APPENDIX A BLOWER PERFORMANCE TABLES - HEAT PUMP
4 Ton Heat Pump
Standard Static Drive
Models: DRH0481D and DRH0483D
Down Flow
Horizontal Flow
SPEED
TAP
EXTERNAL
STATIC
PRESSURE
(ESP),
IN WC
SCFM RPM BHP
SPEED
TAP
EXTERNAL
STATIC
PRESSURE
(ESP),
IN WC
SCFM RPM BHP
T1
0.2
1025 559 0.13
T1
0.2
1046 595 0.14
0.4
893
650 0.15
0.4
911
691 0.16
0.6
755
735 0.17
0.6
770
782 0.19
0.8
622
820 0.20
0.8
635
872 0.21
1.0
-
-
-
1.0
-
-
-
T2
0.2
1699 771 0.46
T2
0.2
1733 819 0.49
0.4
1625 833 0.50
0.4
1659 885 0.53
0.6
1536 879 0.53
0.6
1567 934 0.56
0.8
1437 935 0.56
0.8
1466 993 0.60
1.0
1293 1007 0.60
1.0
1319 1070 0.64
T3
0.2
1607 746 0.36
T3
0.2
1640 793 0.38
0.4
1519 787 0.37
0.4
1550 836 0.40
0.6
1419 859 0.41
0.6
1448 913 0.43
0.8
1259 932 0.44
0.8
1285 990 0.47
1.0
1175 992 0.47
1.0
1199 1054 0.50
T4
0.2
1783 815 0.54
T4
0.2
1819 866 0.58
0.4
1713 870 0.58
0.4
1748 924 0.62
0.6
1642 889 0.59
0.6
1676 945 0.63
0.8
1543 963 0.64
0.8
1574 1023 0.68
1.0
1428 1015 0.68
1.0
1457 1078 0.72
T5
0.2
1846 838 0.64
T5
0.2
1883 890 0.68
0.4
1775 904 0.69
0.4
1812 960 0.73
0.6
1701 922 0.70
0.6
1736 980 0.75
0.8
1630 973 0.74
0.8
1664 1034 0.79
1.0
1513 1028 0.78
1.0
1544 1092 0.83
Shaded area indicates air flow below 1200 SCFM (300 SCFM/ton)
that is not recommended for High Stage cooling or heating
4 Ton Heat Pump
Standard Static Drive
Models: DRH0484D and DRH0487D
Down Flow
Horizontal Flow
SPEED
TAP
EXTERNAL
STATIC
PRESSURE
(ESP),
IN WC
SCFM RPM BHP
SPEED
TAP
EXTERNAL
STATIC
PRESSURE
(ESP),
IN WC
SCFM RPM BHP
T1
0.2
1025 560 0.12
T1
0.2
1046 595 0.13
0.4
893
650 0.14
0.4
911
691 0.15
0.6
755
736 0.16
0.6
770
782 0.17
0.8
622
821 0.18
0.8
635
872 0.19
1.0
500
874 0.19
1.0
510
929 0.20
T2
0.2
1817 796 0.44
T2
0.2
1854 846 0.46
0.4
1736 824 0.45
0.4
1771 876 0.48
0.6
1677 863 0.47
0.6
1711 917 0.50
0.8
1598 911 0.50
0.8
1631 968 0.53
1.0
1517 964 0.53
1.0
1548 1024 0.56
T3
0.2
1588 732 0.31
T3
0.2
1620 778 0.33
0.4
1510 793 0.34
0.4
1541 843 0.36
0.6
1432 838 0.36
0.6
1462 890 0.38
0.8
1347 894 0.38
0.8
1375 950 0.41
1.0
1197 974 0.42
1.0
1221 1035 0.44
T4
0.2
1817 796 0.44
T4
0.2
1854 846 0.46
0.4
1736 824 0.45
0.4
1771 876 0.48
0.6
1677 863 0.47
0.6
1711 917 0.50
0.8
1598 911 0.50
0.8
1631 968 0.53
1.0
1517 964 0.53
1.0
1548 1024 0.56
T5
0.2
1918 817 0.50
T5
0.2
1957 868 0.53
0.4
1842 839 0.51
0.4
1880 891 0.54
0.6
1769 894 0.54
0.6
1805 950 0.58
0.8
1702 935 0.57
0.8
1737 993 0.60
1.0
1623 983 0.60
1.0
1657 1044 0.63
Shaded area indicates air flow below 1200 SCFM (300 SCFM/ton)
that is not recommended for High Stage cooling or heating