1.2 Design Precautions
41
ED721208
Power Proportional Distribution (PPD)
3
1.2.3 The Reason why VRV Heat Recovery must not be Included
For Heat Recovery outdoor units, the watthour meter must be independently installed.
(1) For heat recovery, there is a case that the power consumption is less than VRV and VRV Plus.
(2) However, if different systems are put on the one meter, the electric power distribution would be calculated by constant
counting, and the calculation result would then more than the actual value on all indoor units.
Therefore, it is necessary to install the watthour meter independently as shown in Fig. 2.
In addition, the power port No. in Address Table must be different from others. (To be set at test operation)
Fig.1 Not Recommended : Watthour meter is shared.
Fig.2 Recommended : Heat Recovery and other system watthour meter are separated.
Caution:
It is possible to register to the same electric power group for the following combination.
1. VRV, VRVII Heat Pump (R-22, R-407C)
2. VRV Heat Recovery (R-22, R-407C)
3. VRVII, VRVIII Heat Pump (R-410A)
4. VRVII, VRVIII Heat Recovery (R-410A)
When the combination of the above-mentioned is not observed, a correct power proportional distribution calculation
cannot be done.
Watthour meter with pulse output
Not allowed with 1 unit !
WHM
Power supply
three-phase
Electric energy
pulse signal line
VRV
Heat
Pump
VRV
Heat
Recovery
iTM
WHM
WHM
Power supply
three-phase
Electric
energy
pulse
signal line
Watthour meter with pulse output
VRV
Heat
Recovery
VRV
Heat
Pump
iTM
Содержание DCM601A51
Страница 5: ...1 ED721208 1 Part 1 intelligent Touch Manager ...
Страница 6: ...2 intelligent Touch Manager ED721208 ...
Страница 7: ...3 ED721208 intelligent Touch Manager 1 ...
Страница 8: ...4 intelligent Touch Manager ED721208 ...
Страница 9: ...5 ED721208 intelligent Touch Manager 1 ...
Страница 10: ...6 intelligent Touch Manager ED721208 ...
Страница 11: ...7 ED721208 intelligent Touch Manager 1 ...
Страница 12: ...8 intelligent Touch Manager ED721208 ...
Страница 13: ...9 ED721208 intelligent Touch Manager 1 ...
Страница 14: ...10 intelligent Touch Manager ED721208 ...
Страница 15: ...11 ED721208 intelligent Touch Manager 1 ...
Страница 16: ...12 intelligent Touch Manager ED721208 ...
Страница 17: ...13 ED721208 intelligent Touch Manager 1 ...
Страница 18: ...14 intelligent Touch Manager ED721208 ...
Страница 40: ...36 7 2 Error Code on Initial Setting and Wiring Troubles Fundamental of DIII NET ED721208 ...
Страница 98: ...94 1 7 Adaptor for Wiring KRP1B61 KRP1BA54 B56 BA57 BA59 KRP1C63 C64 Adaptor ED721208 KRP1C63 KRP1C64 ...
Страница 105: ...1 8 External Control Adaptor for Outdoor Unit DTA104A61 DTA104A62 DTA104A53 101 ED721208 Adaptor 4 ...
Страница 403: ......