background image

2

INSTALLATION CLEARANCES

This unit is designed for outdoor installations only. Special consid-
eration must be given to location of the condensing unit(s) in re-
gard to structures, obstructions, other units, and any/all other fac-
tors that may interfere with air circulation.  Where possible, the
top of the unit should be completely unobstructed; however, if
vertical conditions require placement beneath an obstruction 

there

should be a minimum of 60 inches between the top of the unit
and the obstruction(s).  

The specified dimensions meet require-

ments for air circulation only. Consult all appropriate regulatory
codes prior to determining final clearances.

Another important consideration in selecting a location for the
unit(s) is the angle to obstructions.  Either side adjacent the valves
can be placed toward the structure provided the side away from
the structure maintains minimum service clearance.  Corner in-
stallations are strongly discouraged.

12"

12"

12"

60"

24"

This unit can be located at ground floor level or on flat roofs. At
ground floor level, the unit must be on a solid, level foundation
that will not shift or settle. To reduce the possibility of sound trans-
mission, the foundation slab should not be in contact with or be
an integral part of the building foundation. The foundation slab
should be a minimum of 6” wider than the unit in all directions.
Ensure the foundation is sufficient to support the unit. A concrete
slab raised above ground level provides a suitable base.

The selected site should be no greater than 50’ below or 70’ above
the evaporator section. For optimum performance, the minimum
length interconnecting tubing is preferred. When possible mini-
mize the amount of bends and turns.

ROOFTOP INSTALLATIONS

If it is necessary to install this unit on a roof structure, ensure the
roof structure can support the weight and that proper consider-
ation is given to the weather-tight integrity of the roof. Since the
unit can vibrate during operation, sound vibration transmission
should be considered when installing the unit. Vibration absorb-
ing pads or springs can be installed between the condensing unit
legs or frame and the roof mounting assembly to reduce noise
vibration.

NOTE:

 These units require special location consideration in areas

of heavy snow accumulation and/or areas with prolonged
continuous subfreezing temperatures. Heat pump unit bases have
cutouts under the outdoor coil that permit drainage of frost
accumulation. Situate the unit to permit free unobstructed
drainage of the defrost water and ice. A minimum 3" clearance
under the outdoor coil is required in the milder climates.
In more severe weather locations, it is recommended that the
unit be elevated to allow unobstructed drainage and air flow.

RIGGING

To avoid possible injury or death, all panels must be in position 

and secured before lifting this equipment.

Use field-supplied spreader bars when lifting the unit to minimize
the possibility of lifting cable/straps damage. To protect the cabi-
net louvers, use protective material such as plywood behind the
cable/straps. Arrange the straps to form a central suspension
point. 

NOTE:

 When raising and setting the unit, observe all safety

rules. Remove shipping skid and all protection and lifting material
after the unit is in place.

SAFE REFRIGERANT HANDLING

While these items will not cover every conceivable situation,
they should serve as a useful guide.

To avoid possible injury, explosion or death, practice safe
handling of refrigerants.

Содержание DZ11TA Series

Страница 1: ...tion damage or installation of incorrectly shipped units CODES REGULATIONS This product is designed and manufactured to comply with na tional codes Installation in accordance with such codes and or prevailing local codes regulations is the responsibility of the in staller The manufacturer assumes no responsibility for equip ment installed in violation of any codes or regulations Rated per formance...

Страница 2: ...s preferred When possible mini mize the amount of bends and turns ROOFTOP INSTALLATIONS If it is necessary to install this unit on a roof structure ensure the roof structure can support the weight and that proper consider ation is given to the weather tight integrity of the roof Since the unit can vibrate during operation sound vibration transmission should be considered when installing the unit V...

Страница 3: ... tubing clean and dry prior to and during installation Tubing should always be cut square keeping ends round and free from burrs Clean the tubing to prevent contamination Do NOT let refrigerant lines come in direct contact with plumbing ductwork floor joists wall studs floors and walls When running refrigerant lines through a foundation or wall openings should allow for sound and vibration absorbi...

Страница 4: ...iers which are continually wet when the unit is operating NOTE Be careful not to kink or dent refrigerant lines Kinked or dented lines will cause poor performance or compressor damage Do NOT make final refrigerant line connection until plugs are removed from refrigerant tubing NOTE Before brazing verify indoor piston size by checking the piston kit chart packaged with indoor unit LEAK TESTING NITR...

Страница 5: ...fficient to carry the Minimum Circuit Ampacity MCA listed on the serial plate The supply voltage can be unbalanced phase to phase within 2 The following formula can be used to determine the percent age of voltage unbalance for your unit Percentage Voltage Unbalance 100 x Max Voltage Deviation From Average Voltage Average Voltage Example L1 L2 220V L2 L3 216V Average Voltage 220 216 213 3 649 3 Max...

Страница 6: ...y reduced compared to marked values To correct disconnect power and switch any two leads at the unit contactor and re observe HIGH VOLTAGE CONNECTIONS Route power supply and ground wires through the high voltage port and terminate in accordance with the wiring diagram pro vided inside the control panel cover LOW VOLTAGE CONNECTIONS Condensing unit control wiring requires a five conductor low volt ...

Страница 7: ...rature 5 Using an additional electronic thermometer measure the ambient 6 Adjust the charge until the hot gas temperature equals 105º F ambient or 5º F Remove charge to increase the tem perature NOTE When adjusting the charge allow the compressor to operate for about 10 minutes before taking readings NOTE Subsequent opening and replace of the cap will require only 1 2 to 1 hex flat See the table b...

Страница 8: ...t of equipment 1 1 x temp rise In other cases measurement of external static pressure is helpful For details see the Installation Instructions for your indoor unit TROUBLE SHOOTING ANALYSIS TABLE COMPLAINT PROBABLE CAUSE REMEDY 1 High Head Pressure 1 Excessive charge of refrigerant in system 2 Inadequate supply of air across the condenser coil 3 Non condensate gases in the system 1 Purge or pump d...

Страница 9: ...low 375 425 CFM ton will cause excessive discharge pressures that may cause the high pres sure switch to function Low Return Air Temperatures Return ductwork temperatures that are less than 60 F will cause low discharge pressure low suction pressure and excessive de frost cycling Undercharging An undercharged system will cause low discharge pressure low suction pressure and an accumulation of fros...

Страница 10: ...10 THIS PAGE LEFT INTENTIONALLY BLANK ...

Страница 11: ...ER MOTOR RELAY CS COMPRESSOR SOLENOID HPS HIGH PRESSURE SWITCH CHS CRANKCASE HEATER SWITCH SSHR SECOND STAGE HEAT RELAY CONTROLS SHOWN WITH THERMOSTAT IN OFF POSITION WIRING CODE FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE LOW VOLTAGE LVJB CONTROL BO X BK BR PU BK DFT YL PK LPS DFT W O RV DC RVC BK BK CH BK W2 RD YL C T1 L1 T2 L2 T3 L3 YL RD FC PU BR PU ...

Страница 12: ...12 Our continuing commitment to quality products may mean a change in specifications without notice 2018 5151 San Felipe St Suite 500 Houston TX 77056 www daikinac com ...

Отзывы: