CIRCULATION AIRFLOW DATA
Model
DIP SWITCHES
S2-3 , S2-4
External Static Pressure, (Inches Water Column)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
DM96SE
0403A
OFF OFF
715
666
609
558
500
438
386
333
276
220
ON OFF
1110
1081
1042
1003
965
933
893
856
820
803
OFF ON
1191
1168
1135
1112
1081
1055
1024
998
978
N/A
ON ON
1344
1312
1278
1247
1215
1178
1143
1114
1081
1049
DM96SE
0603B
OFF OFF
785
717
648
587
520
457
400
327
269
206
ON OFF
1240
1194
1153
1104
1069
1019
971
929
893
N/A
OFF ON
1155
1105
1056
1006
958
908
857
808
772
723
ON ON
1384
1338
1300
1257
1215
1169
1125
1080
1040
994
DM96SE
0803B
OFF OFF
747
676
602
529
453
386
329
281
186
N/A
ON OFF
1206
1157
1111
1059
1009
966
913
863
834
784
OFF ON
1149
1095
1051
1003
951
900
845
812
762
707
ON ON
1414
1380
1333
1305
1260
1223
1180
1137
1091
1047
DM96SE
0804C
OFF OFF
1010
935
861
785
721
631
553
483
423
350
ON OFF
1621
1570
1521
1467
1414
1378
1327
1274
1221
1167
OFF ON
1826
1775
1726
1684
1634
1588
1538
1492
1448
1398
ON ON
1843
1798
1753
1710
1666
1618
1574
1526
1481
1432
DM96SE
0805C
OFF OFF
1012
937
861
801
722
630
552
485
420
353
ON OFF
1836
1787
1746
1699
1653
1607
1561
1514
1471
1419
OFF ON
1836
1787
1746
1699
1653
1607
1561
1514
1471
1419
ON ON
2215
2171
2137
2098
2060
2022
1986
1948
1908
1869
DM96SE
1005C
OFF OFF
1012
940
863
800
715
627
561
496
437
374
ON OFF
1826
1783
1730
1685
1642
1596
1548
1504
1455
1406
OFF ON
1602
1556
1510
1460
1411
1372
1315
1261
1207
1156
ON ON
2225
2180
2141
2105
2070
2033
1996
1957
1923
1883
DM96SE
1205D
OFF OFF
1121
1018
933
839
762
671
592
519
447
371
ON OFF
1969
1913
1862
1807
1756
1705
1647
1599
1544
1481
OFF ON
1865
1812
1755
1692
1638
1587
1527
1476
1411
1351
ON ON
2268
2214
2173
2117
2068
2022
1978
1924
1874
1832
¹ at 0.5" ESP
Notes
•
CFM in chart is without filter(s). Filters do not ship with this furnace, but must be provided by the installer. If the furnace requires
two return filters, this chart assumes both filters are installed.
•
All furnaces ship as high-speed cooling and medium-speed heating. Installer must adjust blower cooling & heating speed as needed.
•
For most jobs, about 400 CFM per ton when cooling is desirable.
•
INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE.
•
This chart is for information only. For satisfactory operation, external static pressure should not exceed value shown on the rating plate.
The shaded area indicates ranges in excess of maximum static pressure allowed when heating.
•
The above chart is for U.S. furnaces installed at 0-2000 feet. At higher altitudes, a properly derated unit will have approximately
the same temperature rise at a particular CFM, while ESP at the CFM will be lower.
DM96SE Airflow Data