background image

5

NO LEAKS

NO CONDENSIBLES

If the pressure rises to 1000 microns or less and remains
steady the system is considered leak-free; proceed to startup.

• If pressure rises above 1000 microns but holds steady be-

low 2000 microns, moisture and/or noncondensibles may
be present or the system may have a small leak.  Return to
step 2: If the same result is encountered check for leaks as
previously indicated and repair as necessary then repeat
evacuation.

If pressure rises above 2000 microns, a leak is present.  Check
for leaks as previously indicated and repair as necessary
then repeat evacuation.

Electrical Connections

HIGH VOLTAGE! 

Disconnect ALL power before servicing.

Multiple power sources may be present. Failure to do
so may cause property damage, personal injury or

death due to electric shock. Wiring must conform with
NEC or CEC and all local codes. Undersized wires could cause

poor equipment performance, equipment damage or fire.

To avoid the risk of fire or equipment damage, use copper

conductors.

NOTICE

Units with rotary or reciprocating compressors and non-bleed

TXV’s require a Hard Start Kit.

The condensing unit rating plate lists pertinent electrical data
necessary for proper electrical service and overcurrent protec-
tion.  Wires should be sized to limit voltage drop to 2% (max.)
from the main breaker or fuse panel to the condensing unit.  Con-
sult the NEC, CEC, and all local codes to determine the correct wire
gauge and length.

Local codes often require a disconnect switch located near the
unit; do not install the switch on the unit.  Refer to the installation
instructions supplied with the indoor furnace/air handler for spe-
cific wiring connections and indoor unit configuration.  Likewise,
consult the instructions packaged with the thermostat for mount-
ing and location information.

Overcurrent Protection

The following overcurrent protection devices are approved for
use.

Time delay fuses

HACR type circuit breakers

These devices have sufficient time delay to permit the motor-com-
pressor to start and accelerate its load.

Three Phase Compressor Rotation

Use care when handling scroll compressors. Dome temperatures

could be hot.

CAUTION

Three phase compressors are power phase dependent and can
rotate in either direction.

Verify proper rotation for three phase compressors by ensuring
the suction pressure drops and discharge pressure rises when the
compressor is energized. NOTE:  When operated in reverse, a three
phase scroll compressors is noisier and its current draw sub-
stantially reduced compared to marked values.

To correct, disconnect power and switch any two leads at the unit
contactor and re-observe.

High Voltage Connections

Route power supply and ground wires through the high voltage
port and terminate in accordance with the wiring diagram pro-
vided inside the control panel cover.

Low Voltage Connections

The indoor transformer must supply 24 volt AC low voltage power
to the outdoor section for the control wiring.  Cooling only units
require 25VA minimum and heat pump units require 40VA mini-
mum.  Low voltage wiring for two-stage units depends on the ther-
mostat used and the number of control wires between the indoor
unit and the condensing unit.  Route control wires through the low
voltage port and terminate in accordance with the wiring diagram
provided inside the control panel cover.

Содержание DZ13SC

Страница 1: ...e is delivered at the specified airflow See outdoor unit specification sheet for split system models or product specifica tion sheet for packaged and light commercial models Specifica tion sheets can be found at www daikincomfort com for Daikin brand products Within the website please select the residential or commercial products menu and then select the submenu for the type of product to be insta...

Страница 2: ...on in areas of heavy snow accumulation and or areas with prolonged continuous subfreezing temperatures Heat pump unit bases have cutouts under the outdoor coil that permit drainage of frost accumulation Situatetheunittopermitfreeunobstructeddrainage of the defrost water and ice In more severe weather locations it is recommended that the unit be elevated to allow unobstructed drainage and air flow ...

Страница 3: ... or TP 107 Long Line Set Application R 410A or contact your dis tributor for assistance Cond Unit Tons Suct Liq Suct Liq Suct Liq 1 1 2 5 8 1 4 3 4 3 8 3 4 3 8 2 5 8 1 4 3 4 3 8 3 4 3 8 2 1 2 5 8 1 4 3 4 3 8 7 8 3 8 3 3 4 3 8 7 8 3 8 1 1 8 3 8 3 1 2 7 8 3 8 1 1 8 3 8 1 1 8 3 8 4 7 8 3 8 1 1 8 3 8 1 1 8 3 8 5 7 8 3 8 1 1 8 3 8 1 1 8 3 8 Line Diameter In OD RECOMMENDED INTERCONNECTING TUBING Ft 0 24...

Страница 4: ...ially important on suction line filter driers which are continually wet when the unit is operating NOTE Be careful not to kink or dent refrigerant lines Kinked or dented lines will cause poor performance or compressor damage Do NOT make final refrigerant line connection until plugs are removed from refrigerant tubing NOTE Before brazing verify indoor piston size by checking the piston kit chart pa...

Страница 5: ...allation instructions supplied with the indoor furnace air handler for spe cific wiring connections and indoor unit configuration Likewise consult the instructions packaged with the thermostat for mount ing and location information Overcurrent Protection The following overcurrent protection devices are approved for use Time delay fuses HACR type circuit breakers These devices have sufficient time ...

Страница 6: ...il it may be necessary to add or remove refrigerant to attain proper charge If line set exceeds 15 feet in length refrigerant should be added at 6 ounces per foot of liquid line NOTE Charge should always be checked using superheat when using a piston and subcooling when using TXV equipped indoor coil to verify proper charge Open the suction service valve first If the liquid service valve is opened...

Страница 7: ...res to stabilize then check subcooling and or superheat as detailed in the following sec tions Superheat Suct Line Temp Sat Suct Temp Subcooling Sat Liquid Temp Liquid Line Temp To prevent personal injury carefully connect and disconnect manifold gauge hoses Escaping liquid refrigerant can cause burns Do not vent refrigerant into the atmosphere Recover all refrigerant during system repair and befo...

Страница 8: ... n a 123 445 n a 125 475 n a 130 500 n a 134 525 n a 138 550 n a 142 575 n a 145 600 n a 149 625 n a 152 SATURATED LIQUID PRESSURE TEMPERATURE CHART SATURATED LIQUID TEMPERATURE ºF SUCTION PRESSURE PSIG R 22 R 410A 50 26 1 52 28 3 54 29 4 56 31 6 58 32 7 60 34 8 62 35 10 64 37 11 66 38 13 68 40 14 70 41 15 72 42 16 74 44 17 76 45 19 78 46 20 80 48 21 85 50 24 90 53 26 95 56 29 100 59 31 110 64 36 ...

Страница 9: ... 7 to 9 ºF and superheat of 7 to 9 ºF a If subcooling and superheat are low adjust TXV to 7 to 9 ºF superheat then check subcooling NOTE To adjust superheat turn the valve stem clock wise to increase and counter clockwise to decrease b If subcooling is low and superheat is high add charge to raise subcooling to 7 to 9 ºF then check superheat c If subcooling and superheat are high adjust TXV valve ...

Страница 10: ...ltmeter Low Voltage Test Voltage Faulty Evap Fan Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Resistance of Anticipator Shortage of Refrigerant Test For Leaks Add Refrigerant Restricted Liquid Line Remove Restriction Replace Restricted Part Open Element or Limit on Elec Heater Test Heater Element and Controls Dirty Air Filter Inspect ...

Страница 11: ...11 THIS PAGE LEFT INTENTIONALLY BLANK ...

Страница 12: ...ep the outdoor coil clean Dirt leaves or debris could also restrict the airflow If cleaning of the outdoor coil becomes necessary hire a qualified servicer Inexperienced people could easily puncture the tubing in the coil Even a small hole in the tubing could eventually cause a large loss of refriger ant Loss of refrigerant can cause poor operation and or severe equipment damage Do not use a conde...

Отзывы: