Installation Manual 3P291714-1
DCM601A51 intelligent Touch Manager
13
English
1.4
Determining installation place
Be sure to install the intelligent Touch Manager in a place that meets the conditions
described in 1.4.1 through 1.4.3 below.
1.4.1
Installation place and mounting direction
Below are the description of the installation place and mounting direction. Be sure to
confirm.
•
Installation place: Indoor, free from dust and water splashes
•
Mounting direction: Vertical
1.4.2
Environmental conditions
Make sure that the installation environment meets the following conditions.
•
The ambient temperature must be 0 to 40 °C.
• The ambient humidity must be 85% RH or less (without condensation).
•
There must be no electromagnetic disturbance.
1.4.3
Required space
To install the intelligent Touch Manager, the following space is required. Make sure that
there is a minimum clearance of 30 mm from the top edge, 100 mm from the left side
edge, 30 mm from the right side edge, and 60 mm from the bottom edge of the unit.
<Installation space required for intelligent Touch Manager>
Required installa-
tion space
MONITOR
MONITOR
MONITOR
MONITOR
30mm
100mm
290mm
100mm
60mm
60mm
30mm
243mm
A
B
A Top
B Wall
01_EN_3P291714-1.indd 13
5/18/2011 1:45:51 PM