background image

50

SERVICING

NOTE:

 At either location, a hose fitting must be installed prior 

to making the hose connection. 

NOTE:

 Use adapter kit #0151K00000S to measure gas pres

-

sure on White-Rodgers 36G/J 22 gas valves.

GAS LINE

GAS SHUTOFF VALVE

GAS LINE  

TO FURNACE

DRIP LEG CAP 

WITH FITTING

MANOMETER HOSE

MANOMETER

OPEN TO 

ATMOSPHERE

Measuring Inlet Gas Pressure

(Alternate Method)

3.  Turn ON the gas and electrical power supply and operate 

the furnace and all other gas consuming appliances on 

the same gas supply line.

4.  Measure furnace gas supply pressure with burners firing. 

Supply pressure must be within the range specified in the 

following table. 

Natural Gas

Minimum:  4.5" w.c.

Maximum: 10.0" w.c.

Propane Gas Minimum: 11.0" w.c. Maximum: 13.0" w.c.

INLET GAS SUPPLY PRESSURE

If  supply  pressure  differs  from  above,  make  necessary 

adjustments to pressure regulator, gas piping size, etc., and/

or consult with local gas utility.

WARNING

HIGH

 

VOLTAGE

D

ISCONNECT 

ALL

  ELECTRICAL POWER AND  SHUT OFF GAS

SUPPLY  BEFORE SERVICING  OR  INSTALLING  THIS UNIT.

M

ULTIPLE  POWER  SOURCES  MAY  BE  PRESENT. 

F

AILURE  TO

DO  SO MAY  CAUSE PROPERTY  DAMAGE,  PERSONAL INJURY OR DEATH.

5.  Disconnect manometer after turning off gas at manual 

shutoff  valve.  Reinstall  plug  before  turning  on  gas  to 

furnace.

6.  Turn OFF any unnecessary gas appliances started in step 

3. 

7.  Turn on gas to furnace and check for leaks. If leaks are 

found, repair and then reinstall burner compartment door.  

8.  Turn on electrical power and verify proper unit operation.

Gas Manifold Pressure Measurement and Adjustment 

T

O  PREVENT  UNRELIABLE OPERATION OR  EQUIPMENT DAMAGE, THE

GAS MANIFOLD  PRESSURE MUST BE  AS  SPECIFIED ON THE  UNIT

RATING  PLATE.  

O

NLY  MINOR ADJUSTMENTS SHOULD BE MADE  BY

ADJUSTING  THE  GAS  VALVE PRESSURE REGULATOR.

CAUTION

NOTE:

  Use  adapter  kit  #0151K00000S  to  measure  gas 

pressure on White-Rodgers 36J22 gas valves.

Only small variations in gas pressure should be made by 

adjusting  the  gas  valve  pressure  regulator.  The  manifold 

pressure must be measured with the burners operating. To 

measure and adjust the manifold pressure, use the following 

procedure.

WARNING

HIGH

 

VOLTAGE

D

ISCONNECT 

ALL

 ELECTRICAL POWER  AND SHUT  OFF  GAS  SUPPLY

BEFORE  SERVICING OR INSTALLING.

1.  After turning off gas to furnace at the manual gas shutoff 

valve external to the furnace, remove burner compartment 

door to gain access to the gas valve.

2.  Connect a calibrated water manometer (or appropriate gas 

pressure gauge) at the gas valve outlet pressure tap.  Refer 

to 

Measuring Gas Pressure: Single Stage Valves

 figure for 

single stage valve outlet pressure tap connections.

L

INE  VOLTAGE  NOW  PRESENT

WARNING

3.  Turn ON the gas and electrical power supply and operate 

the furnace.

4.  Measure gas manifold pressure with burners firing. Adjust 

manifold pressure using the table below.

Natural Gas

3.5" w.c.

Propane Gas

10.0" w.c.

Manifold Gas Pressure

The final manifold pressure must not vary more than ± 0.3 “ 

w.c. from the above specified pressures. Any necessary major 

changes in gas flow rate should be made by changing the size 

of the burner orifice.
5. White-Rodgers 36J22 Valves:

a. Back outlet pressure test screw (inlet/outlet pressure 

boss) out one turn (counterclockwise, not more than 

one turn).

b. Attach a hose and manometer to the outlet pressure  

outlet pressure boss.

c. Turn ON the gas supply.

