8
(lbs)
Corner Weight - A
582
645
627
Corner Weight - B
475
527
525
Corner Weight - C
565
589
604
Corner Weight - D
461
481
521
Unit Shipping Weight
2198
2357
2513
Unit Operating Weight
2083
2242
2283
X (Inches)
65"
63"
65.6"
Y (Inches)
40"
40"
40.5"
A* and B* information
DATA
15 Tons 20 Tons 25 Tons
DBG Weights
NOTE:
These weights are without accessories installed.
T
O
PREVENT
SEVERE
DAMAGE
TO
THE
BOTTOM
OF
THE
UNIT
,
DO
NOT
FORK
LIFT
UNIT
AFTER
WOOD
STRUTS
HAVE
BEEN
REMOVED
.
CAUTION
Bring condenser end of unit into alignment with the curb. With
condenser end of the unit resting on curb member and using curb
as a fulcrum, lower opposite end of the unit until entire unit is
seated on the curb. When a rectangular cantilever curb is used,
care should be taken to center the unit. Check for proper alignment
and orientation of supply and return openings with duct.
Rigging Removal
T
O
PREVENT
DAMAGE
TO
THE
UNIT
,
DO
NOT
ALLOW
CRANE
HOOKS
AND
SPREADER
BARS
TO
REST
ON
THE
ROOF
OF
THE
UNIT
.
CAUTION
Remove spreader bars, lifting cables and other rigging equipment.
ELECTRICAL WIRING
HIGH VOLTAGE !
D
ISCONNECT
ALL
POWER
BEFORE
SERVICING
OR
INSTALLING
THIS
UNIT
. M
ULTIPLE
POWER
SOURCES
MAY
BE
PRESENT
. F
AILURE
TO
DO
SO
MAY
CAUSE
PROPERTY
DAMAGE
,
PERSONAL
INJURY
OR
DEATH
.
WARNING
HIGH VOLTAGE !
T
O
AVOID
PERSONAL
INJURY
OR
DEATH
DUE
TO
ELECTRICAL
SHOCK
,
DO
NOT
TAMPER
WITH
FACTORY
WIRING
. T
HE
INTERNAL
POWER
AND
CONTROL
WIRING
OF
THESE
UNITS
ARE
FACTORY
-
INSTALLED
AND
HAVE
BEEN
THOROUGHLY
TESTED
PRIOR
TO
SHIPMENT
. C
ONTACT
YOUR
LOCAL
REPRESENTATIVE
IF
ASSISTANCE
IS
REQUIRED
.
WARNING
T
O
PREVENT
DAMAGE
TO
THE
WIRING
,
PROTECT
WIRING
FROM
SHARP
EDGES
. F
OLLOW
NATIONAL
ELECTRICAL
CODE
AND
ALL
LOCAL
CODES
AND
ORDINANCES
. D
O
NOT
ROUTE
WIRES
THROUGH
REMOVABLE
ACCESS
PANELS
.
CAUTION
C
ONDUIT
AND
FITTINGS
MUST
BE
WEATHER
-
TIGHT
TO
PREVENT
WATER
ENTRY
INTO
THE
BUILDING
.
CAUTION
For unit protection, use a fuse or HACR circuit breaker that is in ex-
cess of the circuit ampacity, but less than or equal to the maximum
overcurrent protection device. DO NOT EXCEED THE MAXIMUM
OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA PLATE.
All line voltage connections must be made through weatherproof
fittings. All exterior power supply and ground wiring must be in
approved weatherproof conduit.
The main power supply wiring to the unit and low voltage wiring
to accessory controls must be done in accordance with these in-
structions, the latest edition of the National Electrical Code (ANSI/
NFPA 70), and all local codes and ordinances.
The main power supply shall be three-phase, three wire. The unit
is factory wired for the voltage shown on the unit’s data plate.
NOTE:
If supply voltage is 208V, all leads on primary of trans-
former(s) must be moved from the 230V to the 208V tap.
Main power wiring should be sized for the minimum circuit am-
pacity shown on the unit’s database. Size wires in accordance with
the ampacity tables in Article 310 of the National Electrical Code.
If long wires are required, it may be necessary to increase the wire
size to prevent excessive voltage drop. Wires should be sized for a
maximum of 3% voltage drop.
T
O
AVOID
PROPERTY
DAMAGE
OR
PERSONAL
INJURY
DUE
TO
FIRE
,
USE
ONLY
COPPER
CONDUCTORS
.
CAUTION
T
O
PREVENT
IMPROPER
AND
DANGEROUS
OPERATION
DUE
TO
WIRING
ERRORS
,
LABEL
ALL
WIRES
PRIOR
TO
DISCONNECTION
WHEN
SERVICING
CONTROLS
. V
ERIFY
PROPER
OPERATION
AFTER
SERVICING
.
CAUTION