4-13 Leakage Check
Leakage Check is a function available in VRV III or later outdoor units. It checks refrigeration
systems for leakage. Leakage Check can be carried our centrally for multiple refrigeration systems
installed in a property by sending instructions from the iTM to the outdoor units via DIII-NET. Using
the Schedule Control function, you can make the outdoor units run Leakage Check at a specified
date and time. You can also run Leakage Check manually on site. Furthermore, Leakage Check
can also be run from the Web Remote Management. (See page 90)
The Leakage Check takes approximately 180 minutes to complete.
Before starting leakage check, inform the user of NOTE described on page 80.
NOTE
The following shows the system configuration diagram.
System Configuration
Multi air conditioners for building
DIII-NET
iTM
DIII-NET
Multi air conditioners
for building
D3Plus adapter for iTM
Refrigerant Charging Operation
•
By schedule
•
Manually
Router
Web Remote Management
HUB
Web Remote Management
LAN port
Scope of this specification
Service person
Service person
By schedule
Manually
internet
intranet