Содержание DM92SE

Страница 1: ...gov ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL ADJUST SERVICE OR REPAIR HEREINAFTER SERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL SHOULD SERVICE THE EQUIPMENT THE MANUFACTURER WILL NOT BE RESP...

Страница 2: ...S AND SERVICERS RECOGNIZE SAFETY SYMBOLS WORDS AND LABELS Table of Contents IMPORTANT INFORMATION 2 4 PRODUCT IDENTIFICATION 5 8 INSTALLATION CONSIDERATIONS 9 27 SYSTEM OPERATION 28 ACCESSORIES 29 31...

Страница 3: ...ing permanent brain damage or death Advertencia especial para la instalaci n de calentadores manejadoras de aire en reas cerradas como estacionamientos cuartos de servicio B10259 216 El mon xido de ca...

Страница 4: ...manuel D Donotusethisapplianceifanyparthasbeenunderwater position 6 Attendrecinq 5 minutespourlaisser echapper tout le WHAT TO DO IF YOU SMELL GAS 5 Push thegascontrol leverto Position OFF ARRET sett...

Страница 5: ...Revision D Daikin A InitialRelease B 1st Revision Configuration M Upflow Horizontal Major Revision C Downflow Horizontal A InitialRelease B 1st Revision Nox AFUE N Natural Gas 97 97 AFUE X Low NOx 80...

Страница 6: ...2SE0805CN DM92SE1004CN DM92SE1005CN DM92SE1205DN Daikin Brand 92 Single Stage furnace 34 5 tall Upflow Horizontal Installation 1 stage gas valve induced draft Multi speed ECM motor 120 volt nitride ho...

Страница 7: ...Cleaner A high efficiency air filtration device designed to remove dirt dust pollen and other microscopic particles from the air passing through it Flexible perfor mance range up to 2 000 CFM capacity...

Страница 8: ...rminate outside the structure This kit is NOT intended for use with single pipe indirect vent installations 0170K00001S N A Side Wall Only Concentric Vent Kit This kit is to be used with 2 vent system...

Страница 9: ...ols to their containers before touching any ungrounded object Product Application This product is designed for use as a residential home gas furnace It is not designed or certified for use in mobile h...

Страница 10: ...ion Air Pipe Termination Locations section in this manual or the installation in structions to determine if the piping system from furnace to termination can be accomplished within the guidelines give...

Страница 11: ...om of the confined space In a typical construction the clearance between the door and door frame is usually adequate to satisfy this ventilation requirement Furnace Suspension If suspending the furnac...

Страница 12: ...CGA B149 Installation Codes Sections 7 2 7 3 or 7 4 or applicable provisions of the local building codes for determining the combustion air requirements for the appliances Most homes will require out...

Страница 13: ...d by one or more openings in doors or floors having a total minimum free area of 2 in 2 1000 Btu hr 4400 mm2 kW of total input rating of all appliances 9 3 3 Outdoor Combustion Air Outdoor combustion...

Страница 14: ...stalla tions shall provide an adequate supply of combustion ventilation and dilution air and shall be approved by the authority having jurisdiction 9 3 6 Mechanical CombustionAir Supply Where all comb...

Страница 15: ...s recommended Failure to provide proper condensate drainage can result in property damage Leveling Leveling ensures proper condensate drainage from the heat exchanger and induced draft blower For prop...

Страница 16: ...combustion to the outdoors as the vent pipe or flue pipe The pipe that supplies air for combustion to the furnace will be referred to as the intake pipe or combustion air pipe A condensing gas furnace...

Страница 17: ...ING THE RUBBER ELBOW IS NOT DESIGNED TO SUPPORAT A LOAD WHEN THE RUBBER ELBOW IS MOUNTED EXTERNALLY TO THE FURNACE CABINET EXTREME CARE MUST BE TAKEN TO ADEQUATELY SUPPORT FIELD SUPPLIED VENT FLUE PIP...

Страница 18: ...stacles between pipes etc ROOF LINE COMBUSTION AIR INTAKE OPTIONAL Not required for single pipe installation TEE OPTIONAL 96 MAX 3 MIN 12 MIN HEIGHT DIFFERENCE BETWEEN INTAKE AND VENT 12 MIN TO ROOF O...

Страница 19: ...t through the side of the building or run vertically and exit through the roof of the building The pipes may be run through an existing unused chimney however they must extend a minimum of 12 inches a...

Страница 20: ...rmination kit The termination kit must terminate outside the structure and must be installed per the instructions outlined below for vertical or horizontal termination Vertical termination is preferre...

Страница 21: ...horizontally with the left side down there are two options for connecting the vent pipe to the furnace Option 1 Venting may be connected to the furnace vent pipe fitting on the original top now the en...

Страница 22: ...gas and the altitude Refer to the National Fuel Gas Code NFPA 54 ANSI Z223 1 and information provided by the gas supplier to determine the proper orifice size A different pressure switch may be requi...

Страница 23: ...may damage the gas valve and cause subsequent overfiring resulting in heat exchanger failure Disconnect this unit and shutoff valve from the gas supply piping system before pressure testing the suppl...

Страница 24: ...RS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE WHAT TO DO IF YOU SMELL GAS DO NOT TRY TO LIGHT ANY APPLIANCE DO NOT TOUCH ANY ELECTRICAL SWITCH DO NOT USE ANY PHONE IN YOUR BUILDING IMM...

Страница 25: ...the unit rating plate An electrical disconnect must be provided at the furnace location NOTE Line polarity must be observed when making field connections WARNING IN 90 FURNACE UPRIGHT UPFLOW INSTALLAT...

Страница 26: ...n the unit and the utility room wall so the blower will not interfere with combustion air or draft The room closet or alcove must not be used as a return air chamber When the furnace is used in connec...

Страница 27: ...warm up period deliv ering gas to burners to establish flame 6 The control checks for a signal from the flame sensor within seven 4 seconds after the gas valve is ener gized Gas will only continue to...

Страница 28: ...uced draft blower is off it waits until the fault is corrected The diagnostic light code for this problem is 2 flashes The probable cause is either a faulty pressure switch or wiring 4 Pressure Switch...

Страница 29: ...nsult the Installation Instructions IO 635 SIDE WALL VENT KIT 0170K00001S This side wall only vent kit 0170K00001S is to be used with 2 vent systems This kit is NOT intended for use with single pipe i...

Страница 30: ...ive a brief view of the kit and its application See the section in this manual under Vent Flue and Combustion Air Pipe Terminations for more information or consult the Installation and Operating Instr...

Страница 31: ...ACCESSORIES 31 DAIKIN DM92SE Model Furnace Accessories...

Страница 32: ...FURN C P3 2 P1 1 P3 8 REVERSING VALVE OUTPUT BREAK FOR ODT FURNACE DEMAND OUTPUT P1 3 R 24VAC K4 HP CALL FOR FURNACE DURING DEFROST W2 Y2 STAT Y2 FURN CALL FOR COMPRESSOR P2 7 P3 6 VDC Y2 O REVERSING...

Страница 33: ...gle Stage Furnaces Wire as above for GMH AMH GDH AND GCH hybrid furnaces For installations made prior to 2 1 11 TW I L HER O AT CONN C ON 1 H 1 2ND H 2 1 C L Y1 2ND C L Y2 N U R C N C T nning Contro B...

Страница 34: ...is wiring diagram is for reference only Not all wiring is as shown above Refer to the appropriate wiring diagram for the unit being serviced For use only with 80 or 90 Single Stage Furnaces NOTE Not c...

Страница 35: ...TER VOLT OHM METER These then should be wired to the furnace accordingly CHECKING FOR PHASING PRIMARY TO SECONDARY OF UNMARKED TRANSFORMERS If meter reads approximately 96 volts the primary to seconda...

Страница 36: ...9 947 45 20 40 80 160 400 20 45 90 180 360 900 46 78 157 391 21 43 86 171 343 857 47 19 38 76 153 383 22 41 82 164 327 818 48 75 150 375 23 39 78 157 313 783 49 147 367 24 37 75 150 300 750 50 18 36 7...

Страница 37: ...n Control Test Control S 313 Gas Valve or Gas Supply Shut Off Turn Valves to On Position S 317 Faulty Induced Draft Blower Test Induced Draft Motor S 303 Faulty Blower Motor PSC Test Blower Motor PSC...

Страница 38: ...ated control module diagnostic LED is flashing ONE 1 flash 1 FLASH Furnace lockout due to an excessive number of ignition retries 3 total 1 Failure to establish flame Cause may be no gas to burners fr...

Страница 39: ...blower with correct replacement part Induced draft blower and circulation blower runs continuously No furnace operation Integrated control module diagnostic LED is flashing FIVE 5 flashes 5 FLASHES F...

Страница 40: ...l module diagnostic LED is flashing ELEVEN 11 flashes 11 FLASHES Igniter Open Improperly connected igniter Bad igniter Poor unit ground Poor burner ground Check and correct wiring from integrated cont...

Страница 41: ...d low firing rates If converted to L P gas check size of all orifices 2 Remove Draft Inducer Check the integrity of the gasket between the inducer and the collector box cover any air leak here will ha...

Страница 42: ...ECKING PRIMARY LIMIT CONTROL 45 S 302 CHECKING FLAME ROLLOUT CONTROL 46 S 303 INDUCED DRAFT BLOWER MOTOR 47 S 304 CHECKING GAS VALVE REDUNDANT 47 S 305 CHECKING MAIN BURNERS 48 S 306 CHECKING ORIFICES...

Страница 43: ...nsulation of the same gauge or its equivalent CHECKING THERMOSTAT WIRING AND ANTICIPATOR S 3A THERMOSTAT AND WIRING DISCONNECT ALL POWER BEFORE SERVICING WARNING 1 Remove the blower compartment door t...

Страница 44: ...check and or replacement of transformer and check and or repair of control circuit reinstall blower compartment door 8 Turn on electrical power and verify proper unit operation S 16A CHECKING AIR CIRC...

Страница 45: ...OFF ON ON OFF ON Motor Speed HEAT W T1 T2 T3 T4 DEFAULT SETTING FAN MOTOR SPEED DIP SWITCH SETTING S2 3 S2 4 3 4 3 4 3 4 3 4 Position OFF OFF ON OFF OFF ON ON ON Motor Speed FAN G T1 T2 T4 T1 T2 DEFA...

Страница 46: ...y adjusting the circulator blower speed Increase blower speed to reduce temperature rise Decrease blower speed to increase temperature rise Refer to Circulator Blower Speed section in the Product Desi...

Страница 47: ...AVOID POSSIBLE FIRE ONLY RESET THE AUXILIARY LIMIT CONTROL ONCE IF IT SHOULD OPEN A SECOND TIME A QUALIFIED SERVICER MUST DETERMINE WHY THE AUXILIARY LIMIT OPENED BEFORE RESETTING AGAIN To aid in ide...

Страница 48: ...TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH 1 Remove burner compartment door to gain access to the induced draft blower motor 2 Disconnect the motor wire leads from its connection poin...

Страница 49: ...icult to adjust the flame properly WARNING DISCONNECT ALL GAS AND ELECTRICAL POWER SUPPLY 1 Check orifice visually for distortion and or burrs 2 Check orifice size with orifice sizing drills 3 If resi...

Страница 50: ...NT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE THE GAS MANIFOLD PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE ONLY MINOR ADJUSTMENTS SHOULD BE MADE BY ADJUSTING THE GAS VALVE PRESSURE REGULATOR...

Страница 51: ...system j Remove the manometer hose from the hose barb fitting or outlet pressure boss k Remove the 1 8 NPT hose barb fitting from the outlet pressure tap Replace the outlet pressure boss plug and sea...

Страница 52: ...altitude kit for your furnace S 312 CHECKING FOR DELAYED IGNITION Delayed ignition is a delay in lighting a combustible mixture of gas and air which has accumulated in the combustion chamber Furnace d...

Страница 53: ...AMAGE PERSONAL INJURY OR DEATH 1 Connect a micro amp meter in series with this wire and the sensor terminal 2 Be sure the positive side of the meter is to the sensor depending on the model and the neg...

Страница 54: ...erformance Maintenance Improper filter maintenance is the most common cause of inadequate heating or cooling performance Filters should be cleaned permanent or replaced disposable every two months or...

Страница 55: ...e essential in solving abnormal problems however in many instances they may be rented from local sources Proper equipment promotes faster more efficient service and accurate repairs resulting in fewer...

Страница 56: ...U per cubic foot gas and with proper inlet pressures and correct piping size full capacity will be obtained With propane gas no unit gas valve regulator is used however the second stage supply line pr...

Страница 57: ...Y LIMIT AUTO RESET BL PU MANUAL RESET ROLLOUT LIMIT CONTROL S RD OR PK BK WH WH BLOWER INDUCED DRAFT AUXILIARY LIMIT CONTROLS C FS LIMIT CONTROLS AUXILIARY IGNITER HOT SURFACE IND IGN BLWR CIRCULATOR...

Отзывы: