Table 8: Electric Heat Data
1
Table 9: Amp Draw Data
kW
Voltage
Amps
kW
Voltage
Amps
6
208
16 .7
36
208
99 .9
230
15 .1
230
90 .4
475
7 .3
475
43 .8
575
6 .0
575
36 .1
12
208
33 .3
54
208
149 .9
230
30 .1
230
135 .6
475
14 .6
475
65 .6
575
12 .0
575
54 .2
18
208
50 .0
72
208
N/A
230
45 .2
230
N/A
475
21 .9
475
87 .5
575
18 .1
575
72 .3
30
208
83 .3
230
75 .3
475
36 .5
575
30 .1
NOTE:
1. Maximum temperature rise equals 60ºF
Compressor RLA
Compressor LRA
Compressor Size
Condenser Fan FLA*
Unit
Size
Compressor 1 - Variable
Compressor 3 - Fixed
Compressor 1
Compressor 3
Comp 1
Comp 3
Qty
208
230
460
Voltage
Voltage
Voltage
Voltage
Tons
208
230
460
[%]
208
230
460
208
230
460
208
230
460
[P/N]
[P/N]
3
7 .7
7 .0
3 .5
45 .0%
0 .0
0 .0
0 .0
143 .8 130 .0
65 .0
0 .0
0 .0
0 .0
JT1G
NA
1
0 .9
0 .8
0 .4
4
10 .0
9 .0
4 .5
55 .0%
0 .0
0 .0
0 .0
143 .8 130 .0
65 .0
0 .0
0 .0
0 .0
JT1G
NA
1
0 .9
0 .8
0 .4
5
11 .9
10 .8
5 .4
68 .0%
0 .0
0 .0
0 .0
143 .8 130 .0
65 .0
0 .0
0 .0
0 .0
JT1G
NA
1
2 .0
1 .8
0 .9
6
15 .0
13 .6
6 .8
89 .0%
0 .0
0 .0
0 .0
143 .8 130 .0
65 .0
0 .0
0 .0
0 .0
JT1G
NA
1
2 .0
1 .8
0 .9
7 .5
11 .9
10 .8
5 .4
68 .0%
8 .6
7 .8
3 .9
143 .8 130 .0
65 .0
67 .5
73 .7
37 .1
JT1G
JT71G
2
2 .0
1 .8
0 .9
10
10 .0
9 .0
4 .5
59 .0%
17 .5
15 .8
7 .9
143 .8 130 .0
65 .0
93 .1
84 .2
42 .1
JT1G
JT170G
2
2 .0
1 .8
0 .9
12
15 .0
13 .6
6 .8
89 .0%
17 .5
15 .8
7 .9
143 .8 130 .0
65 .0
93 .1
84 .2
42 .1
JT1G
JT170G
2
2 .0
1 .8
0 .9
15
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
JT150J
JT170G
N/A
N/A
N/A
N/A
Horse Power
Supply Fan FLA
Exhaust Fan FLA
Voltage
Voltage
208
230
460
kW
208
230
460
kW
1 .3
3 .1
2 .8
1 .4
1 .0
3 .1
2 .8
1 .4
1 .0
2 .3
5
4 .6
2 .3
1 .7
5
4 .6
2 .3
1 .7
4
8 .8
7 .4
4 .0
3 .0
8 .8
7 .4
4 .0
3 .0
8
13 .5
12 .2
6 .1
6 .0
—
—
—
—
NOTE:
* Values are for total condenser fan FLA, on 7.5-12 and 15T units the value include both fans
575 Amp Draws: Compressors and motors will be runn off a 575 to 460V transformer. Motors will be nameplated at 460V.
For MCA & MOP calculations the motor's FLA will be multiplier by 80% (575/460) and calculation is run as normal.
IM 1125-6 • REBEL ROOFTOPS 14
www.DaikinApplied.com