background image

7

FINAL CHARGE ADJUSTMENT

The outdoor temperature must be 60°F or higher. Set the room
thermostat to COOL, fan switch to AUTO, and set the tempera-
ture control well below room temperature.

After system has stabilized per startup instructions, check sub-
cooling and superheat as detailed in the following section.

EXPANSION VALVE SYSTEM

NOTE:  

The expansion valve bulb must be in place on the suction

line and insulated.

Expansion Valve Indoor Coils:

Outdoor Temperature Over 60ºF. 

When the outdoor tempera-

ture is above 60ºF, charge the system with the room thermostat
set in the “Cooling” mode and the fan operating in the “Auto”
position.

Outdoor Temperature Below 60ºF. 

When the outdoor tempera-

ture is below 60ºF, charge the system with the room thermostat
set in the “Heat” mode and the fan operating in the “Auto” posi-
tion.

System Charging Cooling Mode.

 At stabilized cooling conditions

and with an outdoor temperature of 60°F or higher, the system
should have from 9°F to 13°F subcooling. For a proper subcooling
reading, measure the refrigerant pressure and temperature at the
outdoor unit’s liquid line service valve. If you have less than 9°F
subcooling, add charge. If you have more than 13°F subcooling,
remove charge.

While reaching the proper subcooling level it is important to know
the discharge line temperature. This temperature should be at
least 80ºF over ambient or unit is flooding back to compressor.

System Charging Heating Mode. 

Measure the hot gas discharge

at the compressor to check the system charge in heat mode.

1. Allow the system to operate for at least 20 minutes.

2. Attach and insulate an electronic thermometer to the hot

gas discharge line mid way between the compressor and the
reversing valve.  

Note: 

 The thermometer is to be well insu-

lated to prevent ambient influences.

3. Adjust the charge to maintain a clear sight glass.

4. Allow the compressor to operate for about 10 additional min-

utes and measure the hot gas discharge temperature.

5. Using an additional electronic thermometer, measure the

ambient.

6. Adjust the charge until the hot gas temperature equals 105

º

F

+ ambient (+ or – 5

º

F). Remove charge to increase the tem-

perature.

NOTE:  

When adjusting the charge, allow the compressor to

operate for about 10 minutes before taking readings.

NOTE:  

Subsequent opening and replace of the cap will require

only 1/2 to 1 hex flat. See the table below for the torque required
for an effective seal on the valve bonnet (1/6 turn past finger tight.

TUBING SIZE

TORQUE

(ft-lbs)

5/8

14

1 3/8

16

After closing the valve bonnet, perform a final refrigerant leak test
on the valves and sweat connections.  Return the room thermo-
stat to the desired settings.

DEFROST CONTROL ADJUSTMENTS

This heat pump uses a Time/Temperature method for defrost.  A
thermal sensor electrically set to “Normally Open” is wired to the
electronic defrost control located in the control box. The thermal
sensor attached to the condenser coil determines the outdoor coil
temperature.

Both coil temperature and compressor “run time” determine de-
frosting of the outdoor coil. Adjustments to the defrost timing se-
lection can be changed from the 60 minute factory setting to ei-
ther 30 or 90 minutes by moving the jumper on the defrost con-
trol.  For the system to initiate a defrost, the following statements
must be true:

The Defrost Sensor is closed, and

The compressor “run time” is equal to the timing selection
on the defrost board.

During defrost the following actions occur:

1. The reversing valve is energized and the heat pump oper-

ates in the cooling mode.

2. The airhandler auxiliary heat (if equipped) is activated.

3. The condenser fan motor is shut-off.

If the defrost cycle has not terminated after ten (10) minutes the
control will override the defrost sensor and revert to a heating
mode.

The defrost control has test pins which can be useful when trouble-
shooting in the heating mode. These test pins accelerate the com-
pressor run time counter.  The suggested method for accessing
this feature is:

1. Run unit in heat mode.

2. Check unit for proper charge.

NOTE:

 Bands of frost indicate low refrigerant charge.

3. Shut off power to unit.

Содержание DZ11TA Series

Страница 1: ...tion damage or installation of incorrectly shipped units CODES REGULATIONS This product is designed and manufactured to comply with na tional codes Installation in accordance with such codes and or prevailing local codes regulations is the responsibility of the in staller The manufacturer assumes no responsibility for equip ment installed in violation of any codes or regulations Rated per formance...

Страница 2: ...s preferred When possible mini mize the amount of bends and turns ROOFTOP INSTALLATIONS If it is necessary to install this unit on a roof structure ensure the roof structure can support the weight and that proper consider ation is given to the weather tight integrity of the roof Since the unit can vibrate during operation sound vibration transmission should be considered when installing the unit V...

Страница 3: ... tubing clean and dry prior to and during installation Tubing should always be cut square keeping ends round and free from burrs Clean the tubing to prevent contamination Do NOT let refrigerant lines come in direct contact with plumbing ductwork floor joists wall studs floors and walls When running refrigerant lines through a foundation or wall openings should allow for sound and vibration absorbi...

Страница 4: ...iers which are continually wet when the unit is operating NOTE Be careful not to kink or dent refrigerant lines Kinked or dented lines will cause poor performance or compressor damage Do NOT make final refrigerant line connection until plugs are removed from refrigerant tubing NOTE Before brazing verify indoor piston size by checking the piston kit chart packaged with indoor unit LEAK TESTING NITR...

Страница 5: ...fficient to carry the Minimum Circuit Ampacity MCA listed on the serial plate The supply voltage can be unbalanced phase to phase within 2 The following formula can be used to determine the percent age of voltage unbalance for your unit Percentage Voltage Unbalance 100 x Max Voltage Deviation From Average Voltage Average Voltage Example L1 L2 220V L2 L3 216V Average Voltage 220 216 213 3 649 3 Max...

Страница 6: ...y reduced compared to marked values To correct disconnect power and switch any two leads at the unit contactor and re observe HIGH VOLTAGE CONNECTIONS Route power supply and ground wires through the high voltage port and terminate in accordance with the wiring diagram pro vided inside the control panel cover LOW VOLTAGE CONNECTIONS Condensing unit control wiring requires a five conductor low volt ...

Страница 7: ...rature 5 Using an additional electronic thermometer measure the ambient 6 Adjust the charge until the hot gas temperature equals 105º F ambient or 5º F Remove charge to increase the tem perature NOTE When adjusting the charge allow the compressor to operate for about 10 minutes before taking readings NOTE Subsequent opening and replace of the cap will require only 1 2 to 1 hex flat See the table b...

Страница 8: ...t of equipment 1 1 x temp rise In other cases measurement of external static pressure is helpful For details see the Installation Instructions for your indoor unit TROUBLE SHOOTING ANALYSIS TABLE COMPLAINT PROBABLE CAUSE REMEDY 1 High Head Pressure 1 Excessive charge of refrigerant in system 2 Inadequate supply of air across the condenser coil 3 Non condensate gases in the system 1 Purge or pump d...

Страница 9: ...low 375 425 CFM ton will cause excessive discharge pressures that may cause the high pres sure switch to function Low Return Air Temperatures Return ductwork temperatures that are less than 60 F will cause low discharge pressure low suction pressure and excessive de frost cycling Undercharging An undercharged system will cause low discharge pressure low suction pressure and an accumulation of fros...

Страница 10: ...10 THIS PAGE LEFT INTENTIONALLY BLANK ...

Страница 11: ...ER MOTOR RELAY CS COMPRESSOR SOLENOID HPS HIGH PRESSURE SWITCH CHS CRANKCASE HEATER SWITCH SSHR SECOND STAGE HEAT RELAY CONTROLS SHOWN WITH THERMOSTAT IN OFF POSITION WIRING CODE FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE LOW VOLTAGE LVJB CONTROL BO X BK BR PU BK DFT YL PK LPS DFT W O RV DC RVC BK BK CH BK W2 RD YL C T1 L1 T2 L2 T3 L3 YL RD FC PU BR PU ...

Страница 12: ...12 Our continuing commitment to quality products may mean a change in specifications without notice 2018 5151 San Felipe St Suite 500 Houston TX 77056 www daikinac com ...

Отзывы: