background image

6

OVERCURRENT PROTECTION

The following overcurrent protection devices are approved for use.

Time delay fuses

HACR type circuit breakers

These devices have sufficient time delay to permit the motor-com-
pressor to start and accelerate its load.

Refer to the unit serial plate for the maximum overcurrent pro-
tection permitted.

Run all line voltage wiring a conduit from the service disconnect
box to the unit. Refer to the NEC (USA) or CEC (Canada) codes for
the correct size conduit based on the wire size. The conduit en-
ters the control box through the hole provided in the bottom.

NOTE: 

The control box hole is sized for 3/4” conduit. If permitted

by code, a flexible conduit is preferred to minimize vibration trans-
mission from the unit to the building.

Connect the line voltage wires to the L1, L2, and L3 terminals of
the definite purpose contactor (located in the unit control box).
Refer to the wiring diagram attached to the unit when making
these connections.

THREE PHASE COMPRESSOR ROTATION

Use care when handling scroll compressors. Dome temperatures

could be hot.

CAUTION

Three phase scrolls are power phase dependent and can compress
in more than one direction.

Verify proper rotation for three phase compressors by ensuring
the suction pressure drops and discharge pressure rises when the
compressor is energized. 

NOTE: 

 When operated in reverse, a three

phase scroll compressors is noisier and its current draw substan-
tially reduced compared to marked values.

To correct, disconnect power and switch any two leads at the unit
contactor and re-observe.

HIGH VOLTAGE CONNECTIONS

Route power supply and ground wires through the high voltage
port and terminate in accordance with the wiring diagram pro-
vided inside the control panel cover.

LOW VOLTAGE CONNECTIONS

Condensing unit control wiring requires a five-conductor low volt-
age circuit from the room thermostat (without options). The wires
should be no smaller than 18 AWG and the field connection for
this circuit  must be made in the unit control box using solderless
connectors (i.e. wire nuts). See the following diagram for a typical
low voltage hook-up.

TWO STAGE LOW VOLTAGE HOOK-UP

THERMOSTAT

O

W2

C

R

RED

BROWN

WHITE

BLUE

BLUE

WHITE

CONDENSING 

UNIT

AIR 

HANDLER

YELLOW

PURPLE

RED

Y1

G

GREEN

Y2

WIRE NUT

ORANGE

SYSTEM START UP

Never operate the compressor with the suction valve

 

closed to

test the compressor’s pumping efficiency. In some

 

cases, this can

result in serious compressor damage and loss of warranty cover-
age.

For the 7-1/2 ton unit starting charge should be 18 lbs. of R-410A and
20 lbs. for the 10 ton unit. The length of line set, indoor unit air-
flow, condensing unit location and number of tubing fittings will
have an impact on final unit charge amount. Turn the electrical
power on, and let the system run. Wait for the refrigerant pres-
sures to stabilize.

CHARGE VERIFICATION

CAUTION

NOTICE

Violation of EPA regulations may result in fines or other penalties.

Operating the compressor with the suction valve closed will void

the warranty and cause serious compressor damage.

CAUTION

Содержание DZ11TA Series

Страница 1: ...tion damage or installation of incorrectly shipped units CODES REGULATIONS This product is designed and manufactured to comply with na tional codes Installation in accordance with such codes and or prevailing local codes regulations is the responsibility of the in staller The manufacturer assumes no responsibility for equip ment installed in violation of any codes or regulations Rated per formance...

Страница 2: ...s preferred When possible mini mize the amount of bends and turns ROOFTOP INSTALLATIONS If it is necessary to install this unit on a roof structure ensure the roof structure can support the weight and that proper consider ation is given to the weather tight integrity of the roof Since the unit can vibrate during operation sound vibration transmission should be considered when installing the unit V...

Страница 3: ... tubing clean and dry prior to and during installation Tubing should always be cut square keeping ends round and free from burrs Clean the tubing to prevent contamination Do NOT let refrigerant lines come in direct contact with plumbing ductwork floor joists wall studs floors and walls When running refrigerant lines through a foundation or wall openings should allow for sound and vibration absorbi...

Страница 4: ...iers which are continually wet when the unit is operating NOTE Be careful not to kink or dent refrigerant lines Kinked or dented lines will cause poor performance or compressor damage Do NOT make final refrigerant line connection until plugs are removed from refrigerant tubing NOTE Before brazing verify indoor piston size by checking the piston kit chart packaged with indoor unit LEAK TESTING NITR...

Страница 5: ...fficient to carry the Minimum Circuit Ampacity MCA listed on the serial plate The supply voltage can be unbalanced phase to phase within 2 The following formula can be used to determine the percent age of voltage unbalance for your unit Percentage Voltage Unbalance 100 x Max Voltage Deviation From Average Voltage Average Voltage Example L1 L2 220V L2 L3 216V Average Voltage 220 216 213 3 649 3 Max...

Страница 6: ...y reduced compared to marked values To correct disconnect power and switch any two leads at the unit contactor and re observe HIGH VOLTAGE CONNECTIONS Route power supply and ground wires through the high voltage port and terminate in accordance with the wiring diagram pro vided inside the control panel cover LOW VOLTAGE CONNECTIONS Condensing unit control wiring requires a five conductor low volt ...

Страница 7: ...rature 5 Using an additional electronic thermometer measure the ambient 6 Adjust the charge until the hot gas temperature equals 105º F ambient or 5º F Remove charge to increase the tem perature NOTE When adjusting the charge allow the compressor to operate for about 10 minutes before taking readings NOTE Subsequent opening and replace of the cap will require only 1 2 to 1 hex flat See the table b...

Страница 8: ...t of equipment 1 1 x temp rise In other cases measurement of external static pressure is helpful For details see the Installation Instructions for your indoor unit TROUBLE SHOOTING ANALYSIS TABLE COMPLAINT PROBABLE CAUSE REMEDY 1 High Head Pressure 1 Excessive charge of refrigerant in system 2 Inadequate supply of air across the condenser coil 3 Non condensate gases in the system 1 Purge or pump d...

Страница 9: ...low 375 425 CFM ton will cause excessive discharge pressures that may cause the high pres sure switch to function Low Return Air Temperatures Return ductwork temperatures that are less than 60 F will cause low discharge pressure low suction pressure and excessive de frost cycling Undercharging An undercharged system will cause low discharge pressure low suction pressure and an accumulation of fros...

Страница 10: ...10 THIS PAGE LEFT INTENTIONALLY BLANK ...

Страница 11: ...ER MOTOR RELAY CS COMPRESSOR SOLENOID HPS HIGH PRESSURE SWITCH CHS CRANKCASE HEATER SWITCH SSHR SECOND STAGE HEAT RELAY CONTROLS SHOWN WITH THERMOSTAT IN OFF POSITION WIRING CODE FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE LOW VOLTAGE LVJB CONTROL BO X BK BR PU BK DFT YL PK LPS DFT W O RV DC RVC BK BK CH BK W2 RD YL C T1 L1 T2 L2 T3 L3 YL RD FC PU BR PU ...

Страница 12: ...12 Our continuing commitment to quality products may mean a change in specifications without notice 2018 5151 San Felipe St Suite 500 Houston TX 77056 www daikinac com ...

Отзывы: