background image

D-EOMWC00803-26_01EN - 16/39 

Setpoint/Sub-
Menu 

Default 

Range 

Description 

Clr Stg Delays 

Off 

Off 
Reset 

This command, visible only with service password, can be 
used to reset the Stage Up/Dn Timer. 

4.2.6.5 

Standby Chiller 

This menu allows to configure the standby chiller 

Setpoint/Sub-
Menu 

Default 

Range 

Description 

Standby Chiller= 

No

 

No,  Auto,  Master,  Slave  1,  Slave 
2, Slave 3 

Standby chiller selection 

Cycling Type= 

Time

 

Run Hours, Sequence 

Cycling  type  of  standby  chiller  if  previous  parameter 
Standby Chiller is set as Auto 

Interval Time= 

7 Days

 

1…365 

Define the interval time (expressed in day) for the cycling of 
standby chiller 

Switch Time= 

00:00:00

 

00:00:00…23:59:59 

Define the time within the day when will be performed the 
switch of the standby chiller 

Tmp Cmp= 

No 

No,Yes 

Enabling of Temperature Compensation function 

Tmp Comp Time= 

120 min 

0…600 

Time constant of Temperature Compensation function 

Standby Reset= 

Off 

Off, Reset 

Parameter to reset standby chiller cycling timer 

 

Rapid Restart 

This page shows if the function Rapid Restart is enabled by external contact and it allows to define the maximum black out 
time in order to recover quickly the unit load. 

Setpoint/Sub-
Menu 

Default 

Range 

Description 

Rapid Restart= 

Disable 

Enable, Disable 

Feature enable if Rapid Restart is installed 

Pwr Off Time= 

60s 

Maximum black out time to enable Rapid Restart 

 

Date/Time 

This page will allow to adjust the time and date in the UC. This time and date will be used in the alarm log and to enable 
and disable the Quiet Mode. Additionally it’s also possible to set the starting and ending date for the DayLight Saving time 
(DLS) if used. Quiet Mode is a feature that is used to reduce the chiller noise. This is done by applying the maximum 
setpoint reset to the cooling setpoint and increasing the condenser temperature target by an adjustable offset.  

Setpoint/Sub-Menu 

Default 

Range 

Description 

Actual Time= 

12:00:00 

 

Set the time 

Actual Date= 

01/01/2014 

 

Set the date 

UTC Diff= 

-60min 

 

Difference with UTC 

DLS Enable= 

Yes 

No, Yes 

Enable DayLight Saving time 

DLS Strt Month= 

Mar 

 

DayLight Saving time start month 

DLS Strt Week= 

2ndWeek 

 

DayLight Saving time start week 

DLS End Month= 

Nov 

NA, Jan…Dec 

DayLight Saving time end month 

DLS End Week= 

1stWeek 

1

st

…5

th

 week 

DayLight Saving time end week 

On board real time clock settings are maintained thanks to a battery mounted on the controller. Make sure  that the battery 
is replaced regularly each 2 years (see section 3.5)

 

Scheduler 

This page allows to program the time scheduler 

Setpoint/Sub-
Menu 

Default 

Range 

Description 

State 

Off 

Off, On Setpoint 1, On Setpoint 

Actual state provided by the time scheduler 

Monday 

 

Link to Monday scheduler programming page 

Tuesday 

 

Link to Tuesday scheduler programming page 

Wednesday 

 

Link to Wednesday scheduler programming page 

Thursday 

 

Link to Thursday scheduler programming page 

Friday 

 

Link to Friday scheduler programming page 

Saturday 

 

Link to Saturday scheduler programming page 

Sunday 

 

Link to Sunday scheduler programming page 

Table below reports the menu used to program daily time slots. Six time slots can be programmed by the user. 

Содержание DWSC - Vintage C

Страница 1: ...WATER COOLED CENTRIFUGAL CHILLERS DWSC Vintage C DWDC Vintage C REV 01 Date 08 2022 Supersedes D EOMWC00803 6_00EN Operating Manual D EOMWC00803 26_01EN...

