background image

12

SPLIT SYSTEMS

AIR CONDITIONING AND HEAT PUMP HOMEOWNER’S

 

ROUTINE MAINTENANCE RECOMMENDATIONS

We strongly recommend a bi-annual maintenance checkup be performed

before the heating and cooling seasons begin by a qualified servicer.

Replace or Clean Filter

IMPORTANT NOTE: Never operate unit without a filter installed as
dust and lint will build up on internal parts resulting in loss of
efficiency, equipment damage and possible fire.

An indoor air filter must be used with your comfort system. A
properly maintained filter will keep the indoor coil of your com-
fort system clean. A dirty coil could cause poor operation and/or
severe equipment damage.

Your air filter or filters could be located in your furnace, in a
blower unit, or in “filter grilles” in your ceiling or walls. The in-
staller of your air conditioner or heat pump can tell you where
your filter(s) are, and how to clean or replace them.

Check your filter(s) at least once a month. When they are dirty,
replace or clean as required. Disposable type filters should be
replaced. Reusable type filters may be cleaned.

You may want to ask your dealer about high efficiency filters. High
efficiency filters are available in both electronic and non-elec-
tronic types. These filters can do a better job of catching small
airborne particles.

Compressor

The compressor motor is hermetically sealed and does not re-
quire additional oiling.

Motors

Indoor and outdoor fan motors are permanently lubricated and
do not require additional oiling.

Clean Outside Coil (Qualified Servicer Only)

HIGH VOLTAGE! 
Disconnect ALL power before servicing. Multiple

power sources may be present. Failure to do so may

cause property damage, personal injury or death.

Air must be able to flow through the outdoor unit of your comfort
system. Do not construct a fence near the unit or build a deck or
patio over the unit without first discussing your plans with your
dealer or other qualified servicer. Restricted airflow could lead to
poor operation and/or severe equipment damage.

Likewise, it is important to keep the outdoor coil clean. Dirt, leaves,
or debris could also restrict the airflow. If cleaning of the outdoor
coil becomes necessary, hire a qualified servicer. Inexperienced
people could easily puncture the tubing in the coil. Even a small
hole in the tubing could eventually cause a large loss of refriger-
ant. Loss of refrigerant can cause poor operation and/or severe
equipment damage.

Do not use a condensing unit cover to “protect” the outdoor unit
during the winter, unless you first discuss it with your  dealer. Any
cover used must include “breathable” fabric to avoid moisture
buildup.

Check the thermostat to confirm that it is properly set.

Wait 15 minutes. Some devices in the outdoor unit or in
programmable thermostats will prevent compressor op-
eration for awhile, and then reset automatically. Also, some
power companies will install devices which shut off air
conditioners for several minutes on hot days. If you wait
several minutes, the unit may begin operation on its own.

T

O

 

AVOID

 

THE

 

RISK

 

OF

 

EQUIPMENT

 

DAMAGE

 

OR

 

FIRE

INSTALL

 

THE

 

SAME

AMPERAGE

 

BREAKER

 

OR

 

FUSE

 

AS

 

YOU

 

ARE

 

REPLACING

.  I

F

 

THE

 

CIRCUIT

 

BREAKER

OR

 

FUSE

 

SHOULD

 

OPEN

 

AGAIN

 

WITHIN

 

THIRTY

 

DAYS

CONTACT

 

A

 

QUALIFIED

SERVICER

 

TO

 

CORRECT

 

THE

 

PROBLEM

.

I

F

 

YOU

 

REPEATEDLY

 

RESET

 

THE

 

BREAKER

 

OR

 

REPLACE

 

THE

 

FUSE

 

WITHOUT

HAVING

 

THE

 

PROBLEM

 

CORRECTED

YOU

 

RUN

 

THE

 

RISK

 

OF

 

SEVERE

 

EQUIPMENT

 

DAMAGE

.

CAUTION

B

EFORE

 C

ALLING

 Y

OUR

 S

ERVICER

Check the electrical panel  for tripped circuit breakers  or
failed fuses. Reset the circuit breakers or replace fuses as
necessary.

Check the disconnect switch near the indoor furnace or
blower to confirm that it is closed.

Check for obstructions on the outdoor unit . Confirm that it
has not been covered on the sides or the top. Remove any
obstruction that can be safely  removed. If  the unit is cov-
ered with dirt or debris, call a qualified servicer to clean it.

Check for blockage of the indoor air inlets and outlets.
Confirm that they are open and have not been blocked by
objects (rugs, curtains or furniture).

Check the filter. If it is dirty, clean or replace it.

Listen for any unusual noise(s), other than normal operat-
ing noise, that might be coming from the outdoor unit.   If
you hear unusual noise(s) coming from the unit, call a quali-
fied servicer.

