Ignition Control Module for Gas Furnace
Figure 35: Typical Staged Gas Furnace Electrical Schematic with Sensor
Ignition Control Module LED Diagnostics
The following LED indicators can be used to diagnose faults associated with the staged gas furnace.
Table 19: LED Indicator and Fault Conditions
Figure 36: Utec 1016-400 Wiring
Indicator
Fault Condition
Steady Off
No power or control hardware fault
Steady On
Power applied, control OK
1 Flash
Combustion fan motor energized, pressure switch open
2 Flashes
Combustion fan motor off, pressure switch closed
3 Flashes
Ignition lockout from too many trials
4 Flashes
Ignition lockout from too many flame losses within single call for heat
5 Flashes
Control hardware fault detected