IM
1133-C
DIII-NET COMMUNICATION GATEWAY
26
www.DaikinApplied.com
Figure 35, Confirm Auto Register Changes
Manually Add a Unit to the iTouch Manager
Most Daikin AHU’s are not recognized by the iTM’s Auto Register feature. Because of this, it is often necessary to register a
unit to the iTouch Manager manually. To manually add a unit to the iTM:
1.
Select the “Menu List” button from the bottom of the home screen. See Figure 30.
2.
From the Menu List Screen, tap the 4 corners of the screen to access the service login. See Figure 31.
3.
Enter the password “daikin” and press OK. See Figure 32.
4.
A red frame will appear around the edges of the screen when the service login is active, as seen in Figure 36.
5.
Go to the Service Settings Tab and Select “Mgmt.Pnt DataRegist” See Figure 36.
Figure 36, Service Login Menu List
– Manually Register
6.
Select Add Unit at the bottom of the Management Point Data Register Menu. See Figure 37.
7.
Select Indoor under Management Point Type Menu. See Figure 38.
Note:
AHUs must be registered as indoor units when manually added to be properly recognized by the iTouch Manager.
Service Settings Tab
Management Point
Data Register