Requirements that must be met
• Cable type: Ordinary tough rubber sheathed cord (60245 IEC 53) equivalent or higher
Ordinary polyvinyl chloride sheathed cord (60227 IEC 53) equivalent or higher
•
Core thickness: 1.0 - 2.0 mm²
• Terminal treatment: Use a round crimp-type terminal (M4) with insulating sleeve.
• Power supply voltage: Single phase 100 to 240 VAC (at 50/60 Hz)
• Voltage fluctuation: ±10% or less
•
Electric power consumption: 23 W
CAUTION
•
The power supply requires circuit breaker (10A) installation and earth wire
connection. After installing a circuit breaker, be sure to connect only the intel-
ligent Touch Manager to it.
•
To prevent accidents due to wire breakage or disconnection, secure the power
supply cables to the blue resin cable mount with cable ties.
•
Be sure to connect the earth wire.
•
For the earth wire, use a green wire with yellow stripes. Do not connect the
earth wire to gas or water pipes, lighting rod, or telephone earth wire.
01_EN_3P291714-1.indd 24