ROOF CURB INSTALLATION

ROOF CURB POST-INSTALLATION CHECKS

After installation, check the top of the curb, duct connection frame 

and duct flanges to make sure gasket has been applied properly.  

Gasket should be firmly applied to the top of the curb perimeter, 

duct flanges and any exposed duct connection frame.  If gasket is 

loose, re-apply using strong weather resistant adhesive.

Protrusion

Inspect curb to ensure that none of the utility services (electric) 

routed through the curb protrude above the curb.

CAUTION

If protrusions exist, do not attempt to set unit on curb. 

Information shown. 

ROOF TOP DUCT CONNECTIONS

Install duct connections on the roof curb before placing the unit 

on the rooftop.

NOTE:

 If duct is to be fasten to the roof curb the fasteners need to 

be installed horizontally to allow the unit to be set flat on the curb. 

RIGGING DETAILS

WARNING

To prevent property damage, the unit should remain in an 

upright position during all rigging and moving operations. 

To facilitate lifting and moving when a crane is used, place 

the unit in an adequate cable sling.

CAUTION

Do not lift units two at a time. Provisions for forks have 

been included in the unit base fram. Minimum fork length is 

72” to prevent damage to the unit.

Provisions for forks have been included in the unit base frame.  No 

other fork locations are approved.

WARNING

To prevent possible equipment damage, property damage, 

personal injury or death, the following bullet points must 

be observed when installing the unit.

•  Unit must be lifted by the four lifting holes located at the 

base frame corners.

•  Lifting cables should be attached to the unit with shackles.
•  The distance between the crane hook and the top of the 

unit must not be less than 60”.

•  Two spreader bars must span over the unit to prevent 

damage to the cabinet by the lift cables.  Spreader bars 

must be of sufficient length so that cables do not come 

in contact with the unit during transport.  Remove wood 

struts mounted beneath unit base frame before setting unit 

on roof curb.  These struts  are intended to protect unit 

base frame from fork lift damage.  Removal is accomplished 

by extracting the sheet metal retainers and pulling the 

struts through the base of the unit.  Refer to rigging label 

on the unit. 

Important:

 If using bottom discharge with roof curb, ductwork 

should be attached to the curb prior to installing the unit. Ductwork 

dimensions are shown in Roof Curb Installation Instructions.
Refer to the Roof Curb Installation Instructions for proper curb 

installation. Curbing must be installed in compliance with the Na

-

tional Roofing Contractors Association Manual.
Lower unit carefully onto roof mounting curb. While rigging unit, 

center of gravity will cause condenser end to be lower than supply 

air end.

DFG

Содержание DFC Series

Страница 1: ...on model shown in picture 20 ton model has 4 fans 15 ton model has 3 fans INSTALLATION INSTRUCTIONS 2022 19001 Kermier Rd Waller TX 77484 www daikincomfort com ONLY PERSONNEL THAT HAVE BEEN TRAINED TO...

Страница 2: ...iance REPLACEMENT PARTS Ordering Parts When reporting shortages or damages or ordering repair parts give the complete unit model and serial numbers as stamped on the unit s nameplate Replacement parts...

Страница 3: ...s 4 File the claim with the following supporting documents a Original Bill of Lading certified copy or indemnity bond b Original paid freight bill or indemnity in lieu thereof c Original invoice or ce...

Страница 4: ...rface for service personnel should be provided As indicated on the unit data plate a minimum clearance of 36 to any combustible material is required on the furnace access side of the unit All combusti...

Страница 5: ...d using industry guidelines The duct work must be placed into the roof curb before mounting the package unit Our full perimeter curbs include duct connection frames to be assembled with the curb Canti...

Страница 6: ...uded in the unit base frame No other fork locations are approved WARNING To prevent possible equipment damage property damage personal injury or death the following bullet points must be observed when...

Страница 7: ...ARNING HIGH VOLTAGE TO AVOID PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK DO NOT TAMPER WITH FACTORY WIRING THE INTERNAL POWER AND CONTROL WIRING OF THESE UNITS ARE FACTORY INSTALL...

