5 Energy saving tips

Operation manual

14

EABH/X16DF6V(7)+9W(7) + EAVH/

X16S(U)18+23DA6V(7)+9W(7)

Daikin Altherma 3 H F+W

4P644480-1A – 2021.09

4.9

Installer settings: Tables to be

filled in by installer

4.9.1

Configuration wizard

Setting

Fill in…

System

Indoor unit type

 (read only)

Backup heater type

 [9.3.1]

Domestic hot water

 [9.2.1]

Emergency

 [9.5]

Number of zones

 [4.4]

Backup heater

Voltage

 [9.3.2]

Configuration

 [9.3.3]

Capacity step 1

 [9.3.4]

Additional capacity step 2

[9.3.5] (if applicable)

Main zone

Emitter type

 [2.7]

Control

 [2.9]

Setpoint mode

 [2.4]

Schedule

 [2.1]

Additional zone

 (only if [4.4] = 1)

Emitter type

 [3.7]

Control

 (read only) [3.9]

Setpoint mode

 [3.4]

Schedule

 [3.1]

Tank

Heat up mode

 [5.6]

Comfort setpoint

 [5.2]

Eco setpoint

 [5.3]

Reheat setpoint

 [5.4]

4.9.2

Settings menu

Setting

Fill in…

Main zone

Thermostat type

 [2.A]

Additional zone

 (if applicable)

Thermostat type

 [3.A]

Information

Dealer information

 [8.3]

5

Energy saving tips

Tips about room temperature

▪ Make sure the desired room temperature is NEVER too high (in

heating  mode)  or  too  low  (in  cooling  mode),  but  ALWAYS

according to your actual needs. Each saved degree can save up

to 6% of heating/cooling costs.

▪ Do  NOT  increase/decrease  the  desired  room  temperature  to

speed up space heating/cooling. The space will NOT heat up/cool

down faster.

▪ When  your  system  layout  contains  slow  heat  emitters  (example:

underfloor  heating),  avoid  large  fluctuation  of  the  desired  room

temperature and do NOT let the room temperature drop too low/

rise  too  high.  It  will  take  more  time  and  energy  to  heat  up/cool

down the room again.

▪ Use a weekly schedule for your normal space heating or cooling

needs. If necessary, you can easily deviate from the schedule:
▪ For  shorter  periods:  You  can  overrule  the  scheduled  room

temperature  until  the  next  scheduled  action. 

Example: 

When

you have a party, or when you are leaving for a couple of hours.

▪ For longer periods: You can use the holiday mode.

Tips about DHW tank temperature

▪ Use a weekly schedule for your normal domestic hot water needs

(ONLY in scheduled mode).
▪ Program to heat up the DHW tank to a preset value (

Comfort

 =

higher DHW tank temperature) during the night, because then

space heating demand is lower.

▪ If  heating  up  the  DHW  tank  once  at  night  is  NOT  sufficient,

program to additionally heat up the DHW tank to a preset value

(

Eco

 = lower DHW tank temperature) during the day.

▪ Make  sure  the  desired  DHW  tank  temperature  is  NOT  too  high.

Example: 

After installation, lower the DHW tank temperature daily

by 1°C and check if you still have enough hot water.

▪ Program  to  turn  ON  the  domestic  hot  water  pump  ONLY  during

periods of the day when instant hot water is necessary. 

Example:

In the morning and evening.

6

Maintenance and service

6.1

Overview: Maintenance and

service

The installer has to perform a yearly maintenance. You can find the

contact/helpdesk number via the user interface.
As end user, you have to:
▪ Keep the area around the unit clean.
▪ Keep the user interface clean with a soft damp cloth. Do NOT use

any detergents.

▪ Regularly check if the water pressure is above 1 bar.

Refrigerant

This  product  contains  fluorinated  greenhouse  gases.  Do  NOT  vent

gases into the atmosphere.
Refrigerant type: R32
Global warming potential (GWP) value: 675

NOTICE

Applicable  legislation  on 

fluorinated  greenhouse  gases

requires that the refrigerant charge of the unit is indicated

both in weight and CO

2

 equivalent.

Formula  to  calculate  the  quantity  in  CO

2

  equivalent

tonnes:

  GWP  value  of  the  refrigerant  ×  total  refrigerant

charge [in kg] / 1000
Please contact your installer for more information.

WARNING: FLAMMABLE MATERIAL

The refrigerant inside this unit is mildly flammable.

Содержание Daikin Altherma 3 H F+W

Страница 1: ...ration manual Daikin Altherma 3 H F W EABH16DF6V 7 EABH16DF9W 7 EABX16DF6V 7 EABX16DF9W 7 EAVH16S18DA6V 7 EAVH16S23DA6V 7 EAVH16S18DA9W 7 EAVH16S23DA9W 7 EAVX16S18DA6V 7 EAVX16S23DA6V 7 EAVX16S18DA9W...

Страница 2: ...Check if he has filled in the installer settings tables If NOT request him to do so Keep the documentation for future reference Target audience End users Documentation set This document is part of a d...

Страница 3: ...refrigerant of oil and of other parts MUST be done by an authorised installer and MUST comply with applicable legislation Units MUST be treated at a specialised treatment facility for reuse recycling...

Страница 4: ...the heat emitters or collectors 3 About the system Depending on the system layout the system can Heat up a space Cool down a space if a heating cooling heat pump model is installed Produce domestic ho...

Страница 5: ...to show a help text related to the current page if available e Right dial The LCD shows an arc on the right side of the display when you can use the right dial Turn then press the right dial Change a...

Страница 6: ...Space heating cooling a Selected submenu Possible actions on this screen Go through the list Enter the submenu Enable disable breadcrumbs Submenu Description 0 or Malfunctioning Restriction Only displ...

Страница 7: ...4 Detailed screen with values Example a b c a b c 7 2 1 Time date Hours 11 30 Minutes a Settings b Values c Selected setting and value Possible actions on this screen Go through the list of settings...

Страница 8: ...on mode to use To tell the system which space operation to use you can You can Location Check which space operation mode is currently used Home screen Set the space operation mode permanently Main men...

Страница 9: ...FORMATION When the DHW tank mode is reheat the risk for capacity shortage and comfort problem is significant In case of frequent reheat operation space heating cooling function is regularly interrupte...

Страница 10: ...nformation To change the user permission level You can change the user permission level as follows 1 Go to B User profile User profile B 2 Enter the applicable pin code for the user permission level B...

Страница 11: ...ious action 4 Confirm the changes Result The schedule for Monday is defined The value of the last action is valid until the next programmed action In this example Monday is the first day you programme...

Страница 12: ...Thu Tue Sun User defined 1 2 Select Rename Delete Rename Select 3 optional To delete the current schedule name browse through the character list until is displayed then press to remove the previous ch...

Страница 13: ...ule 7 User settings Language Time date Holiday Quiet Electricity price Gas price 8 Information Energy data Malfunction history Dealer information Sensors Actuators Operation modes About Connection sta...

Страница 14: ...he scheduled room temperature until the next scheduled action Example When you have a party or when you are leaving for a couple of hours For longer periods You can use the holiday mode Tips about DHW...

Страница 15: ...en 7 2 Symptom You are feeling too cold hot in your living room Possible cause Corrective action The desired room temperature is too low high Increase decrease the desired room temperature See 4 4 2 T...

Страница 16: ...If hydraulic balancing is not sufficient change the pump limitation settings 9 0D and 9 0E if applicable Various malfunctions Check if or is displayed on the home screen of the user interface See 7 1...

Страница 17: ......