1.1 Wiring Adaptor for Electrical Appendices (1) <KRP2A61 / KRP2A62 / KRP2A53>
57
ED721208
Adaptor
4
2. Setting control mode selector switch (RS1)
Using control mode selector switch (RS1), select the control mode as described below.
(1) When operating with only individual display function
(2) When operating with constant input from A
Note:
Input B is for forced-OFF. When ON, stop + remote controller is rejected, and input A is ignored. When OFF, even if A
is ON, the contents of when input A is ON, are not achieved. Input A must therefore be re-input.
(3) When operating with momentary input from A
(Use a momentary input of ON time 200 msec or longer.)
For demand control from input B
Forced thermostat OFF command
Forces indoor unit to operate the fan only.
Forced temperature shift command
The indoor unit operates at 2°C higher (cooling) or 2°C lower (heating) than the set temperature.
Note:
In zone control, operation is displayed as long as one indoor unit is running. When in the last command priority mode,
some units are not operating while ON.
In such case, even if input A is ON, the unit and all other units in the same zone will stop.
Position
Function
0
Individual Display (Input Ignored)
CONTROL
MODE
Position
Function
Input A ON
Input A OFF
Input B ON
Operation
or not of
indoor
unit
From Remote
controller
Operation
or not of
indoor
unit
From Remote
controller
Operation or not
of indoor unit
From
Remote
Controller
1
Remote Control
Rejection
ON
Rejection
OFF
Rejection
Forced OFF
Rejection
2
Central Priority
ON
Acceptable
3
Stop by Remote
controller Acceptable
ON
Only Stop
acceptable
4
Remote controller
acceptance / rejection
Permit
Acceptable
Position
Function
Input A ON
Constant Input B ON (Input A is ignored)
Operation or
not of indoor
unit
From Remote controller
Operation or
not of indoor
unit
From Remote controller
5
Remote Control Rejection
ON/OFF
Rejection
Forced OFF
Rejection
6
Last command Priority
ON/OFF
Acceptable
Position
Function when input A is ON
Function when input B is ON
C
Remote controller rejected (Same as position “5”)
Forced thermostat OFF command
D
Forced temperature shift command
E
Last command priority (Same as position “6”)
Forced thermostat OFF command
F
Forced temperature shift command
RS1
RS1
1
Input A
Input B
B1
B2
BC
Содержание DCM601A51
Страница 5: ...1 ED721208 1 Part 1 intelligent Touch Manager ...
Страница 6: ...2 intelligent Touch Manager ED721208 ...
Страница 7: ...3 ED721208 intelligent Touch Manager 1 ...
Страница 8: ...4 intelligent Touch Manager ED721208 ...
Страница 9: ...5 ED721208 intelligent Touch Manager 1 ...
Страница 10: ...6 intelligent Touch Manager ED721208 ...
Страница 11: ...7 ED721208 intelligent Touch Manager 1 ...
Страница 12: ...8 intelligent Touch Manager ED721208 ...
Страница 13: ...9 ED721208 intelligent Touch Manager 1 ...
Страница 14: ...10 intelligent Touch Manager ED721208 ...
Страница 15: ...11 ED721208 intelligent Touch Manager 1 ...
Страница 16: ...12 intelligent Touch Manager ED721208 ...
Страница 17: ...13 ED721208 intelligent Touch Manager 1 ...
Страница 18: ...14 intelligent Touch Manager ED721208 ...
Страница 40: ...36 7 2 Error Code on Initial Setting and Wiring Troubles Fundamental of DIII NET ED721208 ...
Страница 98: ...94 1 7 Adaptor for Wiring KRP1B61 KRP1BA54 B56 BA57 BA59 KRP1C63 C64 Adaptor ED721208 KRP1C63 KRP1C64 ...
Страница 105: ...1 8 External Control Adaptor for Outdoor Unit DTA104A61 DTA104A62 DTA104A53 101 ED721208 Adaptor 4 ...
Страница 403: ......