Страница 8: ...LTAGE TERMINAL LOCATIONS NOTE Depending on the options installed the location of the components may vary in some models WARNING Failure of unit due to operation on improper line voltage or with excess...

Страница 9: ...AWG wire may be required before entering thermostat sub base NOTE Refer to unit wiring diagrams for thermostat hookups CIRCULATING AIR AND FILTERS Ductwork The supply duct from the unit through a wal...

Страница 10: ...d and corresponds with installation instructions All thermostats are mounted and wired in accordance with installation instructions All electric power all gas hot water or steam line connections and t...

Страница 11: ...n by default Taps T1 and T2 are for low cool operation cooling stage 1 and Taps T3 to T5 are for high cool operation cooling stage 2 Taps T6 and T7 are for low heat operation heating stage 1 and taps...

Страница 12: ...ed during heating stage 1 operation Do not move wires WH and BR to the same taps Move PURPLE PU wire from TB1 T3 to T4 or T5 to change blower speed during cooling stage 2 operation Do not move wires Y...

Страница 13: ...heck ing superheat run the unit in cooling for 15 20 minutes or until refrigerant pressures stabilize Use the following guidelines and methods to check unit operation and ensure that the refrigerant c...

Страница 14: ...ards check the power wiring for that motor and correct any leads that have been interchanged at the contactor or at the motor 7 With all safety devices closed the system will continue cooling operatio...

Страница 15: ...E must be completely cleaned following the cleaning procedure This practice must also be performed during short shut down periods where corrosive deposits accumulate on the MCHE Cleaning Procedure Rel...

Страница 16: ...should be increased depending on the level of dirt dust accumulation and the environment e g coastal areas with chlorides and salts or industrial areas with aggressive substances WARNING Field applie...

Страница 17: ...2 0 4 7527 764 782 1 47 1 51 0 6 7247 805 821 1 55 1 58 0 8 6941 848 857 1 63 1 65 1 6620 892 893 1 72 1 72 1 2 6275 946 932 1 82 1 79 T6 T7 T8 T9 T5 T10 DFC1803DStandardStatic T1 T2 T3 T4 SpeedTap St...

Страница 18: ...10162 1132 1061 3 37 3 16 1 10002 1152 1097 3 44 3 27 1 2 9806 1179 1132 3 52 3 38 0 2 10958 1088 1013 3 38 3 15 0 4 10701 1112 1038 3 45 3 22 0 6 10521 1140 1058 3 54 3 29 0 8 10359 1164 1089 3 61 3...

Страница 19: ...0 89 0 88 0 4 8969 851 848 2 78 1 73 0 6 7516 814 811 0 93 0 93 0 6 8688 886 884 2 90 1 80 0 8 7185 852 849 0 97 0 97 0 8 8398 923 920 3 02 1 88 1 6864 887 885 1 01 1 01 1 8132 956 952 3 12 1 94 1 2...

Страница 20: ...6 9153 954 897 2 27 2 13 0 8 8724 966 925 2 19 2 10 0 8 8974 988 942 2 35 2 24 1 8554 992 980 2 25 2 22 1 8814 1013 995 2 41 2 37 1 2 8298 1025 1027 2 33 2 33 1 2 8568 1045 1042 2 48 2 48 1 4 8015 10...

Страница 21: ...1042 3 48 3 25 0 6 8911 930 878 2 11 1 99 0 6 10544 1144 1062 3 57 3 31 0 8 8724 966 925 2 19 2 10 0 8 10382 1168 1093 3 65 3 41 1 8554 992 980 2 25 2 22 1 10209 1190 1123 3 71 3 51 1 2 8298 1025 102...

Страница 22: ...6 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 4200 683 665 13 0 04 0 01 762 747 16 0 11 0 14 850 845 20 0 32 0 34 928 929 23 0 51 0 53 4500 718 695...

Страница 23: ...6 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 4200 683 665 13 0 04 0 01 762 747 16 0 11 0 14 850 845 20 0 32 0 34 928 929 23 0 51 0 53 4500 718 695...

Страница 24: ...4 0 6 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 4200 689 688 17 1 72 0 41 761 770 20 1 89 0 54 836 838 22 1 77 0 60 994 948 27 2 26 0 81 4500 704...

Страница 25: ...RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 5600 881 830 35 0 98 0 93 937 886 36 1 12 1 06 990 947 38 1 26 1 21 1039 1000 39 1 41 1 37 6000 907 849...

Страница 26: ...RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 5600 881 830 35 0 98 0 93 937 886 36 1 12 1 06 990 947 38 1 26 1 21 1039 1000 39 1 41 1 37 6000 907 849...

Страница 27: ...M1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 RPM1 RPM2 DDC BHP1 BHP2 5600 775 789 22 0 86 0 88 842 861 24 0 99 1 04 889 918 27 1 14 1 21 938 985 30 1 31 1 41 6000 789 797 25 0...

Страница 28: ...RE DROP SCFM 4500 5000 5500 6000 6500 7000 7500 8000 8500 9000 9500 10000 In WG 0 15 0 18 0 22 0 27 0 32 0 37 0 42 0 48 0 55 0 61 0 69 0 76 Airflow Pressure Drop of Downflow Economizer for 15 to 25 To...

Страница 29: ...00 9 6 8 7 4 8 204 192 225 200 9 6 8 7 13 9 216 203 225 225 44 4 50 2 4 46 8 50 8 1 52 5 60 4 3 48 7 60 4 3 2 4 51 1 60 4 3 8 1 56 8 60 61 3 70 2 4 64 3 70 8 1 71 4 80 4 3 66 7 70 4 3 2 4 69 7 70 4 3...

Страница 30: ...7 189 211 200 225 9 6 8 7 4 8 195 217 200 225 9 6 8 7 13 9 207 229 225 250 103 103 125 125 4 8 108 108 125 125 13 9 117 117 125 125 9 6 8 7 113 112 125 125 9 6 8 7 4 8 118 117 125 125 9 6 8 7 13 9 127...

Страница 31: ...3 74 8 80 3 5 68 8 70 3 5 2 71 3 80 3 5 8 3 79 2 80 67 9 70 2 70 4 80 8 3 78 3 80 3 5 72 3 80 3 5 2 74 8 80 3 5 8 3 82 7 90 81 8 90 2 84 3 90 8 3 92 2 100 3 5 86 2 90 3 5 2 88 7 90 3 5 8 3 96 5 100 43...

Страница 32: ...8 167 183 200 200 9 6 8 7 13 9 178 194 200 200 186 175 200 175 4 8 192 181 200 200 13 9 204 192 225 200 9 6 8 7 198 186 200 200 9 6 8 7 4 8 204 192 225 200 9 6 8 7 13 9 216 203 225 225 186 209 200 22...

Страница 33: ...89 8 90 8 3 97 7 100 3 5 91 7 100 3 5 2 94 2 100 3 5 8 3 102 110 52 6 60 2 54 6 60 8 3 60 9 70 3 5 56 1 70 3 5 2 58 1 70 3 5 8 3 64 4 70 52 6 60 2 55 1 60 8 3 63 0 70 3 5 57 0 70 3 5 2 59 5 70 3 5 8...

Страница 34: ...NSIONS VERTICAL DISCHARGE TOP VIEW 21 60 7 48 22 NOTE 15 ton models have 3 fans 20 ton models have 4 fans 25 ton models have 5 fans Model A B C D 15 Ton 133 7 8 88 1 2 51 11 16 5 5 32 20 Ton 25 Ton 13...

Страница 35: ...ITIONAL DEVICES IN SERIES PLUG IN JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED CUT WIRE ON THE JUMPER PLUG AND WIRE IT IN SERIES WITH THE SAFETY CI...

Страница 36: ...TAP AT THE FACTORY AND BLACK WIRES TO COM TERMINAL FOR 208V SUPPLY POWER MOVE RED WIRES FROM 240V TAP TO THE 208V TAP SEE CONTROL DIAGRAM FOR CONTROL TRANSFORMER LOW VOLTAGE CONNECTIONS OPTIONAL FACTO...

Страница 37: ...ITIONAL DEVICES IN SERIES PLUG IN JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED CUT WIRE ON THE JUMPER PLUG AND WIRE IT IN SERIES WITH THE SAFETY CI...

Страница 38: ...H VOLTAGE CONNECTIONS RED WIRES CONNECTED TO 240 460 575V TAP AT THE FACTORY AND BLACK WIRES TO COM TERMINAL FOR 208V SUPPLY POWER MOVE RED WIRES FROM 240V TAP TO THE 208V TAP ON BOTH TRANSFORMERS SEE...

Страница 39: ...IES PLUG IN JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED CUT WIRE ON THE JUMPER PLUG AND WIRE IT IN SERIES WITH THE SAFETY CIRCUIT FOR HIGHER TORQU...

Страница 40: ...CTED TO 240 460 575V TAP AT THE FACTORY AND BLACK WIRES TO COM TERMINAL FOR 208V SUPPLY POWER MOVE RED WIRES FROM 240V TAP TO THE 208V TAP ON BOTH TRANSFORMERS SEE CONTROL DIAGRAM FOR CONTROL TRANSFOR...

Страница 41: ...ORMER LINE VOLTAGE CONNECTIONS V2 V1 TB1 AG TB1 ALM ALM CFS TB1 CFS TB1 XS2 TB1 XS2 RSS TB1 RSS TB1 XS2 TB1 LDS LDS TB1 XS2 TB1 AG TB1 CO2 CO2 VIN COM VOUT TB1 AG TB1 IAH TB1 XS2 VIN IAH COM VOUT 1 2...

Страница 42: ...FOR CONTROL TRANSFORMER LOW VOLTAGE CONNECTIONS OPTIONAL FACTORY INSTALLED EQUIPMENT NOTES BC BLOWER CONTACTOR BM BLOWER MOTOR CB CIRCUIT BREAKER CC COMPRESSOR CONTACTOR CCH CRANKCASE HEATER CCX COMPR...

Страница 43: ...ORMER LINE VOLTAGE CONNECTIONS V2 V1 TB1 AG TB1 ALM ALM CFS TB1 CFS TB1 XS2 TB1 XS2 RSS TB1 RSS TB1 XS2 TB1 LDS LDS TB1 XS2 TB1 AG TB1 CO2 CO2 VIN COM VOUT TB1 AG TB1 IAH TB1 XS2 VIN IAH COM VOUT 1 2...

Страница 44: ...TAP ON BOTH TRANSFORMERS SEE CONTROL DIAGRAM FOR CONTROL TRANSFORMER LOW VOLTAGE CONNECTIONS FUSE BLOCKS ARE OPTIONAL FACTORY INSTALLED EQUIPMENT BK OR RD BK RD OR BK RD OR BK OR RD OR BK F1 F1 F1 F2...

Страница 45: ...R LINE VOLTAGE CONNECTIONS V2 V1 TB1 AG TB1 ALM ALM CFS TB1 CFS TB1 XS2 TB1 XS2 RSS TB1 RSS TB1 XS2 TB1 LDS LDS TB1 XS2 TB1 AG TB1 CO2 CO2 VIN COM VOUT TB1 AG TB1 IAH TB1 XS2 VIN IAH COM VOUT 1 2 3 6...

Страница 46: ...CONTROL DIAGRAM FOR CONTROL TRANSFORMER LOW VOLTAGE CONNECTIONS FUSE BLOCKS ARE OPTIONAL 1 2 4 3 BK OR RD BK RD OR BK RD OR BK OR RD F1 F1 F1 F2 F2 F3 F3 F3 POWER WIRING DIAGRAM DFC300 LINE VOLTAGE 20...

Страница 47: ...47...

Страница 48: ...48...

Страница 49: ...49 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 50: ...50 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 51: ...51 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 52: ...form on the following link https daikincomfort com contact us You can also scan the QR code on the right to be directed to the feedback page Our continuing commitment to quality products may mean a c...

Отзывы: