Modulating Hot Gas Reheat
The reheat coil option comes complete with an aluminum
micro channel coil and modulating hot gas valves for leaving
air temperature control. On a call for dehumidification, the unit
will enable the supply to be over-cooled by the DX coil. Hot
gas from the unit condenser will be routed to an indoor coil
downstream of the DX coil to reheat the air. Hot gas reheat
) will control how much hot gas is routed to
the indoor coil to maintain a discharge air setpoint.
Figure 25: Dual 2-Way Valve Refrigeration Schematic (Cooling Model Shown)