Содержание DZ13SC

Страница 1: ...e is delivered at the specified airflow See outdoor unit specification sheet for split system models or product specifica tion sheet for packaged and light commercial models Specifica tion sheets can be found at www daikincomfort com for Daikin brand products Within the website please select the residential or commercial products menu and then select the submenu for the type of product to be insta...

Страница 2: ...on in areas of heavy snow accumulation and or areas with prolonged continuous subfreezing temperatures Heat pump unit bases have cutouts under the outdoor coil that permit drainage of frost accumulation Situatetheunittopermitfreeunobstructeddrainage of the defrost water and ice In more severe weather locations it is recommended that the unit be elevated to allow unobstructed drainage and air flow ...

Страница 3: ... or TP 107 Long Line Set Application R 410A or contact your dis tributor for assistance Cond Unit Tons Suct Liq Suct Liq Suct Liq 1 1 2 5 8 1 4 3 4 3 8 3 4 3 8 2 5 8 1 4 3 4 3 8 3 4 3 8 2 1 2 5 8 1 4 3 4 3 8 7 8 3 8 3 3 4 3 8 7 8 3 8 1 1 8 3 8 3 1 2 7 8 3 8 1 1 8 3 8 1 1 8 3 8 4 7 8 3 8 1 1 8 3 8 1 1 8 3 8 5 7 8 3 8 1 1 8 3 8 1 1 8 3 8 Line Diameter In OD RECOMMENDED INTERCONNECTING TUBING Ft 0 24...

Страница 4: ...ially important on suction line filter driers which are continually wet when the unit is operating NOTE Be careful not to kink or dent refrigerant lines Kinked or dented lines will cause poor performance or compressor damage Do NOT make final refrigerant line connection until plugs are removed from refrigerant tubing NOTE Before brazing verify indoor piston size by checking the piston kit chart pa...

Страница 5: ...allation instructions supplied with the indoor furnace air handler for spe cific wiring connections and indoor unit configuration Likewise consult the instructions packaged with the thermostat for mount ing and location information Overcurrent Protection The following overcurrent protection devices are approved for use Time delay fuses HACR type circuit breakers These devices have sufficient time ...

Страница 6: ...il it may be necessary to add or remove refrigerant to attain proper charge If line set exceeds 15 feet in length refrigerant should be added at 6 ounces per foot of liquid line NOTE Charge should always be checked using superheat when using a piston and subcooling when using TXV equipped indoor coil to verify proper charge Open the suction service valve first If the liquid service valve is opened...

Страница 7: ...res to stabilize then check subcooling and or superheat as detailed in the following sec tions Superheat Suct Line Temp Sat Suct Temp Subcooling Sat Liquid Temp Liquid Line Temp To prevent personal injury carefully connect and disconnect manifold gauge hoses Escaping liquid refrigerant can cause burns Do not vent refrigerant into the atmosphere Recover all refrigerant during system repair and befo...

Страница 8: ... n a 123 445 n a 125 475 n a 130 500 n a 134 525 n a 138 550 n a 142 575 n a 145 600 n a 149 625 n a 152 SATURATED LIQUID PRESSURE TEMPERATURE CHART SATURATED LIQUID TEMPERATURE ºF SUCTION PRESSURE PSIG R 22 R 410A 50 26 1 52 28 3 54 29 4 56 31 6 58 32 7 60 34 8 62 35 10 64 37 11 66 38 13 68 40 14 70 41 15 72 42 16 74 44 17 76 45 19 78 46 20 80 48 21 85 50 24 90 53 26 95 56 29 100 59 31 110 64 36 ...

Страница 9: ... 7 to 9 ºF and superheat of 7 to 9 ºF a If subcooling and superheat are low adjust TXV to 7 to 9 ºF superheat then check subcooling NOTE To adjust superheat turn the valve stem clock wise to increase and counter clockwise to decrease b If subcooling is low and superheat is high add charge to raise subcooling to 7 to 9 ºF then check superheat c If subcooling and superheat are high adjust TXV valve ...

Страница 10: ...ltmeter Low Voltage Test Voltage Faulty Evap Fan Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Resistance of Anticipator Shortage of Refrigerant Test For Leaks Add Refrigerant Restricted Liquid Line Remove Restriction Replace Restricted Part Open Element or Limit on Elec Heater Test Heater Element and Controls Dirty Air Filter Inspect ...

Страница 11: ...11 THIS PAGE LEFT INTENTIONALLY BLANK ...

Страница 12: ...ep the outdoor coil clean Dirt leaves or debris could also restrict the airflow If cleaning of the outdoor coil becomes necessary hire a qualified servicer Inexperienced people could easily puncture the tubing in the coil Even a small hole in the tubing could eventually cause a large loss of refriger ant Loss of refrigerant can cause poor operation and or severe equipment damage Do not use a conde...

Отзывы: