Commissioning Manual EM11A021
DCM601A51 intelligent Touch Manager
75
Starting Leakage Check by manual operation
Start Leakage Check by manual operation.
(15)
(16)
1. Select the target outdoor unit from the Outdoor Unit list
(15)
and touch the
Check Start
button
(16)
. A confirmation dialog appears. Touching the Yes button starts a check to determine whether
the statuses of the target outdoor unit and indoor units registered in the refrigeration system of
the outdoor unit are suitable for starting Leakage Check. If they are in normal status, the
Leakage Check starts.
2. Statuses unsuitable for starting Leakage Check are as follows.
•
Target outdoor unit
Is under maintenance by System Settings.
Is undergoing Leakage Check.
Is experiencing communication error.
Refrigerant Charging Operation is incomplete.
•
Indoor units registered in the same refrigeration system as the target outdoor unit
At least one is experiencing equipment error.
At least one is under maintenance.
At least one is in emergency stop.