Страница 2: ...n Menu 12 4 2 View Set Unit 12 Thermostat Ctrl 13 Network Ctrl 13 Pumps 13 Condenser 13 Evaporator 14 Master Slave 14 4 2 6 1 Data 14 4 2 6 2 Options 15 4 2 6 3 Thermostat Ctrl 15 4 2 6 4 Timers 15 4...

Страница 3: ...5 1 4 4 Setpoint Reset by External 4 20 mA Signal 30 5 1 4 5 Setpoint Reset by Evaporator Return Temperature 30 5 1 4 6 Soft Load 31 Scheduler 31 5 2 Unit Start up 31 Unit Status 31 Prepare the unit t...

Страница 4: ...n the controller The emergency stop causes all motors to stop but does not switch off power to the unit Do not service or operate on the unit without having switched off the main switch 1 2 Before swi...

Страница 5: ...e refrigeration circuits are called circuit 1 and circuit 2 The compressor in circuit 1 is labelled Cmp1 The other in circuit 2 is labelled Cmp2 The following abbreviations are used CEWT Condenser Ent...

Страница 6: ...ll boards can be also supplied by a 24Vdc source CAUTION Maintain the correct polarity when connecting the power supply to the boards otherwise the peripheral bus communication will not operate and th...

Страница 7: ...ripheral bus with the UC The UC continuously manages the information received from the various pressure and temperature probes installed on the unit The UC incorporates a program that controls the uni...

Страница 8: ...O f f U n i t S W A c t i v e S e t p t 7 0 C The active item is highlighted in contrast in this example the item highlighted in Main Menu is a link to another page By pressing the push n roll the HMI...

Страница 9: ...ED Mode Solid Green BSP running Solid Green Communication running I O working Solid Red Hardware Error Solid Red Communication down Flashing Red BSP Error Solid Yellow Communication running but parame...

Страница 10: ...ting diode located below the bell button The Remote can be ordered with the unit and shipped loose as a field installed option It can also be ordered any time after chiller shipment and mounted and wi...

Страница 11: ...Enter the following credential to get access to the web interface User Name ADMIN Password SBTAdmin The Main Menu page will be displayed The page is a copy of the onboard HMI and follows the same rule...

Страница 12: ...age Evaporator LWT 273 1 C Evaporator leaving water temperature link to Temperatures page Condenser LWT 273 1 C Condenser leaving water temperature link to Temperatures page W C units only Unit Capaci...

Страница 13: ...nt Sub Menu Default Range Description Evp Pmp Ctrl 1 Only 1 Only 2 Only Auto 1 Primary 2 Primary Set number of Evaporator pumps operational and which priority Evap Recirc Tm 30s 0 300s Water recircula...

Страница 14: ...ink is available only on the Master unit Timers Submenu Timers This link is available only on the Master unit Standby Chiller Submenu Standby Chiller This link is available only on the Master unit Dis...

Страница 15: ...sible only if the parameter M S Num Of Unit has been configured at least with value 4 Master Enable Enable Enable Disable This parameter allows to enable or disable locally the Master Chiller Control...

Страница 16: ...ed in the alarm log and to enable and disable the Quiet Mode Additionally it s also possible to set the starting and ending date for the DayLight Saving time DLS if used Quiet Mode is a feature that i...

Страница 17: ...ad Setpoint Reset Submenu for Setpoint Reset 4 2 10 1 Demand Limit Setpoint Sub Menu Default Range Description Demand Lim En Disable Disable Enable Demand Limit Enable Demand Limit 100 0 Demand Limit...

Страница 18: ...munication is established only if this parameter displays Connected Cntrlr ID Controller ID This parameter is helpful to identify the specific controller in DoS Remote Update Disable Disable Enable Al...

Страница 19: ...and repeat the steps in chapter 4 2 13 1 If there is no enough time to ask for a Password to Daikin Personnel ex an expected failure of the controller a set of Free Limited Password is provided in ord...

Страница 20: ...otocol settings page can be accessed via the path Main Menu Commission Unit SW Modbus MSTP The values that can be set are the same as those found on the Modbus MSTP option page with the relative drive...

Страница 21: ...ettings page can be accessed via the path Main Menu Commission Unit SW BACNet MSTP The values that can be set are the same as those found on the BACNet MSTP option page with the relative driver and de...

Страница 22: ...via the path Main Menu Commission Unit SW BACNet IP The values that can be set are the same as those found on the BACNet MSTP option page with the relative driver and depend on the specific system whe...

Страница 23: ...jumps to the page Temperatures This page resumes all the relevant water temperatures Setpoint Sub Menu Default Range Description Evap LWT 273 1 C Controlled water temperature Evap EWT 273 1 C Return w...

Страница 24: ...d 4 9 Timers This page indicates the remaining cycle timers for each circuit and the remaining staging timers When the cycle timers are active any new start of a compressor is inhibited Setpoint Sub M...

Страница 25: ...NA 27 0 310 0 Low pressure alarm prevention TZ with R1234ze Evap Water Frz 2 2 C 2 0 6 0 C Evaporator Water Freeze Limit Cond Water Frz 2 2 C 2 0 6 0 C Condenser Water Freeze Limit Flow Proof Time 15...

Страница 26: ...il Feed Pressure offset Oil Sump Pres Oil Sump e Pressure current reading includes the offset Oil Sump P Offset 0 0kPa Oil Sump Pressure offset Calibrations of the Evaporator Pressure and Suction Temp...

Страница 27: ...de is required This setting implies an operation with double setpoint which is activated through a customer supplied switch according to the following logic Switch OFF The chiller will work in cooling...

Страница 28: ...each setpoint Operating Mode Units Double Setpoint Input Scheduler LWT Setpoint Default Range Cool W C OFF Off On Setpoint 1 Cool LWT 1 7 0 C 4 0 C 15 0 C ON On Setpoint 2 Cool LWT 2 7 0 C 4 0 C 15 0...

Страница 29: ...up 2 Primary Set to this in case of twin pump with 2 running and 1 as a backup Power Conservation 5 1 4 1 Demand Limit Demand limit function allows the unit to be limited to a specified maximum load C...

Страница 30: ...Max Setpoint Reset valid for all active modes Start Reset DT Used on Setpoint Reset by Evaporator DT 5 1 4 4 Setpoint Reset by External 4 20 mA Signal The active setpoint is calculated applying a corr...

Страница 31: ...e BAS company how to start the unit Master Disable Unit is disabled by the Master Slave function Scheduler Disabled Unit is disabled by the time scheduler Unit Alarm A unit alarm is active Check the a...

Страница 32: ...ependently from the status of the individual enable switches 5 2 2 2 Keypad Enable The Keypad enable setpoint is not accessible by user password level If it is set to Disable contact your local mainte...

Страница 33: ...ur 1 Vfd by mean of a modulating 0 10V signal generated through a PID controller The following graph is an example of the modulating signal behavior in case of a PID control supposed to be purely prop...

Страница 34: ...at the monitor is connected to the PLC via Ethernet cable so that the PLC data is displayed correctly It allows the unit s operating parameters to be set and the data to be displayed At the top of the...

Страница 35: ...s the main information of the unit such as 1 Condenser Leaving Water Temperature 2 Condenser Entering Water Temperature 3 Evaporator Leaving Water Temperature 4 Evaporator Entering Water Temperature I...

Страница 36: ...ate the Touchscreen 6 Select the logging 7 Update the software version when a new release is available In addition the system device and the USB device if present storages are shown It is possible to...

Страница 37: ...ssible to track a maximum of 4 datapoints for each graph chart There are four customizable graph charts Two options are available to change the time range of the trend 1 20 minutes 2 1 hour To add a d...

Страница 38: ...ion integrates the current limit function which allows the unit to limit its capacity in order not to exceed a pre defined current setpoint This setpoint can be set in the unit display or can be chang...

Страница 39: ...t of its knowledge No express or implied warranty is given for the completeness accuracy reliability or fitness for particular purpose of its content and the products and services presented therein Sp...

Отзывы: