4 Installation

Installation manual

20

D2C20ND0 D2C24ND035A5AA

Wall-mounted condensing boiler

3P469346-10J – 2018.05

h

L

i

j

a

b

c

b

d
e
f

g

a

Flex kit PP Dn 60-80 or Dn 80

b

Spacer

c

Extension Flex PP 80 mm

d

Connector Flex-Flex PP 80 mm

e

Chimney connection 60/100 or 80/125

f

90° elbow 60/100 (boiler outlet)

Optional:

g

Inspection elbow 60/100

h

30° elbow 60/100

i

45° elbow 60/100

j

Extension 80/125
L = 500-1000 mm

Instead of 60/100, 80/125 flue ducts can be used at the outlet of the
boiler. In that case, the parts below are used:

a

b

c

d

e

a

60/100 to 80/125 adapter

b

90° elbow 80/125

c

45° elbow 80/125

d

30° elbow 80/125

e

Extension 80/125
L = 500-1000 mm

Allowable flue length for C93x

Shaft

Chimney

cross-

section

Parameter

C3

“3”

“5”

60-100
Concentric

circular and smooth

100

8.0

21

DN 60 Flex

circular and rough

106

3.7

9.8

DN 60 Flex

circular and rough

100

2.7

7.0

DN 60 Flex

square and rough

95

3.8

9.9

DN 60 Flex

square and rough

90

2.8

7.4

80-125
Concentric

circular and smooth

124

34

100

DN 80 Flex

circular and rough

140

18.2

53.5

Allowable flue length for C93x

DN 80 Flex

circular and rough

130

11.6

34.1

DN 80 Flex

circular and rough

120

4.4

13.0

DN 80 Flex

square and rough

140

23.8

69.9

DN 80 Flex

square and rough

130

20.6

60.6

DN 80 Flex

square and rough

120

14.8

43.5

DN 80 Star

square and rough

140

58

169.5

DN 80 Star

square and rough

120

40.7

119.0

Equivalent length of options

45° elbow 60/100 mm

1.0 m

90° elbow 60/100 mm

1.5 m

45° elbow 80/125 mm

1.0 m

90° elbow 80/125 mm

1.5 m

Maximum  allowable  length  of  the  flue  duct  up  to  common
chimney is 2  1 60/100 90° elbow.

Subtract  equivalent  length  value  of  bends  from  the  allowable  flue
length value.

Type B53 (open flue system)

The  boiler  draws  combustion  air  from  the  installation  room  and
expels flue gas through the flue to above the roof (1).

The  boiler  draws  combustion  air  from  the  installation  room  and
routes flue gas through the moisture-resistant chimney to above the
roof (2).

Allowable flue length for B53

Flue duct 60 mm

15.0 m

Flue duct 80 mm

100.0 m

Equivalent length of options

90° elbow 60 mm

1.5 m

45° elbow 60 mm

1.0 m

90° elbow 80 mm

2.0 m

45° elbow 80 mm

1.0 m

Subtract  equivalent  length  value  of  bends  from  the  allowable  flue
length value.

Содержание D2C20ND028A5AA

Страница 1: ...Installation manual Wall mounted condensing boiler English Manuel d installation Chaudi re murale condensation Fran ais Installation manual Wall mounted condensing boiler D2C20ND028A5AA D2C24ND035A5AA...

Страница 2: ...tiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lie...

Страница 3: ...commission the domestic hot water 25 6 Hand over to the user 25 Disposal Old units must be appropriately disposed of in accordance with local and national regulations The components are easy to separa...

Страница 4: ...ualified person shall explain the operating principles and the use of the unit to the user The user is not allowed to perform any modifications maintenance or repairs on the unit unless otherwise stat...

Страница 5: ...llation Automatic air vents There are two air vents one on the pump other on the heat exchanger They help discharging the air inside the installation and heating circuit to avoid air traps and consequ...

Страница 6: ...vessel 10 litres d Gas valve e Heat exchanger f 3 way valve stepper motor g Domestic hot water temperature sensor h Plate heat exchanger i Safety valve 3 bar j Condensate trap k Ignition transformer...

Страница 7: ...min max m h 0 51 2 04 0 51 2 45 Natural Gas G25 Consumption min max m h 0 59 2 35 0 59 2 85 LPG G31 Consumption min max m h 0 2 0 98 0 2 1 19 Combustion products mass flow rate min max G20 g s 2 2 12...

Страница 8: ...60 C return temperature at heater inlet and 80 C flow temperature at heater outlet b Low temperature means for condensing boilers 30 C for low temperature boilers 37 C and for other heaters 50 C retur...

Страница 9: ...room or compartment it does not require a dedicated ventilation for combustion air If however installed in a room containing a bath or a shower then particular reference is drawn to the current I E E...

Страница 10: ...3 m 1 5 bar h h System water height m p System charge pressure bar According to the graph below there is no need to install an additional expansion vessel for the systems with a water volume in the ar...

Страница 11: ...central heating circuit 0 0 100 200 300 400 500 600 700 800 200 400 600 800 1000 1200 1400 1600 1800 A mbar B l h A Residual pump lift mbar B Flow l h 4 8 Connections NOTICE During installation do no...

Страница 12: ...onger than 1 5 metres The safety valve piping should be connected to a water outlet with an additional hose or piping This outlet should not be installed in places where there is risk of freezing nor...

Страница 13: ...b a L N a b WARNING Do not interchange the supply conductors L and the neutral conductor N DANGER Do not use gas and water pipes for earthing purposes and ensure that they have not been used for this...

Страница 14: ...C20ND028A5AA D2C24ND035A5AA Wall mounted condensing boiler 3P469346 10J 2018 05 4 8 6 Wiring diagram DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes before servicing...

Страница 15: ...temperature sensor Ext1 X8 BCC Boiler Chip Card Ext2 X10 Personal computer production interface Ext3 X1M Daikin room thermostat Ext4 X2M External power output 230 V AC Ext5 X2M Reserved not in use X1...

Страница 16: ...The boiler must be installed so that the terminal is exposed to external air Position of the terminal must allow the free passage of air across it at all times Pluming may occur at the flue terminal P...

Страница 17: ...flue length value Flue length determination Flue duct length L is measured from lip of the elbow to end of the flue terminal L a L Flue duct length a Distance of outer lip of terminal to outer wall a...

Страница 18: ...e flex boiler connection set 100 or 130 b Extension 60 mm c Chimney connection 60 100 d Elbow 60 100 90 Optional e 90 elbow 60 100 f 45 elbow 60 100 g Inspection elbow 60 100 h 30 elbow 60 100 i Exten...

Страница 19: ...45 elbow 80 mm 1 0 m 90 elbow 80 mm 2 0 m Subtract equivalent length value of bends from the allowable flue length value Note The air intake length is 3 metres In case of longer air intake use flue o...

Страница 20: ...ular and rough 140 18 2 53 5 Allowable flue length for C93x DN 80 Flex circular and rough 130 11 6 34 1 DN 80 Flex circular and rough 120 4 4 13 0 DN 80 Flex square and rough 140 23 8 69 9 DN 80 Flex...

Страница 21: ...FGP4661 45 elbow 80 125 EKFGP4811 30 elbow 60 100 EKFGP4664 30 elbow 80 125 EKFGP4814 Extension duct 60 100 500 mm EKFGP4651 1000 mm EKFGP4652 Extension duct 80 125 500 mm EKFGP4801 1000 mm EKFGP4802...

Страница 22: ...t the update process When the app finalizes the update the next screen with the current firmware version appears It will take some time before the adapter finalized the firmware update reboot process...

Страница 23: ...e opened Vent the air from the installation with the manual air vent screws on the radiators Make sure screws are tightened after venting 9 If after the venting the pressure decreases below 0 8 bar re...

Страница 24: ...outlet 5 2 Gas air ratio No need to adjust The installer does not have to adjust the gas air ratio because the boiler has an electronic gas adaptive feature 5 3 To check for gas leakage DANGER Before...

Страница 25: ...weeper mode again press Cancel and Menu buttons together five seconds Sweeper mode will be deactivated and boiler will return to normal operation mode Sweeper mode also finishes automatically after 15...

Страница 26: ...e en service de l eau chaude sanitaire 49 6 Remise l utilisateur 49 Mise au rebut Les anciennes unit s doivent tre mises au rebut correctement conform ment aux r glements locaux et nationaux Les compo...

Страница 27: ...r L utilisateur n est pas autoris effectuer une quelconque modification maintenance ou r paration de l unit sauf mention contraire ou demander des tiers non agr s d effectuer de telles actions Sinon l...

Страница 28: ...Purgeurs d air automatiques Il y a deux purgeurs d air un sur la pompe et un autre sur l changeur de chaleur Ils aident d charger l air l int rieur de l installation et du circuit de chauffage afin d...

Страница 29: ...r pas pas de vanne 3 voies g Capteur de temp rature d eau chaude sanitaire h changeur de chaleur plaques i Vanne de s curit 3 bar j Purgeur de condensat k Transformateur d allumage l Capteur de temp r...

Страница 30: ...in max m h 0 51 2 04 0 51 2 45 Consommation de gaz naturel G25 min max m h 0 59 2 35 0 59 2 85 Consommation de GPL G31 min max m h 0 2 0 98 0 2 1 19 D bit de masse de produits de combustion min max G2...

Страница 31: ...de retour de 60 C l entr e du chauffage et une temp rature du d part de 80 C la sortie du chauffage b Une temp rature faible signifie 30 C pour les chaudi res condensation 37 C pour les chaudi res bas...

Страница 32: ...la mesure applicable Reportez vous la section Espacements d installation minimaux la page 32 Si la chaudi re est install e dans une pi ce ou un compartiment une a ration s par e pour l air comburant n...

Страница 33: ...rature de l eau qui circule dans le circuit La d termination de la hauteur d eau du syst me et de la pression de charge du syst me concern e est indiqu e ci dessous h p 6 m 0 8 bar 7 m 0 9 bar 8 m 1 0...

Страница 34: ...Graphique de rel vement de pompe r siduel Le graphique de rel vement de pompe r siduel montre la quantit de rel vement de pompe mbar qui reste pour le circuit de chauffage central 0 0 100 200 300 400...

Страница 35: ...ges Le circuit de chauffage central doit tre capable de r sister une pression d au moins 6 bar Le branchement crois doit tre privil gi dans les radiateurs d une longueur sup rieure 1 5 m tre La tuyaut...

Страница 36: ...idement Le c ble d alimentation lectrique doit tre au minimum quivalent H05RN F 2451EC57 Conformez vous au point ci dessous lors du c blage au bloc de bornes d alimentation b a L N a b AVERTISSEMENT N...

Страница 37: ...2C24ND035A5AA Chaudi re murale condensation 3P469346 10J 2018 05 4 8 6 Sch ma de c blage DANGER RISQUE D LECTROCUTION D branchez l alimentation lectrique pendant plus de 10 minutes avant d effectuer l...

Страница 38: ...ce pour chaudi re Ext2 X10 Interface de production pour ordinateur personnel Ext3 X1M Thermostat d ambiance Daikin Ext4 X2M Sortie d alimentation ext rieure 230 V c a Ext5 X2M R serv pas en usage X1M...

Страница 39: ...r rapport aux ouvertures pour l a ration doivent tre conformes aux r glementations nationales La chaudi re doit tre install e de mani re exposer le terminal l air externe La position du terminal doit...

Страница 40: ...gment e jusqu 19 9 m tres en r glant le param tre C3 sur 5 Reportez vous aux consignes d entretien pour cette op ration La longueur de ventouse 80 125 peut tre augment e jusqu 99 m tres en r glant le...

Страница 41: ...une valeur de longueur de coudes quivalente de la valeur de longueur de ventouse admissible Syst me de ventouse 80 125 mm Pour augmenter la longueur de conduit de combustion maximale admissible vous p...

Страница 42: ...ion maximale autoris e entre l entr e d air comburant et la sortie de gaz de combustion y compris les pressions du vent 185 Pa pour les mod les D2C T ND028 et D2C T ND035 D bit de masse minimale des p...

Страница 43: ...oivent tre obtenus par l interm diaire de Daikin Dans les unit s de type C83x le flux de condensat n est pas admis dans l unit a b d c d f g L h e a Plaque murale b Rallonge 80 mm c Adaptateur 60 100...

Страница 44: ...yez une valeur de longueur de coudes quivalente de la valeur de longueur de ventouse admissible Type B53 syst me de ventouse ouverte La chaudi re aspire de l air comburant de la pi ce d installation e...

Страница 45: ...54 60 130 EKFGS0257 Raccord de chemin e 60 100 EKFGP4678 80 125 EKFGS4828 Kit de terminal pour toit 80 mm EKFGP6864 Coude 80 mm de 90 EKFGW4085 Coude 80 mm de 45 EKFGW4086 Conduit de rallonge de 80 mm...

Страница 46: ...vous dans l cran d accueil 2 Appuyez sur les r glages partie sup rieure droite de l cran pour afficher l heure et la date de l adaptateur LAN 3 Appuyez sur Heure pour afficher une fen tre de dialogue...

Страница 47: ...8 bar 10 R glez la vanne 8 sur la position arr t D montez la boucle de remplissage si les r glementations locales l exigent 11 V rifiez que le circuit de chauffage central les raccords du circuit en...

Страница 48: ...combustion de la chaudi re 5 2 Rapport gaz air R glage non n cessaire L installateur ne doit pas r gler le rapport gaz air car la chaudi re dispose d une fonctionnalit de gaz adaptatif lectronique 5 3...

Страница 49: ...ouveau les boutons Annuler et Menu appuy s ensemble pendant cinq secondes Le mode ramoneur se d sactive et la chaudi re repasse au mode de fonctionnement normal Le mode ramoneur s arr te aussi automat...

Страница 50: ......

Страница 51: ......

Страница 52: ...MA S STEMLER SAN T C A K kbakkalk y Mah Kay da Cad No 1 Kat 21 22 34750 Ata ehir STANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr 3P469346 10J 2018 05...

Отзывы: