 8: ... n a 123 445 n a 125 475 n a 130 500 n a 134 525 n a 138 550 n a 142 575 n a 145 600 n a 149 625 n a 152 SATURATED LIQUID PRESSURE TEMPERATURE CHART SATURATED LIQUID TEMPERATURE ºF SUCTION PRESSURE PSIG R 22 R 410A 50 26 1 52 28 3 54 29 4 56 31 6 58 32 7 60 34 8 62 35 10 64 37 11 66 38 13 68 40 14 70 41 15 72 42 16 74 44 17 76 45 19 78 46 20 80 48 21 85 50 24 90 53 26 95 56 29 100 59 31 110 64 36 ...

Страница 9: ... 7 to 9 ºF and superheat of 7 to 9 ºF a If subcooling and superheat are low adjust TXV to 7 to 9 ºF superheat then check subcooling NOTE To adjust superheat turn the valve stem clock wise to increase and counter clockwise to decrease b If subcooling is low and superheat is high add charge to raise subcooling to 7 to 9 ºF then check superheat c If subcooling and superheat are high adjust TXV valve ...

Страница 10: ...ltmeter Low Voltage Test Voltage Faulty Evap Fan Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Resistance of Anticipator Shortage of Refrigerant Test For Leaks Add Refrigerant Restricted Liquid Line Remove Restriction Replace Restricted Part Open Element or Limit on Elec Heater Test Heater Element and Controls Dirty Air Filter Inspect ...

Страница 11: ...11 THIS PAGE LEFT INTENTIONALLY BLANK ...

Страница 12: ...ep the outdoor coil clean Dirt leaves or debris could also restrict the airflow If cleaning of the outdoor coil becomes necessary hire a qualified servicer Inexperienced people could easily puncture the tubing in the coil Even a small hole in the tubing could eventually cause a large loss of refriger ant Loss of refrigerant can cause poor operation and or severe equipment damage Do not use a conde...